InverterLS M100 VFD User Guide: Wiring, Keypad Operation, Speed Settings and Trip Troubleshooting

2SK TECH BLOG · LS ELECTRIC M100

LS M100 VFD User Guide: Wiring, Keypad Operation, Speed Settings and Trip Troubleshooting

A practical guide for first installations and on-site checks. Single-phase 200–240 V input · three-phase motor operation · Standard / Advanced I/O.

LS M100 VFD User Guide: Wiring, Settings and Troubleshooting — original reference image 1Product photograph cropped from the original M100 catalogue.

Welcome to 2SK. If RUN does not start your M100 motor or the front dial does not change speed, check the selected run-command and speed-reference sources before assuming a fault.

Based on the M100 Korean user manual V2.2 (14 November 2025) and Korean catalogue (December 2020). Product overview follows the catalogue; operation and parameters follow the manual. Page references are printed page numbers, not PDF viewer positions.

 Three Things to Remember First 
① M100 takes single-phase power and drives a  three-phase motor  .
②  drv selects start/stop control; Frq selects the speed source  .
③ The M100 front dial uses Frq=2 . Do not copy setting numbers from another drive series.

What This Guide Covers

TopicMain content
Product and installationModel codes, Standard/Advanced differences, supply, motor and control wiring
Basic operationKeypad, hidden groups, ENT saving and first run
ApplicationInternal/external potentiometers, 4–20 mA, direction, ramps and preset speeds
Checks and managementCurrent monitoring, RS-485, trip diagnosis, initialization and restart precautions

01. What Kind of Motor Does M100 Drive?

M100 is a micro drive for speed control in compact machinery. The cited range accepts single-phase 200–240 V and covers 0.1–2.2 kW. Connect a three-phase induction motor with compatible voltage/current to U/V/W.

ItemM100 specificationApplication check
Input supplySingle-phase 200–240 VMatch supply phases/voltage to the drive nameplate
MotorThree-phase induction motorNot intended for single-phase motors
Power range0.1 / 0.2 / 0.4 / 0.75 / 1.5 / 2.2kWCheck motor rated current and load as well as kW
EMC filterBuilt-in C2-class filterCheck applicability to the supply earthing system
Braking unitBuilt into 1.5–2.2 kW modelsDoes not mean the braking resistor is included
MountingPanel and DIN-rail mounting supportedCheck dimensions and cooling space

Single-phase input does not mean a single-phase motor can be connected. For a dual-voltage 220/380 V motor, follow its nameplate and diagram for a connection suited to 200 V-class output. Do not select a 380 V-only motor by simply connecting it.

References: catalogue pp.1–2; manual safety p.iii and p.23.

02. The Final S or A Changes Available Functions

LS M100 VFD User Guide: Wiring, Settings and Troubleshooting — original reference image 2Manual p.2 · Nameplate and model identification

For example, LSLV0022M100-1EOFNS identifies power code 0022, M100 series, single-phase 200–240 V and Standard I/O. S means Standard; A means Advanced. Required signals determine the variant even at the same kW.

ItemStandard I/O · SAdvanced I/O · A
Multifunction inputsP1–P3: three inputsP1–P5: five inputs
External voltage inputV1, 0~10VV1 and I2 voltage mode
External current inputNo I2I2 current input supported
OutputsRelay A1/B1/C1 + Q1/EG open collectorRelay A1/B1/C1 + A2/C2
RS-485 communicationNot supportedSupported
RJ45 portRemote keypad and applicable accessoriesRemote keypad, RS-485 and applicable functions
 Questions to Ask During Selection 
Alongside “What is the motor kW?”, ask:  “Do you need 4–20 mA, PLC communication or additional input contacts?”  These questions help avoid ordering the wrong I/O specification.

References: manual pp.2, 24–28.

03. Check Installation and Wiring Before Power-Up

Keep Supply Input and Motor Output Separate

TerminalFunctionCheck
R / TSingle-phase AC supply inputConnect mains only to supply-input terminals
U / V / WThree-phase motor outputApplying mains here can damage the drive
Earth terminalProtective earthEarth both drive and motor correctly
B1 / B2Braking resistor connection · 1.5–2.2 kWRead power-terminal markings; do not confuse with control relay B1

Qualified electrical personnel must perform wiring. Internal voltage remains after isolation. Wait at least 10 minutes, then verify DC-bus discharge with suitable test equipment before opening the cover and working. Control terminals must not receive arbitrary voltages.

Do not add power-factor correction capacitors or surge suppressors arbitrarily to the output. Follow the rating-specific instructions for motor wiring, earth, breakers and cables. Never alter wiring during operation.

Compact Drives Still Need Cooling Space

The reference environment is −10 to 50°C, without condensation. Drive ambient temperature inside a closed panel can exceed room temperature. Nearby heat sources and blocked ventilation can cause overtemperature trips and shorten service life.

For side-by-side installation, the manual specifies at least 2 mm between products and removal of the applicable optional top cover. This is not the top/bottom clearance. Follow installation drawings on pp.7–10 for vertical spacing and fans. Also check catalogue life-related guidance for continuous rated-load operation of 0.1–0.2 kW models above 40°C.

References: manual pp.ii–iii, 6–11, 23–33; catalogue p.2.

04. Reading Control Terminals: P1, CM, VR and V1

LS M100 VFD User Guide: Wiring, Settings and Troubleshooting — original reference image 3 Manual p.26 · Standard I/O LS M100 VFD User Guide: Wiring, Settings and Troubleshooting — original reference image 4Manual p.26 · Advanced I/O
Terminal / switchFunctionBasics
P1 / P2Multifunction inputsFactory functions: P1=FX, P2=RX
P3Multifunction inputFactory function: output-disable/emergency-stop input
P4 / P5Additional Advanced inputsFactory functions: P4=RESET, P5=JOG
CMContact / analog commonUse according to input mode; distinguish from protective earth
VR / V1 / CMExternal potentiometer supply / signal / commonVR maximum 12 V; external potentiometer 1–5 kΩ
I2Advanced current or voltage inputCheck SW2 I/V selection together with Frq
SW1NPN / PNP selectionMatch PLC output type and contact wiring
AOAnalog output0–10 V monitoring signal, such as frequency

The later P1–CM example assumes SW1=NPN and P1 assigned to FX. PNP wiring differs. For a PLC, establish sink/source and common arrangements before using any NPN example.

A1/B1/C1 are relay-contact terminals, not supply inputs. Even if another device uses A1/A2 for power, read the M100-specific terminal definitions.

References: manual pp.24–31.

05. Understanding the Keypad Display and Buttons

LS M100 VFD User Guide: Wiring, Settings and Troubleshooting — original reference image 5Manual p.39 · Original keypad diagram with margins cropped
Indicator / buttonFunctionRemember
SETParameter-setting indicatorFlashes during setting
RUN indicatorOperating statusOn while running; flashes during acceleration/deceleration
FWD / REVForward / reverse indicationVerify actual machine direction separately
RUN keyRun commandUsed with keypad control, drv=0
STOP/RESETStop or fault resetRemove the fault cause and check restart conditions before resetting
▲ / ▼Navigate codes / change valuesDistinguish code selection from value editing
MODE/SHIFTChange group / digitMoves the edited digit during value entry
ENTSelect item / confirm valuePress ENT again when the whole value flashes to save
Front potentiometerAdjust frequency referenceSelect Frq=2 on M100

Settings Are Not Complete Until the Final ENT

StepKeypad action
1Find the code with ▲/▼ → ENT
2Change the number with ▲/▼; move digits with MODE/SHIFT if needed
3Press ENT to confirm the edited value
4When the whole value flashes, press ENT again to save
5Return to the code, reopen it and verify the saved value

A flashing value is easily mistaken for completed saving. Some parameters cannot be changed while running. Stop safely and check the parameter's change conditions if it will not accept a new value.

Cannot See dr, In or Pr? Check OGr

At factory settings, groups beyond the operation group are hidden. Set OGr=1 to access other groups. The communication group appears only on Advanced models, and some codes appear only under specific conditions; skipped numbers do not necessarily indicate a fault.

GroupMain functions
Operation groupFrequency, ACC, dEC, drv, Frq and basic motor values
dr / bAOperation/control, direction, motor and preset-speed settings
Ad / CnRamp patterns, direction restrictions and control functions
In / OUInput signals/terminal functions and output functions
CM / APAdvanced communication / PID control
Pr / CFProtection/trip history and management such as initialization

References: manual pp.39–50, 190–192.

06. First-Run Essentials: Select drv and Frq Separately

drv selects who starts/stops the motor; Frq selects who sets speed. You can combine keypad run with an external voltage reference, or external run contacts with the front dial.

Required methoddrvFrqAdditional check
Front RUN + numeric keypad frequency00Enter and save frequency directly
Front RUN + built-in dial02Start with the dial low
External forward/reverse switches + numeric speed10Check FX/RX assignments and NPN/PNP
External switch + external potentiometer / 0–10 V13Check VR/V1/CM or V1/CM
External switch + 4–20 mA14Advanced model, SW2=I and correct input scaling
RS-485 run and speed control39Advanced model and communication settings required
 A Common Reason RUN Does Nothing 
Factory defaults are  drv=1 (terminal run) and Frq=0 (keypad frequency)  . For a RUN-key test, check drv=0. A zero reference or active stop/protection input can still prevent operation.

Example A: Numeric Speed with RUN-Key Operation

StageCheck / action
PreparationCheck wiring, earth and motor ratings; guard rotating parts and remove run commands.
1While stopped, save drv=0.
2Save Frq=0.
3On the frequency screen: ENT → enter target → ENT → when flashing, ENT again.
4Press RUN at a low approved test frequency; check direction, noise and current.
5Press STOP/RESET and verify normal deceleration and stopping.

The manual's basic example uses 10 Hz, but this is not suitable for every load. Establish approved test conditions for machines with cooling, lubrication, brakes or minimum-speed requirements.

Example B: Change Speed with the Front Dial

Save drv=0 and Frq=2. Start with a low dial setting, check the frequency display and press RUN. Adjust slowly while monitoring current and machine condition. Turning the dial and issuing RUN are separate actions.

References: manual pp.53–57, 68, 80, 190.

07. External Run Switch and Speed Potentiometer

Start/Stop with an External Switch

With SW1=NPN, P1=FX (In.65=0) and drv=1, a maintained P1–CM contact commands forward operation. ON means run; OFF means stop. This differs from a momentary three-wire pushbutton sequence.

P1 may have been reassigned on an existing machine. Check In.65 and actual wiring rather than assuming P1 always means FX. Also confirm the stop method and deceleration time.

Speed Control with an External Potentiometer or 0–10 V

LS M100 VFD User Guide: Wiring, Settings and Troubleshooting — original reference image 6Manual p.55 · NPN-contact operation example. The 10 Hz value is illustrative.

Use the manual's specified 1–5 kΩ potentiometer. Connect its ends to VR and CM and its wiper to V1, with all power fully isolated. Select Frq=3.

For a PLC/controller 0–10 V output, connect the signal to V1–CM. VR supplies an external potentiometer; it is not the terminal for feeding an external voltage signal.

V1 codeFunctionFactory reference
In.08 / In.09Minimum input voltage / corresponding frequency0V / 0Hz
In.10 / In.11Maximum input voltage / corresponding frequency10V / 60Hz

With the listed scaling, 5 V corresponds to 30 Hz. Frequency limits or higher-priority commands can change operation. If full potentiometer travel does not reach the intended speed, check input scaling as well as FrM.

References: manual pp.27, 30–31, 53–55, 69–70, 81.

08. Use Advanced I2 for a 4–20 mA Signal

First confirm an Advanced I/O model when using a current reference from a pressure/flow controller or PLC. Isolate power, select SW2=I, use I2–CM and set Frq=4.

CodeItemManual factory reference
In.53Minimum input current4.00mA
In.54Frequency at minimum current0.00Hz
In.55Maximum input current20.00mA
In.56Frequency at maximum current60.00Hz

With this scaling, 12 mA corresponds to 30 Hz. Although the functional range includes 0–20 mA, the factory minimum is 4 mA. Adjust the minimum for a 0–20 mA device. I2 voltage mode instead uses SW2=V and Frq=5.

Check the sensor's two-wire/four-wire power and common arrangement in its own instructions. Incorrect signal-type selection prevents proper speed control.

References: manual pp.27, 71.

09. Direction Settings Depend on the Run-Command Mode

ModeSelectionOperation
Keypad: drv=0dr.20=F or rF=forward; r=reverse
Terminals: drv=1FX and RX are separate run commandsFX only ON=forward; RX only ON=reverse
Terminals: drv=2FX=run/stop; RX=directionWith FX ON: RX OFF=forward; RX ON=reverse

With drv=1, both FX/RX ON or both OFF commands stop. Still design the sequence to avoid overlapping commands. dr.20 direction selection applies to drv=0; external-control direction follows the terminal-command arrangement.

If only one direction works, check Ad.09: 0 permits both, 1 prohibits forward and 2 prohibits reverse. Existing restrictions may protect the machine; do not remove them without understanding their purpose.

References: manual pp.80–84.

10. Why Actual Ramp Time Can Differ from ACC/dEC

ACC is acceleration time; dEC is deceleration time. Factory values are 5.0 and 10.0 seconds, but are not universal machine settings. Rapid acceleration of high inertia can cause overcurrent; rapid deceleration can cause overvoltage.

 Maximum-Frequency Ramp Example 
With bA.09=0, FrM=60 Hz and ACC=5 seconds, the 0→60 Hz reference time is 5 seconds. For a 30 Hz target, ideal linear acceleration takes  approximately 2.5 seconds  . Actual time can differ with load and control/protection intervention.

Also check bA.09's reference-frequency basis and bA.08's time unit. A different time to the target frequency does not alone indicate a faulty drive.

Check the Rating Before Adding a Braking Resistor

M100 braking units are fitted to 1.5–2.2 kW models. For deceleration trips, first review ramp time, inertia and supply. Select any resistor by the exact model's resistance, power and duty requirements; do not add one arbitrarily or merely raise protection settings.

References: manual pp.23, 86–87, 169, 221; catalogue p.1.

11. Use Preset Speeds for Repeated Speed Selection

For low/medium/high conveyor speeds, set preset frequencies in bA.50–bA.56 and assign speed-selection functions to multifunction inputs.

The manual example uses Advanced P3/P4/P5 for preset-speed selection. Factory assignments are P3 output-disable/emergency-stop, P4 reset and P5 jog; reassigning them removes those roles. Standard has only three inputs, so count run, direction and stop requirements too.

PID, Slip Compensation and Simple Sensorless Control Come After Basic Setup

The manual also covers PID, slip compensation and simple sensorless control. First match nameplate-based MkW, MrC and MbF. PID requires its own setpoint, feedback, units and input-range design.

References: manual pp.78–79, 119–126, 190–195.

12. Monitor Current as Well as Frequency

Display codeValueUse
CUrOutput currentCheck increased load, mechanical restraint and prolonged running
dCLDC-link voltageUseful for supply/deceleration issues
vOLOutput voltage displayCheck the display selection in dr.81
nOnCurrent fault stateCheck active trips
Pr.91~Pr.95Trip historyRecord repeated fault types and conditions

Press ENT at CUr to view current. During long low-speed operation, also check motor temperature and cooling. Lower speed can reduce self-fan cooling; slower does not automatically mean less thermal stress.

Before reset, record the code, event timing, frequency and current. Checks differ for acceleration, steady running and stopping.

References: manual pp.58–59, 152–157, 218–225.

13. RS-485 Basics Before PLC/SCADA Connection

RS-485 is available on Advanced I/O. The RJ45-shaped connector is not an Ethernet LAN port. The manual assigns pin 1 to S+ and pin 8 to S−; verify connector orientation and numbering from the original drawing before wiring.

CodeFunctionManual example
CM.01Drive station address1; assign unique addresses to multiple drives
CM.02Protocol0=Modbus RTU, 1=LS INV 485
CM.03Baud rate3=9,600bps
CM.04Data, parity and stop bits0 = 8 data bits, no parity, 1 stop bit
drv / FrqCommunication command selectionRun via communication: drv=3 / speed via communication: Frq=9

Monitoring-only and communication-based control are different. Reading values does not require switching drv/Frq to communication. Match protocol, address, baud rate and frame format; configure termination using SW3 and the actual network layout.

Check register addressing, read/write permission and scaling rather than copying an address number alone. Begin by reading status, then validate run-command writes under controlled, stopped-machine conditions.

References: manual pp.76, 83, 172–189.

14. Common Trips and First Checks

DisplayMeaningFirst checks
OCtOvercurrentShort ramp times, excessive load or restarting a rotating motor
OvtOvervoltageRapid deceleration, regenerative load and input voltage
LvtUndervoltageSupply, momentary voltage drop and input contactor
OLt / EtHOverload / electronic motor thermal protectionLoad, motor ratings, prolonged low-speed operation and cooling
OHtDrive overtemperatureAmbient temperature, ventilation and cooling fan
GFtOutput ground faultMotor and output-cable insulation
EStOutput disabled by stop inputActual state of the input assigned to output-disable/emergency-stop
rOtPrecharge-circuit faultInput supply and repowering conditions; stop use for inspection if repeated

A trip identifies a detected condition, not necessarily its root cause. An Ovt indication does not automatically call for drive replacement: establish whether it occurs during deceleration, immediately after power-up or after a load change.

 After a Trip 
① Remove the run command and stop the machine safely.
② Record code, timing, frequency, current and recent changes.
③ Isolate, verify discharge and perform the required wiring/load checks.
④ Remove the cause, check the area, then reset and test.
⑤ For repeated faults, request professional inspection instead of repeatedly resetting.

No Trip, but the Motor Will Not Run?

Check drv → Frq → target frequency → input assignments → NPN/PNP → stop input → motor/load. Both a run command and valid speed reference are needed. For unchangeable settings, check running restrictions, I/O type, locks and allowed range.

References: manual pp.218–225.

15. Consider Initialization and Automatic Restart Carefully

Record Existing Settings Before CF.93 Initialization

CF.93 initializes parameters; the manual's full-reset example uses CF.93=1. Resetting an installed drive can erase terminal, speed, protection and communication configuration. Record or back up settings and establish a recovery procedure first.

Initialization can return a keypad-controlled drive to factory terminal control. Completing a reset does not mean completing the machine's setup.

Unexpected Movement at Power-Up or After Reset

CodeFunctionCondition to consider
Ad.10Start on power-up selectionWith drv=1/2 and an active run contact, restarting can occur
Pr.08Start after trip reset selectionA remaining terminal run command can restart the motor after reset

Both functions default to 0 in the cited manual. Even in automatic machinery, assess whether movement after power/fault recovery is permitted. A normal stop input or keypad STOP does not complete the machine's safety system.

References: manual pp.52, 84–85.

16. Frequently Asked Questions

Can M100 drive a single-phase motor?

No. The cited manual specifies three-phase motor operation. Single-phase supply input is a separate matter.

The front dial does not change speed.

First check Frq=2. Also check whether external, communication or preset-speed commands are active.

Is Frq=2 for an external potentiometer?

No. M100's external V1 potentiometer uses Frq=3; the built-in dial uses Frq=2. Do not mix parameter numbers between series.

Standard also has RJ45. Does it support communication?

Connector shape alone is insufficient. M100 RS-485 is supported by Advanced I/O models.

The display still says 10.00 after stopping.

The frequency-reference screen can retain the target after stopping. Check RUN indication and actual operation together.

Can I run faster by setting above 60 Hz?

The drive setting range is not the machine's allowable range. Check motor/load ratings, bearings and mechanical speed limits. Analog scaling matters as well as FrM.

Will longer ramp times solve every trip?

No. Causes include load, supply, insulation and cooling. Diagnose from the code and event timing.

Can I reset a used M100 and operate immediately?

A reset does not establish suitability. Inspect model, ratings, condition, wiring, motor data and safety requirements, then enter the required settings.

17. Record These Items Before and After Setup

RecordInformation
Drive and motorFull M100 model, I/O type, motor kW, voltage, rated current and frequency
Basic settingsdrv / Frq / ACC / dEC / MkW / MrC / MbF / FrM
Site signalsP1–P5 assignments, SW1/SW2 and external-input scaling
Operating conditionsNormal frequency/current, rotation and ramp behavior
Fault recordCode, timing, recent changes and Pr.91–95 history

Troubleshooting M100 often comes down to identifying which command it is following. Check model/I/O, select drv and Frq separately, then verify current, direction and stopping behavior.

Information for M100 Selection and Setup Enquiries

Send the full drive model, motor nameplate, switch/potentiometer/PLC signals and intended operating method. For trips, include the code and when it occurs.

M100 product information and quotations →

References

① LS ELECTRIC M100 Korean user manual V2.2, 14 November 2025.
② LS ELECTRIC M100 Korean catalogue (04), December 2020.
Product photos and diagrams are excerpts from the original materials. Click images to enlarge. Actual wiring and commissioning must follow the supplied product's nameplate, manual and site design.

LS M100 VFD User Guide: Wiring, Settings and Troubleshooting — original reference image 7

#M100 #LSM100 #M100VFD #LSInverter #M100UserGuide #VFDWiring #FrequencySetting #VFDTroubleshooting #LSELECTRIC #2SK

English edition by 2SK. Original catalogue/reference images are retained; some labels within images are in Korean. Read the original Korean article

2SK Tech Blog

E.mail. 2sk@2sk.co.kr  Tel.1833-7728  Fax.031-479-3585


Company Name: 2SK 

Business Registration No.: 657-76-00077


Store: #16-111, Anyang International Distribution Complex, 92 LS-ro, Dongan-gu, Anyang-si, Gyeonggi-do, Postal Code 14771, Republic of Korea

Office: Room 503, Building B, Geumjeong Station 3rd SK V1 Center, 91 LS-ro 116beon-gil, Dongan-gu, Anyang-si, Gyeonggi-do, Republic of Korea

Factory: 1F, 27 Heongan-daero 49beon-gil, Dongan-gu, Anyang-si, Gyeonggi-do, Republic of Korea


CEO: Shin Jae-woon


Mail-Order Business License: No. 2017-Anyang Dongan-0311

Retail Webpage: https://2sk.co.kr

Copyright: Copyright ⓒ 2SK SOLUTION. All rights reserved.


MON-FRI · AM 09:00 ~ PM 05:00
LUNCH · PM 12:00 - PM 01:00
SAT.SUN.HOLIDAY OFF