LS M100 Single-Phase Input VFD: Control a Three-Phase Motor from a 220 V Supply
Single-phase input · three-phase output · 0.1–2.2 kW. A practical guide to selection, wiring and first-run settings.
Welcome to 2SK.
Installing a small conveyor or pump where only single-phase 220 V power is available? If you also need speed control, the LS ELECTRIC M100 compact VFD is worth considering.
“Single-phase” describes the input supply. M100 receives single-phase power and drives a three-phase motor. It is not a drive for a single-phase motor. Understanding this distinction makes selection and wiring straightforward.

Official LS ELECTRIC product image. Details vary with power rating and I/O configuration.
01. Single-Phase In, Three-Phase Out
The drive accepts the site's single-phase supply and produces three-phase voltage and frequency for the motor. Changing the output frequency changes motor speed. This output is for driving a motor; M100 is not a general three-phase power supply for an entire installation.
Key Point
Single-phase 220 V-class supply → M100 → three-phase 220 V-class motor
M100 is not intended for single-phase motors and does not step 220 V up to 380 V. Maximum output voltage cannot exceed the input supply voltage.
This article covers the M100-1 series with single-phase 200–240 V input, commonly used on 220 V supplies in Korea. The 100–120 V input series uses different model numbers.
02. Read the Motor Nameplate First
Before matching a 0.75 kW motor to a 0.75 kW drive, check the number of phases, voltage and winding connection. Equal power ratings do not guarantee electrical compatibility.
For a motor marked Δ 220 V / Y 380 V, a 220 V-class output generally calls for delta connection. Do not expect rated operation from a 380 V-only motor supplied by a 220 V-class M100. Follow the motor manufacturer's terminal diagram and rated frequency.
Next check motor rated current against the drive's rated output current. Consider starting load and continuous low-speed operation. A motor's self-cooling decreases at low speed, so reducing speed does not always reduce thermal stress.
03. M100 Ratings and Model Numbers
| Applicable motor | Standard S model | Rated output current | Rated input current |
|---|
| 0.1kW | LSLV0001M100-1EOFNS | 0.8A | 1.0A |
| 0.2kW | LSLV0002M100-1EOFNS | 1.4A | 1.8A |
| 0.4kW | LSLV0004M100-1EOFNS | 2.4A | 3.7A |
| 0.75kW | LSLV0008M100-1EOFNS | 4.2A | 7.1A |
| 1.5kW | LSLV0015M100-1EOFNS | 7.5A | 13.6A |
| 2.2kW | LSLV0022M100-1EOFNS | 11.0A | 18.7A |
This table follows the manufacturer's single-phase 200 V-class specifications. Motor ratings are based on standard four-pole motors; carrier frequency and installation conditions can limit output current. The code 0008 identifies the 0.75 kW model.

Input current and motor current are different.
For example, the 2.2 kW model has 11.0 A rated output current and 18.7 A rated input current. Select input cables and protection using the manufacturer's recommendations and actual circuit conditions, not motor current alone.
The final S or A indicates I/O configuration. For example, LSLV0008M100-1EOFNS is Standard I/O, while LSLV0008M100-1EOFNA is Advanced I/O. In the model code, O is the letter for Open Type.
04. Standard S or Advanced A? Check Communication Requirements
| Item | Standard S | Advanced A |
|---|
| Multifunction inputs | P1~P3 | P1~P5 |
| External 0–10 V speed reference | V1 input | V1 input |
| Additional current/voltage input | No I2 input | I2 provided; check SW2 and input settings |
| RS-485 / Modbus | Not supported | Supported |
| Best suited to | Basic buttons, dial and voltage-reference control | Additional inputs or PLC communication control |
Front-dial or contact-based operation needs a different configuration from PLC control and monitoring over communication. If communication is required, start with the Advanced I/O A model.
An RJ45-shaped connector is not necessarily a LAN or Ethernet port. Use the correct M100 accessory cable and wiring for its purpose. For RS-485, match the address, baud rate, protocol, termination and connected equipment's register map.


05. Supply to R/T, Motor to U/V/W
Keep input and output wiring distinct. Connect the single-phase supply to R and T, and the three-phase motor to U, V and W. Connect protective earth to both drive and motor.
| Circuit | Terminals | What to check |
|---|
| Input supply | R / T | Single-phase 200–240 V supply; input protection and cable sizing |
| Motor output | U / V / W | Compatible three-phase motor with the nameplate-specified connection |
| Protective earth | Earth terminal | Earth both drive and motor; do not confuse protective earth with control CM |
| Run and speed signals | P terminals / V1 / CM, etc. | Terminal assignments, NPN/PNP selection and PLC output type |
Connecting mains power to U/V/W can damage the drive. Use the keypad or control signals for normal start/stop operation rather than repeatedly switching the input supply. Do not connect power-factor correction capacitors to the drive output.
External-switch wiring depends on NPN/PNP selection and terminal assignments; P1-to-CM is not a universal arrangement. The front STOP key is not a substitute for the machine's emergency-stop safety circuit.
06. Begin with the RUN Key and Front Dial
M100 selects run and speed commands separately. The keys determine whether the motor runs; the dial determines its requested speed. Turning the dial alone does not issue a run command.

Official LS ELECTRIC image. Select the correct Frq setting to use the built-in dial.
| Setting | Purpose | Check |
|---|
| drv = 0 | Select keypad run command | Start and stop with RUN / STOP |
| Frq = 2 | Select built-in dial as speed source | Confirm the reference changes as the dial turns |
| MkW / MrC | Motor capacity / motor rated current | Use the motor nameplate values, not the drive rating |
| MbF / FrM | Base frequency / maximum frequency | Match the motor rating and machine speed limit |
| ACC / dEC | Acceleration / deceleration time | Adjust for smooth starting and stopping under load |
Change settings while stopped and confirm they are saved. Make the first test brief, at a low frequency allowed by the machine, checking rotation, noise and output current. Correct rotation is especially important for fans and pumps.
For an external potentiometer or PLC 0–10 V reference, select V1 with Frq = 3. Frq = 2 selects the built-in dial. Use M100 parameter definitions rather than copying numbers from another LS drive.
Do not automatically set 60 Hz or 400 Hz.
Use the motor's 50 Hz or 60 Hz rating as applicable. A drive output range of 0–400 Hz does not mean every motor can safely run at 400 Hz.
Also check In.39 and In.41, which define the internal potentiometer's frequency endpoints. Distinguish these scaling values from maximum frequency FrM when the dial reaches its end but the requested speed remains too low.
07. Compact Installation Still Needs Cooling
M100 supports DIN-rail mounting and side-by-side installation, making it convenient for small panels with multiple drives. Its compact size does not remove the need for ventilation and thermal design.

Official LS ELECTRIC installation image. Apply the current spacing, temperature and derating instructions for the selected rating.
The enclosure rating is IP20 / Open Type. Use a suitable enclosure where water spray or dust is present, and design for panel temperature and cooling. A built-in EMC filter still requires proper earthing and separation of power and signal wiring.
08. What to Check When the Drive Will Not Run or Trips
| Symptom | First checks |
|---|
| No response to RUN | Check keypad selection in drv and any stop or external-trip signals |
| Dial has no effect on speed | Check Frq, frequency limits and preset-speed commands |
| Overcurrent during starting | Check motor wiring, mechanical restraint/load, acceleration time, ratings and settings |
| Overvoltage during deceleration | Review deceleration time and regenerative energy; consider braking requirements for repeated rapid stops |
| Drive or motor overheats | Check ambient temperature, ventilation, fan, low-speed duration, current and load |
Before repeatedly resetting a trip, record the code, frequency, output current and whether it occurred during acceleration, steady running or deceleration. Even the same overcurrent code can require different checks depending on when it appears.
Do not increase torque boost or enable automatic restart without diagnosing the cause. Restart settings determine whether machinery moves again after power restoration or fault clearance, so include the machine's safety requirements.
09. Five Details to Send Before Ordering
Send ① supply voltage ② motor nameplate photo ③ machine/load type ④ speed range and acceleration/deceleration requirements ⑤ control method and communication needs. This lets us check current, winding connection and S/A configuration as well as kW.
For example: “Single-phase 220 V supply, three-phase 220 V 0.75 kW motor, small conveyor, front-dial speed control, no communication.” When replacing an LS iE5 or iC5, also send the old drive nameplate and terminal photos. Wiring and settings must be checked against M100 requirements.
Simple Glossary
Hz: cycles per second; here, the motor output frequency.
Reference/command: an instruction to run or operate at a selected speed.
I/O: input/output signals exchanged with switches, sensors and PLCs.
Acceleration/deceleration: increasing or decreasing speed.
Regeneration: energy returning from the motor to the drive during deceleration.
Derating: reducing allowable current or power for temperature or installation conditions.
EMC: electromagnetic compatibility with surrounding equipment.
References LS ELECTRIC M100 catalogue (February 2025), English user manual V2.3 (February 2026) and official product information. Product photos are official manufacturer images; conceptual diagrams were prepared by 2SK.
Official M100 catalogue →Official M100 user manual →Wiring and configuration must be performed by qualified electrical personnel using the product nameplate, current manual and site design. Internal voltage may remain after isolation; follow the manufacturer's waiting time and absence-of-voltage procedure.

#LSM100 #M100VFD #LSELECTRIC #SinglePhaseVFD #220VInverter #ThreePhaseMotor #CompactVFD #MotorSpeedControl #M100Wiring #M100Settings #LSLV0008M100 #LSLV0015M100 #LSLV0022M100 #2SK
2SK TECH BLOG · LS ELECTRIC M100
LS M100 Single-Phase Input VFD: Control a Three-Phase Motor from a 220 V Supply
Single-phase input · three-phase output · 0.1–2.2 kW. A practical guide to selection, wiring and first-run settings.
Welcome to 2SK.
Installing a small conveyor or pump where only single-phase 220 V power is available? If you also need speed control, the LS ELECTRIC M100 compact VFD is worth considering.
“Single-phase” describes the input supply. M100 receives single-phase power and drives a three-phase motor. It is not a drive for a single-phase motor. Understanding this distinction makes selection and wiring straightforward.
Official LS ELECTRIC product image. Details vary with power rating and I/O configuration.
01. Single-Phase In, Three-Phase Out
The drive accepts the site's single-phase supply and produces three-phase voltage and frequency for the motor. Changing the output frequency changes motor speed. This output is for driving a motor; M100 is not a general three-phase power supply for an entire installation.
Single-phase 220 V-class supply → M100 → three-phase 220 V-class motor
M100 is not intended for single-phase motors and does not step 220 V up to 380 V. Maximum output voltage cannot exceed the input supply voltage.
This article covers the M100-1 series with single-phase 200–240 V input, commonly used on 220 V supplies in Korea. The 100–120 V input series uses different model numbers.
02. Read the Motor Nameplate First
Before matching a 0.75 kW motor to a 0.75 kW drive, check the number of phases, voltage and winding connection. Equal power ratings do not guarantee electrical compatibility.
For a motor marked Δ 220 V / Y 380 V, a 220 V-class output generally calls for delta connection. Do not expect rated operation from a 380 V-only motor supplied by a 220 V-class M100. Follow the motor manufacturer's terminal diagram and rated frequency.
Next check motor rated current against the drive's rated output current. Consider starting load and continuous low-speed operation. A motor's self-cooling decreases at low speed, so reducing speed does not always reduce thermal stress.
03. M100 Ratings and Model Numbers
This table follows the manufacturer's single-phase 200 V-class specifications. Motor ratings are based on standard four-pole motors; carrier frequency and installation conditions can limit output current. The code 0008 identifies the 0.75 kW model.
For example, the 2.2 kW model has 11.0 A rated output current and 18.7 A rated input current. Select input cables and protection using the manufacturer's recommendations and actual circuit conditions, not motor current alone.
The final S or A indicates I/O configuration. For example, LSLV0008M100-1EOFNS is Standard I/O, while LSLV0008M100-1EOFNA is Advanced I/O. In the model code, O is the letter for Open Type.
04. Standard S or Advanced A? Check Communication Requirements
Front-dial or contact-based operation needs a different configuration from PLC control and monitoring over communication. If communication is required, start with the Advanced I/O A model.
An RJ45-shaped connector is not necessarily a LAN or Ethernet port. Use the correct M100 accessory cable and wiring for its purpose. For RS-485, match the address, baud rate, protocol, termination and connected equipment's register map.
05. Supply to R/T, Motor to U/V/W
Keep input and output wiring distinct. Connect the single-phase supply to R and T, and the three-phase motor to U, V and W. Connect protective earth to both drive and motor.
Connecting mains power to U/V/W can damage the drive. Use the keypad or control signals for normal start/stop operation rather than repeatedly switching the input supply. Do not connect power-factor correction capacitors to the drive output.
External-switch wiring depends on NPN/PNP selection and terminal assignments; P1-to-CM is not a universal arrangement. The front STOP key is not a substitute for the machine's emergency-stop safety circuit.
06. Begin with the RUN Key and Front Dial
M100 selects run and speed commands separately. The keys determine whether the motor runs; the dial determines its requested speed. Turning the dial alone does not issue a run command.
Official LS ELECTRIC image. Select the correct Frq setting to use the built-in dial.
Change settings while stopped and confirm they are saved. Make the first test brief, at a low frequency allowed by the machine, checking rotation, noise and output current. Correct rotation is especially important for fans and pumps.
For an external potentiometer or PLC 0–10 V reference, select V1 with Frq = 3. Frq = 2 selects the built-in dial. Use M100 parameter definitions rather than copying numbers from another LS drive.
Use the motor's 50 Hz or 60 Hz rating as applicable. A drive output range of 0–400 Hz does not mean every motor can safely run at 400 Hz.
Also check In.39 and In.41, which define the internal potentiometer's frequency endpoints. Distinguish these scaling values from maximum frequency FrM when the dial reaches its end but the requested speed remains too low.
07. Compact Installation Still Needs Cooling
M100 supports DIN-rail mounting and side-by-side installation, making it convenient for small panels with multiple drives. Its compact size does not remove the need for ventilation and thermal design.
Official LS ELECTRIC installation image. Apply the current spacing, temperature and derating instructions for the selected rating.
The enclosure rating is IP20 / Open Type. Use a suitable enclosure where water spray or dust is present, and design for panel temperature and cooling. A built-in EMC filter still requires proper earthing and separation of power and signal wiring.
08. What to Check When the Drive Will Not Run or Trips
Before repeatedly resetting a trip, record the code, frequency, output current and whether it occurred during acceleration, steady running or deceleration. Even the same overcurrent code can require different checks depending on when it appears.
Do not increase torque boost or enable automatic restart without diagnosing the cause. Restart settings determine whether machinery moves again after power restoration or fault clearance, so include the machine's safety requirements.
09. Five Details to Send Before Ordering
Send ① supply voltage ② motor nameplate photo ③ machine/load type ④ speed range and acceleration/deceleration requirements ⑤ control method and communication needs. This lets us check current, winding connection and S/A configuration as well as kW.
For example: “Single-phase 220 V supply, three-phase 220 V 0.75 kW motor, small conveyor, front-dial speed control, no communication.” When replacing an LS iE5 or iC5, also send the old drive nameplate and terminal photos. Wiring and settings must be checked against M100 requirements.
LS M100 Product Information and Quotations
2SK · Korea: 1833-7728 · Email: 2sk@2sk.co.kr
View M100 products → Ask about selection or a quotation →Simple Glossary
Hz: cycles per second; here, the motor output frequency.
Reference/command: an instruction to run or operate at a selected speed.
I/O: input/output signals exchanged with switches, sensors and PLCs.
Acceleration/deceleration: increasing or decreasing speed.
Regeneration: energy returning from the motor to the drive during deceleration.
Derating: reducing allowable current or power for temperature or installation conditions.
EMC: electromagnetic compatibility with surrounding equipment.
LS ELECTRIC M100 catalogue (February 2025), English user manual V2.3 (February 2026) and official product information. Product photos are official manufacturer images; conceptual diagrams were prepared by 2SK.
Official M100 catalogue →
Official M100 user manual →
Wiring and configuration must be performed by qualified electrical personnel using the product nameplate, current manual and site design. Internal voltage may remain after isolation; follow the manufacturer's waiting time and absence-of-voltage procedure.