2SK TECH BLOG · LS ELECTRIC M100
LS M100 VFD User Guide: Wiring, Keypad Operation, Speed Settings and Trip Troubleshooting
A practical guide for first installations and on-site checks. Single-phase 200–240 V input · three-phase motor operation · Standard / Advanced I/O.

Product photograph cropped from the original M100 catalogue.
Welcome to 2SK. If RUN does not start your M100 motor or the front dial does not change speed, check the selected run-command and speed-reference sources before assuming a fault.
Based on the M100 Korean user manual V2.2 (14 November 2025) and Korean catalogue (December 2020). Product overview follows the catalogue; operation and parameters follow the manual. Page references are printed page numbers, not PDF viewer positions.
Three Things to Remember First
① M100 takes single-phase power and drives a three-phase motor .
② drv selects start/stop control; Frq selects the speed source .
③ The M100 front dial uses Frq=2 . Do not copy setting numbers from another drive series.
What This Guide Covers
| Topic | Main content |
|---|
| Product and installation | Model codes, Standard/Advanced differences, supply, motor and control wiring |
| Basic operation | Keypad, hidden groups, ENT saving and first run |
| Application | Internal/external potentiometers, 4–20 mA, direction, ramps and preset speeds |
| Checks and management | Current monitoring, RS-485, trip diagnosis, initialization and restart precautions |
01. What Kind of Motor Does M100 Drive?
M100 is a micro drive for speed control in compact machinery. The cited range accepts single-phase 200–240 V and covers 0.1–2.2 kW. Connect a three-phase induction motor with compatible voltage/current to U/V/W.
| Item | M100 specification | Application check |
|---|
| Input supply | Single-phase 200–240 V | Match supply phases/voltage to the drive nameplate |
| Motor | Three-phase induction motor | Not intended for single-phase motors |
| Power range | 0.1 / 0.2 / 0.4 / 0.75 / 1.5 / 2.2kW | Check motor rated current and load as well as kW |
| EMC filter | Built-in C2-class filter | Check applicability to the supply earthing system |
| Braking unit | Built into 1.5–2.2 kW models | Does not mean the braking resistor is included |
| Mounting | Panel and DIN-rail mounting supported | Check dimensions and cooling space |
Single-phase input does not mean a single-phase motor can be connected. For a dual-voltage 220/380 V motor, follow its nameplate and diagram for a connection suited to 200 V-class output. Do not select a 380 V-only motor by simply connecting it.
References: catalogue pp.1–2; manual safety p.iii and p.23.
02. The Final S or A Changes Available Functions

Manual p.2 · Nameplate and model identification
For example, LSLV0022M100-1EOFNS identifies power code 0022, M100 series, single-phase 200–240 V and Standard I/O. S means Standard; A means Advanced. Required signals determine the variant even at the same kW.
| Item | Standard I/O · S | Advanced I/O · A |
|---|
| Multifunction inputs | P1–P3: three inputs | P1–P5: five inputs |
| External voltage input | V1, 0~10V | V1 and I2 voltage mode |
| External current input | No I2 | I2 current input supported |
| Outputs | Relay A1/B1/C1 + Q1/EG open collector | Relay A1/B1/C1 + A2/C2 |
| RS-485 communication | Not supported | Supported |
| RJ45 port | Remote keypad and applicable accessories | Remote keypad, RS-485 and applicable functions |
Questions to Ask During Selection
Alongside “What is the motor kW?”, ask: “Do you need 4–20 mA, PLC communication or additional input contacts?” These questions help avoid ordering the wrong I/O specification.
References: manual pp.2, 24–28.
03. Check Installation and Wiring Before Power-Up
Keep Supply Input and Motor Output Separate
| Terminal | Function | Check |
|---|
| R / T | Single-phase AC supply input | Connect mains only to supply-input terminals |
| U / V / W | Three-phase motor output | Applying mains here can damage the drive |
| Earth terminal | Protective earth | Earth both drive and motor correctly |
| B1 / B2 | Braking resistor connection · 1.5–2.2 kW | Read power-terminal markings; do not confuse with control relay B1 |
Qualified electrical personnel must perform wiring. Internal voltage remains after isolation. Wait at least 10 minutes, then verify DC-bus discharge with suitable test equipment before opening the cover and working. Control terminals must not receive arbitrary voltages.
Do not add power-factor correction capacitors or surge suppressors arbitrarily to the output. Follow the rating-specific instructions for motor wiring, earth, breakers and cables. Never alter wiring during operation.
Compact Drives Still Need Cooling Space
The reference environment is −10 to 50°C, without condensation. Drive ambient temperature inside a closed panel can exceed room temperature. Nearby heat sources and blocked ventilation can cause overtemperature trips and shorten service life.
For side-by-side installation, the manual specifies at least 2 mm between products and removal of the applicable optional top cover. This is not the top/bottom clearance. Follow installation drawings on pp.7–10 for vertical spacing and fans. Also check catalogue life-related guidance for continuous rated-load operation of 0.1–0.2 kW models above 40°C.
References: manual pp.ii–iii, 6–11, 23–33; catalogue p.2.
04. Reading Control Terminals: P1, CM, VR and V1

Manual p.26 · Standard I/O

Manual p.26 · Advanced I/O
| Terminal / switch | Function | Basics |
|---|
| P1 / P2 | Multifunction inputs | Factory functions: P1=FX, P2=RX |
| P3 | Multifunction input | Factory function: output-disable/emergency-stop input |
| P4 / P5 | Additional Advanced inputs | Factory functions: P4=RESET, P5=JOG |
| CM | Contact / analog common | Use according to input mode; distinguish from protective earth |
| VR / V1 / CM | External potentiometer supply / signal / common | VR maximum 12 V; external potentiometer 1–5 kΩ |
| I2 | Advanced current or voltage input | Check SW2 I/V selection together with Frq |
| SW1 | NPN / PNP selection | Match PLC output type and contact wiring |
| AO | Analog output | 0–10 V monitoring signal, such as frequency |
The later P1–CM example assumes SW1=NPN and P1 assigned to FX. PNP wiring differs. For a PLC, establish sink/source and common arrangements before using any NPN example.
A1/B1/C1 are relay-contact terminals, not supply inputs. Even if another device uses A1/A2 for power, read the M100-specific terminal definitions.
References: manual pp.24–31.
05. Understanding the Keypad Display and Buttons

Manual p.39 · Original keypad diagram with margins cropped
| Indicator / button | Function | Remember |
|---|
| SET | Parameter-setting indicator | Flashes during setting |
| RUN indicator | Operating status | On while running; flashes during acceleration/deceleration |
| FWD / REV | Forward / reverse indication | Verify actual machine direction separately |
| RUN key | Run command | Used with keypad control, drv=0 |
| STOP/RESET | Stop or fault reset | Remove the fault cause and check restart conditions before resetting |
| ▲ / ▼ | Navigate codes / change values | Distinguish code selection from value editing |
| MODE/SHIFT | Change group / digit | Moves the edited digit during value entry |
| ENT | Select item / confirm value | Press ENT again when the whole value flashes to save |
| Front potentiometer | Adjust frequency reference | Select Frq=2 on M100 |
Settings Are Not Complete Until the Final ENT
| Step | Keypad action |
|---|
| 1 | Find the code with ▲/▼ → ENT |
| 2 | Change the number with ▲/▼; move digits with MODE/SHIFT if needed |
| 3 | Press ENT to confirm the edited value |
| 4 | When the whole value flashes, press ENT again to save |
| 5 | Return to the code, reopen it and verify the saved value |
A flashing value is easily mistaken for completed saving. Some parameters cannot be changed while running. Stop safely and check the parameter's change conditions if it will not accept a new value.
Cannot See dr, In or Pr? Check OGr
At factory settings, groups beyond the operation group are hidden. Set OGr=1 to access other groups. The communication group appears only on Advanced models, and some codes appear only under specific conditions; skipped numbers do not necessarily indicate a fault.
| Group | Main functions |
|---|
| Operation group | Frequency, ACC, dEC, drv, Frq and basic motor values |
| dr / bA | Operation/control, direction, motor and preset-speed settings |
| Ad / Cn | Ramp patterns, direction restrictions and control functions |
| In / OU | Input signals/terminal functions and output functions |
| CM / AP | Advanced communication / PID control |
| Pr / CF | Protection/trip history and management such as initialization |
References: manual pp.39–50, 190–192.
06. First-Run Essentials: Select drv and Frq Separately
drv selects who starts/stops the motor; Frq selects who sets speed. You can combine keypad run with an external voltage reference, or external run contacts with the front dial.
| Required method | drv | Frq | Additional check |
|---|
| Front RUN + numeric keypad frequency | 0 | 0 | Enter and save frequency directly |
| Front RUN + built-in dial | 0 | 2 | Start with the dial low |
| External forward/reverse switches + numeric speed | 1 | 0 | Check FX/RX assignments and NPN/PNP |
| External switch + external potentiometer / 0–10 V | 1 | 3 | Check VR/V1/CM or V1/CM |
| External switch + 4–20 mA | 1 | 4 | Advanced model, SW2=I and correct input scaling |
| RS-485 run and speed control | 3 | 9 | Advanced model and communication settings required |
A Common Reason RUN Does Nothing
Factory defaults are drv=1 (terminal run) and Frq=0 (keypad frequency) . For a RUN-key test, check drv=0. A zero reference or active stop/protection input can still prevent operation.
Example A: Numeric Speed with RUN-Key Operation
| Stage | Check / action |
|---|
| Preparation | Check wiring, earth and motor ratings; guard rotating parts and remove run commands. |
| 1 | While stopped, save drv=0. |
| 2 | Save Frq=0. |
| 3 | On the frequency screen: ENT → enter target → ENT → when flashing, ENT again. |
| 4 | Press RUN at a low approved test frequency; check direction, noise and current. |
| 5 | Press STOP/RESET and verify normal deceleration and stopping. |
The manual's basic example uses 10 Hz, but this is not suitable for every load. Establish approved test conditions for machines with cooling, lubrication, brakes or minimum-speed requirements.
Example B: Change Speed with the Front Dial
Save drv=0 and Frq=2. Start with a low dial setting, check the frequency display and press RUN. Adjust slowly while monitoring current and machine condition. Turning the dial and issuing RUN are separate actions.
References: manual pp.53–57, 68, 80, 190.
07. External Run Switch and Speed Potentiometer
Start/Stop with an External Switch
With SW1=NPN, P1=FX (In.65=0) and drv=1, a maintained P1–CM contact commands forward operation. ON means run; OFF means stop. This differs from a momentary three-wire pushbutton sequence.
P1 may have been reassigned on an existing machine. Check In.65 and actual wiring rather than assuming P1 always means FX. Also confirm the stop method and deceleration time.
Speed Control with an External Potentiometer or 0–10 V

Manual p.55 · NPN-contact operation example. The 10 Hz value is illustrative.
Use the manual's specified 1–5 kΩ potentiometer. Connect its ends to VR and CM and its wiper to V1, with all power fully isolated. Select Frq=3.
For a PLC/controller 0–10 V output, connect the signal to V1–CM. VR supplies an external potentiometer; it is not the terminal for feeding an external voltage signal.
| V1 code | Function | Factory reference |
|---|
| In.08 / In.09 | Minimum input voltage / corresponding frequency | 0V / 0Hz |
| In.10 / In.11 | Maximum input voltage / corresponding frequency | 10V / 60Hz |
With the listed scaling, 5 V corresponds to 30 Hz. Frequency limits or higher-priority commands can change operation. If full potentiometer travel does not reach the intended speed, check input scaling as well as FrM.
References: manual pp.27, 30–31, 53–55, 69–70, 81.
08. Use Advanced I2 for a 4–20 mA Signal
First confirm an Advanced I/O model when using a current reference from a pressure/flow controller or PLC. Isolate power, select SW2=I, use I2–CM and set Frq=4.
| Code | Item | Manual factory reference |
|---|
| In.53 | Minimum input current | 4.00mA |
| In.54 | Frequency at minimum current | 0.00Hz |
| In.55 | Maximum input current | 20.00mA |
| In.56 | Frequency at maximum current | 60.00Hz |
With this scaling, 12 mA corresponds to 30 Hz. Although the functional range includes 0–20 mA, the factory minimum is 4 mA. Adjust the minimum for a 0–20 mA device. I2 voltage mode instead uses SW2=V and Frq=5.
Check the sensor's two-wire/four-wire power and common arrangement in its own instructions. Incorrect signal-type selection prevents proper speed control.
References: manual pp.27, 71.
09. Direction Settings Depend on the Run-Command Mode
| Mode | Selection | Operation |
|---|
| Keypad: drv=0 | dr.20=F or r | F=forward; r=reverse |
| Terminals: drv=1 | FX and RX are separate run commands | FX only ON=forward; RX only ON=reverse |
| Terminals: drv=2 | FX=run/stop; RX=direction | With FX ON: RX OFF=forward; RX ON=reverse |
With drv=1, both FX/RX ON or both OFF commands stop. Still design the sequence to avoid overlapping commands. dr.20 direction selection applies to drv=0; external-control direction follows the terminal-command arrangement.
If only one direction works, check Ad.09: 0 permits both, 1 prohibits forward and 2 prohibits reverse. Existing restrictions may protect the machine; do not remove them without understanding their purpose.
References: manual pp.80–84.
10. Why Actual Ramp Time Can Differ from ACC/dEC
ACC is acceleration time; dEC is deceleration time. Factory values are 5.0 and 10.0 seconds, but are not universal machine settings. Rapid acceleration of high inertia can cause overcurrent; rapid deceleration can cause overvoltage.
Maximum-Frequency Ramp Example
With bA.09=0, FrM=60 Hz and ACC=5 seconds, the 0→60 Hz reference time is 5 seconds. For a 30 Hz target, ideal linear acceleration takes approximately 2.5 seconds . Actual time can differ with load and control/protection intervention.
Also check bA.09's reference-frequency basis and bA.08's time unit. A different time to the target frequency does not alone indicate a faulty drive.
Check the Rating Before Adding a Braking Resistor
M100 braking units are fitted to 1.5–2.2 kW models. For deceleration trips, first review ramp time, inertia and supply. Select any resistor by the exact model's resistance, power and duty requirements; do not add one arbitrarily or merely raise protection settings.
References: manual pp.23, 86–87, 169, 221; catalogue p.1.
11. Use Preset Speeds for Repeated Speed Selection
For low/medium/high conveyor speeds, set preset frequencies in bA.50–bA.56 and assign speed-selection functions to multifunction inputs.
The manual example uses Advanced P3/P4/P5 for preset-speed selection. Factory assignments are P3 output-disable/emergency-stop, P4 reset and P5 jog; reassigning them removes those roles. Standard has only three inputs, so count run, direction and stop requirements too.
PID, Slip Compensation and Simple Sensorless Control Come After Basic Setup
The manual also covers PID, slip compensation and simple sensorless control. First match nameplate-based MkW, MrC and MbF. PID requires its own setpoint, feedback, units and input-range design.
References: manual pp.78–79, 119–126, 190–195.
12. Monitor Current as Well as Frequency
| Display code | Value | Use |
|---|
| CUr | Output current | Check increased load, mechanical restraint and prolonged running |
| dCL | DC-link voltage | Useful for supply/deceleration issues |
| vOL | Output voltage display | Check the display selection in dr.81 |
| nOn | Current fault state | Check active trips |
| Pr.91~Pr.95 | Trip history | Record repeated fault types and conditions |
Press ENT at CUr to view current. During long low-speed operation, also check motor temperature and cooling. Lower speed can reduce self-fan cooling; slower does not automatically mean less thermal stress.
Before reset, record the code, event timing, frequency and current. Checks differ for acceleration, steady running and stopping.
References: manual pp.58–59, 152–157, 218–225.
13. RS-485 Basics Before PLC/SCADA Connection
RS-485 is available on Advanced I/O. The RJ45-shaped connector is not an Ethernet LAN port. The manual assigns pin 1 to S+ and pin 8 to S−; verify connector orientation and numbering from the original drawing before wiring.
| Code | Function | Manual example |
|---|
| CM.01 | Drive station address | 1; assign unique addresses to multiple drives |
| CM.02 | Protocol | 0=Modbus RTU, 1=LS INV 485 |
| CM.03 | Baud rate | 3=9,600bps |
| CM.04 | Data, parity and stop bits | 0 = 8 data bits, no parity, 1 stop bit |
| drv / Frq | Communication command selection | Run via communication: drv=3 / speed via communication: Frq=9 |
Monitoring-only and communication-based control are different. Reading values does not require switching drv/Frq to communication. Match protocol, address, baud rate and frame format; configure termination using SW3 and the actual network layout.
Check register addressing, read/write permission and scaling rather than copying an address number alone. Begin by reading status, then validate run-command writes under controlled, stopped-machine conditions.
References: manual pp.76, 83, 172–189.
14. Common Trips and First Checks
| Display | Meaning | First checks |
|---|
| OCt | Overcurrent | Short ramp times, excessive load or restarting a rotating motor |
| Ovt | Overvoltage | Rapid deceleration, regenerative load and input voltage |
| Lvt | Undervoltage | Supply, momentary voltage drop and input contactor |
| OLt / EtH | Overload / electronic motor thermal protection | Load, motor ratings, prolonged low-speed operation and cooling |
| OHt | Drive overtemperature | Ambient temperature, ventilation and cooling fan |
| GFt | Output ground fault | Motor and output-cable insulation |
| ESt | Output disabled by stop input | Actual state of the input assigned to output-disable/emergency-stop |
| rOt | Precharge-circuit fault | Input supply and repowering conditions; stop use for inspection if repeated |
A trip identifies a detected condition, not necessarily its root cause. An Ovt indication does not automatically call for drive replacement: establish whether it occurs during deceleration, immediately after power-up or after a load change.
After a Trip
① Remove the run command and stop the machine safely.
② Record code, timing, frequency, current and recent changes.
③ Isolate, verify discharge and perform the required wiring/load checks.
④ Remove the cause, check the area, then reset and test.
⑤ For repeated faults, request professional inspection instead of repeatedly resetting.
No Trip, but the Motor Will Not Run?
Check drv → Frq → target frequency → input assignments → NPN/PNP → stop input → motor/load. Both a run command and valid speed reference are needed. For unchangeable settings, check running restrictions, I/O type, locks and allowed range.
References: manual pp.218–225.
15. Consider Initialization and Automatic Restart Carefully
Record Existing Settings Before CF.93 Initialization
CF.93 initializes parameters; the manual's full-reset example uses CF.93=1. Resetting an installed drive can erase terminal, speed, protection and communication configuration. Record or back up settings and establish a recovery procedure first.
Initialization can return a keypad-controlled drive to factory terminal control. Completing a reset does not mean completing the machine's setup.
Unexpected Movement at Power-Up or After Reset
| Code | Function | Condition to consider |
|---|
| Ad.10 | Start on power-up selection | With drv=1/2 and an active run contact, restarting can occur |
| Pr.08 | Start after trip reset selection | A remaining terminal run command can restart the motor after reset |
Both functions default to 0 in the cited manual. Even in automatic machinery, assess whether movement after power/fault recovery is permitted. A normal stop input or keypad STOP does not complete the machine's safety system.
References: manual pp.52, 84–85.
16. Frequently Asked Questions
Can M100 drive a single-phase motor?
No. The cited manual specifies three-phase motor operation. Single-phase supply input is a separate matter.
The front dial does not change speed.
First check Frq=2. Also check whether external, communication or preset-speed commands are active.
Is Frq=2 for an external potentiometer?
No. M100's external V1 potentiometer uses Frq=3; the built-in dial uses Frq=2. Do not mix parameter numbers between series.
Standard also has RJ45. Does it support communication?
Connector shape alone is insufficient. M100 RS-485 is supported by Advanced I/O models.
The display still says 10.00 after stopping.
The frequency-reference screen can retain the target after stopping. Check RUN indication and actual operation together.
Can I run faster by setting above 60 Hz?
The drive setting range is not the machine's allowable range. Check motor/load ratings, bearings and mechanical speed limits. Analog scaling matters as well as FrM.
Will longer ramp times solve every trip?
No. Causes include load, supply, insulation and cooling. Diagnose from the code and event timing.
Can I reset a used M100 and operate immediately?
A reset does not establish suitability. Inspect model, ratings, condition, wiring, motor data and safety requirements, then enter the required settings.
17. Record These Items Before and After Setup
| Record | Information |
|---|
| Drive and motor | Full M100 model, I/O type, motor kW, voltage, rated current and frequency |
| Basic settings | drv / Frq / ACC / dEC / MkW / MrC / MbF / FrM |
| Site signals | P1–P5 assignments, SW1/SW2 and external-input scaling |
| Operating conditions | Normal frequency/current, rotation and ramp behavior |
| Fault record | Code, timing, recent changes and Pr.91–95 history |
Troubleshooting M100 often comes down to identifying which command it is following. Check model/I/O, select drv and Frq separately, then verify current, direction and stopping behavior.
Information for M100 Selection and Setup Enquiries
Send the full drive model, motor nameplate, switch/potentiometer/PLC signals and intended operating method. For trips, include the code and when it occurs.
M100 product information and quotations →References
① LS ELECTRIC M100 Korean user manual V2.2, 14 November 2025.
② LS ELECTRIC M100 Korean catalogue (04), December 2020.
Product photos and diagrams are excerpts from the original materials. Click images to enlarge. Actual wiring and commissioning must follow the supplied product's nameplate, manual and site design.

#M100 #LSM100 #M100VFD #LSInverter #M100UserGuide #VFDWiring #FrequencySetting #VFDTroubleshooting #LSELECTRIC #2SK
English edition by 2SK. Original catalogue/reference images are retained; some labels within images are in Korean. Read the original Korean article
2SK TECH BLOG · LS ELECTRIC M100
LS M100 VFD User Guide: Wiring, Keypad Operation, Speed Settings and Trip Troubleshooting
A practical guide for first installations and on-site checks. Single-phase 200–240 V input · three-phase motor operation · Standard / Advanced I/O.
Welcome to 2SK. If RUN does not start your M100 motor or the front dial does not change speed, check the selected run-command and speed-reference sources before assuming a fault.
Based on the M100 Korean user manual V2.2 (14 November 2025) and Korean catalogue (December 2020). Product overview follows the catalogue; operation and parameters follow the manual. Page references are printed page numbers, not PDF viewer positions.
① M100 takes single-phase power and drives a three-phase motor .
② drv selects start/stop control; Frq selects the speed source .
③ The M100 front dial uses Frq=2 . Do not copy setting numbers from another drive series.
What This Guide Covers
01. What Kind of Motor Does M100 Drive?
M100 is a micro drive for speed control in compact machinery. The cited range accepts single-phase 200–240 V and covers 0.1–2.2 kW. Connect a three-phase induction motor with compatible voltage/current to U/V/W.
Single-phase input does not mean a single-phase motor can be connected. For a dual-voltage 220/380 V motor, follow its nameplate and diagram for a connection suited to 200 V-class output. Do not select a 380 V-only motor by simply connecting it.
References: catalogue pp.1–2; manual safety p.iii and p.23.
02. The Final S or A Changes Available Functions
For example, LSLV0022M100-1EOFNS identifies power code 0022, M100 series, single-phase 200–240 V and Standard I/O. S means Standard; A means Advanced. Required signals determine the variant even at the same kW.
Alongside “What is the motor kW?”, ask: “Do you need 4–20 mA, PLC communication or additional input contacts?” These questions help avoid ordering the wrong I/O specification.
References: manual pp.2, 24–28.
03. Check Installation and Wiring Before Power-Up
Keep Supply Input and Motor Output Separate
Qualified electrical personnel must perform wiring. Internal voltage remains after isolation. Wait at least 10 minutes, then verify DC-bus discharge with suitable test equipment before opening the cover and working. Control terminals must not receive arbitrary voltages.
Do not add power-factor correction capacitors or surge suppressors arbitrarily to the output. Follow the rating-specific instructions for motor wiring, earth, breakers and cables. Never alter wiring during operation.
Compact Drives Still Need Cooling Space
The reference environment is −10 to 50°C, without condensation. Drive ambient temperature inside a closed panel can exceed room temperature. Nearby heat sources and blocked ventilation can cause overtemperature trips and shorten service life.
For side-by-side installation, the manual specifies at least 2 mm between products and removal of the applicable optional top cover. This is not the top/bottom clearance. Follow installation drawings on pp.7–10 for vertical spacing and fans. Also check catalogue life-related guidance for continuous rated-load operation of 0.1–0.2 kW models above 40°C.
References: manual pp.ii–iii, 6–11, 23–33; catalogue p.2.
04. Reading Control Terminals: P1, CM, VR and V1
The later P1–CM example assumes SW1=NPN and P1 assigned to FX. PNP wiring differs. For a PLC, establish sink/source and common arrangements before using any NPN example.
A1/B1/C1 are relay-contact terminals, not supply inputs. Even if another device uses A1/A2 for power, read the M100-specific terminal definitions.
References: manual pp.24–31.
05. Understanding the Keypad Display and Buttons
Settings Are Not Complete Until the Final ENT
A flashing value is easily mistaken for completed saving. Some parameters cannot be changed while running. Stop safely and check the parameter's change conditions if it will not accept a new value.
Cannot See dr, In or Pr? Check OGr
At factory settings, groups beyond the operation group are hidden. Set OGr=1 to access other groups. The communication group appears only on Advanced models, and some codes appear only under specific conditions; skipped numbers do not necessarily indicate a fault.
References: manual pp.39–50, 190–192.
06. First-Run Essentials: Select drv and Frq Separately
drv selects who starts/stops the motor; Frq selects who sets speed. You can combine keypad run with an external voltage reference, or external run contacts with the front dial.
Factory defaults are drv=1 (terminal run) and Frq=0 (keypad frequency) . For a RUN-key test, check drv=0. A zero reference or active stop/protection input can still prevent operation.
Example A: Numeric Speed with RUN-Key Operation
The manual's basic example uses 10 Hz, but this is not suitable for every load. Establish approved test conditions for machines with cooling, lubrication, brakes or minimum-speed requirements.
Example B: Change Speed with the Front Dial
Save drv=0 and Frq=2. Start with a low dial setting, check the frequency display and press RUN. Adjust slowly while monitoring current and machine condition. Turning the dial and issuing RUN are separate actions.
References: manual pp.53–57, 68, 80, 190.
07. External Run Switch and Speed Potentiometer
Start/Stop with an External Switch
With SW1=NPN, P1=FX (In.65=0) and drv=1, a maintained P1–CM contact commands forward operation. ON means run; OFF means stop. This differs from a momentary three-wire pushbutton sequence.
P1 may have been reassigned on an existing machine. Check In.65 and actual wiring rather than assuming P1 always means FX. Also confirm the stop method and deceleration time.
Speed Control with an External Potentiometer or 0–10 V
Use the manual's specified 1–5 kΩ potentiometer. Connect its ends to VR and CM and its wiper to V1, with all power fully isolated. Select Frq=3.
For a PLC/controller 0–10 V output, connect the signal to V1–CM. VR supplies an external potentiometer; it is not the terminal for feeding an external voltage signal.
With the listed scaling, 5 V corresponds to 30 Hz. Frequency limits or higher-priority commands can change operation. If full potentiometer travel does not reach the intended speed, check input scaling as well as FrM.
References: manual pp.27, 30–31, 53–55, 69–70, 81.
08. Use Advanced I2 for a 4–20 mA Signal
First confirm an Advanced I/O model when using a current reference from a pressure/flow controller or PLC. Isolate power, select SW2=I, use I2–CM and set Frq=4.
With this scaling, 12 mA corresponds to 30 Hz. Although the functional range includes 0–20 mA, the factory minimum is 4 mA. Adjust the minimum for a 0–20 mA device. I2 voltage mode instead uses SW2=V and Frq=5.
Check the sensor's two-wire/four-wire power and common arrangement in its own instructions. Incorrect signal-type selection prevents proper speed control.
References: manual pp.27, 71.
09. Direction Settings Depend on the Run-Command Mode
With drv=1, both FX/RX ON or both OFF commands stop. Still design the sequence to avoid overlapping commands. dr.20 direction selection applies to drv=0; external-control direction follows the terminal-command arrangement.
If only one direction works, check Ad.09: 0 permits both, 1 prohibits forward and 2 prohibits reverse. Existing restrictions may protect the machine; do not remove them without understanding their purpose.
References: manual pp.80–84.
10. Why Actual Ramp Time Can Differ from ACC/dEC
ACC is acceleration time; dEC is deceleration time. Factory values are 5.0 and 10.0 seconds, but are not universal machine settings. Rapid acceleration of high inertia can cause overcurrent; rapid deceleration can cause overvoltage.
With bA.09=0, FrM=60 Hz and ACC=5 seconds, the 0→60 Hz reference time is 5 seconds. For a 30 Hz target, ideal linear acceleration takes approximately 2.5 seconds . Actual time can differ with load and control/protection intervention.
Also check bA.09's reference-frequency basis and bA.08's time unit. A different time to the target frequency does not alone indicate a faulty drive.
Check the Rating Before Adding a Braking Resistor
M100 braking units are fitted to 1.5–2.2 kW models. For deceleration trips, first review ramp time, inertia and supply. Select any resistor by the exact model's resistance, power and duty requirements; do not add one arbitrarily or merely raise protection settings.
References: manual pp.23, 86–87, 169, 221; catalogue p.1.
11. Use Preset Speeds for Repeated Speed Selection
For low/medium/high conveyor speeds, set preset frequencies in bA.50–bA.56 and assign speed-selection functions to multifunction inputs.
The manual example uses Advanced P3/P4/P5 for preset-speed selection. Factory assignments are P3 output-disable/emergency-stop, P4 reset and P5 jog; reassigning them removes those roles. Standard has only three inputs, so count run, direction and stop requirements too.
PID, Slip Compensation and Simple Sensorless Control Come After Basic Setup
The manual also covers PID, slip compensation and simple sensorless control. First match nameplate-based MkW, MrC and MbF. PID requires its own setpoint, feedback, units and input-range design.
References: manual pp.78–79, 119–126, 190–195.
12. Monitor Current as Well as Frequency
Press ENT at CUr to view current. During long low-speed operation, also check motor temperature and cooling. Lower speed can reduce self-fan cooling; slower does not automatically mean less thermal stress.
Before reset, record the code, event timing, frequency and current. Checks differ for acceleration, steady running and stopping.
References: manual pp.58–59, 152–157, 218–225.
13. RS-485 Basics Before PLC/SCADA Connection
RS-485 is available on Advanced I/O. The RJ45-shaped connector is not an Ethernet LAN port. The manual assigns pin 1 to S+ and pin 8 to S−; verify connector orientation and numbering from the original drawing before wiring.
Monitoring-only and communication-based control are different. Reading values does not require switching drv/Frq to communication. Match protocol, address, baud rate and frame format; configure termination using SW3 and the actual network layout.
Check register addressing, read/write permission and scaling rather than copying an address number alone. Begin by reading status, then validate run-command writes under controlled, stopped-machine conditions.
References: manual pp.76, 83, 172–189.
14. Common Trips and First Checks
A trip identifies a detected condition, not necessarily its root cause. An Ovt indication does not automatically call for drive replacement: establish whether it occurs during deceleration, immediately after power-up or after a load change.
① Remove the run command and stop the machine safely.
② Record code, timing, frequency, current and recent changes.
③ Isolate, verify discharge and perform the required wiring/load checks.
④ Remove the cause, check the area, then reset and test.
⑤ For repeated faults, request professional inspection instead of repeatedly resetting.
No Trip, but the Motor Will Not Run?
Check drv → Frq → target frequency → input assignments → NPN/PNP → stop input → motor/load. Both a run command and valid speed reference are needed. For unchangeable settings, check running restrictions, I/O type, locks and allowed range.
References: manual pp.218–225.
15. Consider Initialization and Automatic Restart Carefully
Record Existing Settings Before CF.93 Initialization
CF.93 initializes parameters; the manual's full-reset example uses CF.93=1. Resetting an installed drive can erase terminal, speed, protection and communication configuration. Record or back up settings and establish a recovery procedure first.
Initialization can return a keypad-controlled drive to factory terminal control. Completing a reset does not mean completing the machine's setup.
Unexpected Movement at Power-Up or After Reset
Both functions default to 0 in the cited manual. Even in automatic machinery, assess whether movement after power/fault recovery is permitted. A normal stop input or keypad STOP does not complete the machine's safety system.
References: manual pp.52, 84–85.
16. Frequently Asked Questions
Can M100 drive a single-phase motor?
No. The cited manual specifies three-phase motor operation. Single-phase supply input is a separate matter.
The front dial does not change speed.
First check Frq=2. Also check whether external, communication or preset-speed commands are active.
Is Frq=2 for an external potentiometer?
No. M100's external V1 potentiometer uses Frq=3; the built-in dial uses Frq=2. Do not mix parameter numbers between series.
Standard also has RJ45. Does it support communication?
Connector shape alone is insufficient. M100 RS-485 is supported by Advanced I/O models.
The display still says 10.00 after stopping.
The frequency-reference screen can retain the target after stopping. Check RUN indication and actual operation together.
Can I run faster by setting above 60 Hz?
The drive setting range is not the machine's allowable range. Check motor/load ratings, bearings and mechanical speed limits. Analog scaling matters as well as FrM.
Will longer ramp times solve every trip?
No. Causes include load, supply, insulation and cooling. Diagnose from the code and event timing.
Can I reset a used M100 and operate immediately?
A reset does not establish suitability. Inspect model, ratings, condition, wiring, motor data and safety requirements, then enter the required settings.
17. Record These Items Before and After Setup
Troubleshooting M100 often comes down to identifying which command it is following. Check model/I/O, select drv and Frq separately, then verify current, direction and stopping behavior.
Information for M100 Selection and Setup Enquiries
Send the full drive model, motor nameplate, switch/potentiometer/PLC signals and intended operating method. For trips, include the code and when it occurs.
M100 product information and quotations →References
① LS ELECTRIC M100 Korean user manual V2.2, 14 November 2025.