Welcome to 2SK.
After powering up a G100, the RUN key may seem ineffective or the dial may not change speed. Often nothing is broken: the drive is configured to receive its commands somewhere else.
This guide focuses on starting, stopping, frequency settings, direction and command-source selection. Begin with simple operation before exploring sensorless control, PID or detailed communication settings.

Official LS ELECTRIC image. Terminals and functions vary by rating and G100/G100C model.
01. Separate Two Commands to Make Setup Easy
A drive needs a run command telling it whether to turn, and a speed reference telling it how fast. G100 selects these with drv and Frq respectively.
Run and Speed Are Selected Separately
| drv · Run Command | Run or stop? Use the RUN key or an external switch. |
| Frq · Frequency Reference | How fast? Use a numeric setting, dial or external signal. |
| Remember | A speed setting alone does not start the motor. |
Begin with This Test Combination
drv = 0 → run/stop from the front keys
Frq = 0 → enter frequency numerically on the keypad
Remember: buttons run the motor; the number sets speed.
Frequency is measured in Hz. For the same motor and connection, lower frequency generally means lower speed. But 30 Hz does not mean 30 rpm: actual speed depends on pole count and load.
02. Check Supply and Motor Before Settings
This guide assumes a suitable drive/motor and correctly installed main circuit, earth and safety circuit. G100 has different voltage classes, so compare the drive input nameplate with motor voltage and connection.
R/S/T are supply inputs; U/V/W are motor outputs. Connecting mains to output terminals can damage the drive. Protective earth and control CM serve different purposes.
| Setting to check | Setting basis |
|---|
| dr.14 · Motor capacity | Motor nameplate kW. Select the corresponding entry; do not confuse its selection number with the kW value. |
| bA.13 · Motor rated current | Motor nameplate amperes, not automatically the drive's rated current. |
| bA.15 · Motor rated voltage | Match the nameplate and actual winding connection; check the input-voltage-based behavior when set to 0. |
| dr.18 · Base frequency | Motor rated frequency: distinguish 50 Hz and 60 Hz. |
| dr.20 · Maximum frequency | Operating ceiling based on motor and machine speed limits. |
The aim is to check existing values against the motor, not change every value blindly. Record installed-machine settings and avoid a factory reset without understanding the cause of a problem.
03. Press the Final ENT to Save
G100 setup follows a repeated pattern: find the code, edit the value, then confirm. A flashing entire value means a final confirmation is still needed.
Save the Setting: Press ENT Once More
| 1. Select the Code | At drv, Frq, ACC or another code, press ENT. |
| 2. Change the Value | Use ▲/▼, then ENT. The whole value flashes. |
| 3. Confirm Saving | Press ENT again and confirm flashing stops. |
| MODE/SHIFT | Use this key to change groups or move the digit being edited. |
Code → ENT → change with ▲/▼ → ENT → whole value flashes → ENT again. Move digits with MODE/SHIFT. Reopen the code afterward to verify the saved value.
04. First Run: Start and Stop from the Keypad
Start with the Keypad Diagram

Original “Keypad Operation and Functions” image from page 22 of the LS ELECTRIC G100 catalogue. Click to enlarge. Numbers ①–⑤ below match the original diagram.
① Numeric display: shows frequency, parameter names and values. 10.00 means 10 Hz on the frequency screen, but a time value inside ACC. Read the parameter as well as the number.
② SET flashes while setting a value.
③ RUN lights during operation and flashes during acceleration/deceleration.
④ FWD indicates forward operation.
⑤ REV indicates reverse operation.
RUN: starts the motor with keypad control (drv=0).
STOP/RESET: stops operation or resets a fault after its cause has been checked.
▲/▼: navigate and increase/decrease values.
MODE/SHIFT: changes groups or the edited digit.
ENT: opens, confirms and saves settings.
Right-hand dial: speed reference; select Frq=4 for the G100 built-in dial.
Read the following with the motor stopped. Record existing settings and operate under the responsible person's supervision. Clear explanations do not make electrical wiring or motor testing suitable for unsupervised beginners.
| Item | Setting | Meaning |
|---|
| drv | 0 | Receive run commands from RUN/STOP keys. |
| Frq | 0 | Enter target frequency numerically on the keypad. |
| Target frequency | Example: 10.00 Hz | Set on the operation-group frequency screen using a test value permitted by the machine. |
| drC | F | Select forward direction for keypad operation. |
| ACC / dEC | Times suited to the load | Check acceleration/deceleration to avoid abrupt starts and stops. |
Start from the operation group's first frequency screen. A new drive commonly shows 0.00; an existing unit may differ. If dr.0 or bA.0 is shown, use MODE/SHIFT to reach the operation group. Confirm the actual drv/Frq code rather than relying only on press counts.
A. Set drv = 0 to Enable the RUN Key
| Step | Button action | Display and check |
|---|
| 1 | From the frequency screen, press ▲ three times | In the basic menu: ACC → dEC → drv. Confirm drv appears. |
| 2 | Press ENT once | The current value appears. The factory value is 1; an installed drive may differ. |
| 3 | Select 0 with ▲ or ▼ | If currently 1, press ▼ once. If already 0, leave it. |
| 4 | Press ENT once | The entire 0 flashes; confirmation is still required. |
| 5 | Press ENT again | Returning to drv confirms saving. |
B. Set Frq = 0 for Numeric Keypad Speed
| Step | Button action | Display and check |
|---|
| 1 | From drv, press ▲ once | Frq appears; the display may resemble frq. |
| 2 | Press ENT once | The current frequency-source number appears. |
| 3 | Select 0 with ▲ or ▼ | 0 selects keypad entry. Leave unchanged if already 0. |
| 4 | ENT → whole value flashes → ENT | Returning to Frq confirms saving. |
| 5 | Press ▼ four times | In the basic menu: drv → dEC → ACC → frequency screen. |
C. Example: Change 0.00 to 10.00 Hz
This digit example starts at 0.00. First confirm the machine permits a 10 Hz test. If the current value differs, edit the necessary digits to reach the target.
| Step | Button action | Display and check |
|---|
| 1 | At 0.00, press ENT | The rightmost digit flashes. |
| 2 | Press MODE/SHIFT three times | Confirm the tens digit flashes. The display may show 00.00 while shifting. |
| 3 | Press ▲ once | The tens digit becomes 1, giving 10.00. |
| 4 | Press ENT once | The entire 10.00 flashes. |
| 5 | Press ENT again | When flashing stops, 10.00 Hz is saved. |
| 6 | Check the surroundings, then RUN | Frequency rises. Check RUN/FWD indication and actual machine rotation. |
| 7 | STOP/RESET | With deceleration-stop selected, frequency falls to zero. A displayed target of 10.00 after stopping does not mean the motor is still running at 10 Hz. |
First, save drv=0 and Frq=0 while stopped. Return to the frequency screen, enter an approved test frequency and save. The manual's 10 Hz example is not a universal test value for every machine.
Next, when the area is clear and direction can be checked, press RUN. Confirm acceleration toward the target, correct machine direction and absence of abnormal noise. CUr displays output current.
Press STOP/RESET to stop. With normal deceleration-stop settings, frequency ramps down. Existing stop-mode settings may produce different behavior. The STOP key does not replace an emergency-stop safety circuit.
RUN May Not Work with Factory Settings Alone.
The cited manual's default is drv=1, terminal control. For a keypad test, change to drv=0 and save.
05. Use the Front Dial Instead of a Number

Official LS ELECTRIC image. The dial provides a frequency reference, separate from the start command.
RUN Key + Built-In Dial
drv = 0 → front-key start/stop
Frq = 4 → built-in V0 dial frequency reference
| Step | Button action | Display and check |
|---|
| 1 | From the frequency screen, press ▲ four times | Frq appears in the basic menu. Open with ENT. |
| 2 | Select 4 with ▲ or ▼ | 4 = V0, the built-in dial. From 0, press ▲ four times. |
| 3 | ENT → whole value flashes → ENT | Returning to Frq confirms saving. |
| 4 | Press ▼ four times | Return to the frequency screen. |
| 5 | Turn the dial slowly | Confirm the displayed frequency changes; choose a low approved test value. |
| 6 | Confirm drv=0, then RUN | Run the motor; stop with STOP/RESET. |
Begin with a low dial position, check the displayed reference and press RUN. Adjust slowly within the permitted machine range. Turning the dial alone does not start the motor.
The dial's endpoint frequency depends on In.01, V0 scaling and frequency limits. Do not assume full rotation always means 60 Hz. G100's built-in dial uses Frq=4; do not copy another LS model's setting number.
06. Change Direction from the Keypad
With drv=0, select direction using drC in the operation group. F means forward; r means reverse and appears as a lowercase-style character.
| Step | Button action | Display and check |
|---|
| 1 | STOP/RESET → verify actual stop | Proceed only after motor and machine stop completely, and only if reverse operation is permitted. |
| 2 | Find drC using ▲/▼ in the operation group | drC selects rotation direction. |
| 3 | ENT | The current F or r is displayed. |
| 4 | Select r with ▲ or ▼ | r selects reverse; choose F to return to forward. |
| 5 | ENT → whole value flashes → ENT | Returning to drC confirms saving. |
| 6 | Confirm drv=0, then RUN | Check REV indication and actual reverse movement. |
FWD/REV indicates commanded direction; verify the physical machine direction separately. Do not reverse equipment such as pumps or fans that prohibit it. If reverse is blocked, check Ad.09, but do not remove a protective restriction without authorization from the machine design.
07. Forward/Reverse with External Switches
To use panel forward/stop/reverse switches, select terminal run control. A simple example assigns P1 to forward (Fx) and P2 to reverse (Rx).
| Setting | Value | Function |
|---|
| drv | 1 | Fx/Rx-1: separate forward and reverse run inputs |
| In.65 | 1 | Assign P1 to forward (Fx) |
| In.66 | 2 | Assign P2 to reverse (Rx) |
| Frq | 0 or 4 | 0: numeric keypad reference / 4: built-in dial. Speed selection remains separate. |
External-switch setup:
① drv → ENT → 1 → ENT → flashing → ENT.
② MODE/SHIFT to In.0 → find In.65 → ENT → 1 → ENT → flashing → ENT.
③ In.66 → ENT → 2 → ENT → flashing → ENT.
④ Save Frq=0 for numeric speed or 4 for the front dial.
⑤ After wiring and safety checks, test the forward switch.
External-Switch Concept · NPN Mode
| Forward | Example: a maintained dry contact between P1(Fx) and CM. |
| Reverse | Example: a maintained dry contact between P2(Rx) and CM. |
| Conditions | SW1 = NPN. Do not copy directly for PNP or PLC outputs. |
| Interlock | Prevent both contacts closing simultaneously. CM is not protective earth. |
This example uses maintained dry contacts with SW1 set to NPN. PNP and PLC transistor outputs require different wiring checks. Never apply mains voltage to control input terminals.
| Forward contact | Reverse contact | Operation with drv = 1 |
|---|
| ON | OFF | Forward running |
| OFF | ON | Reverse running |
| OFF | OFF | Stop |
| ON | ON | Run interrupted per the manual; do not use this as a normal operating state. |
The run command remains active while the contact is closed. A momentary “press once and keep running” circuit requires seal-in or three-wire control. Use an interlocked selector with a stop position or an equivalent design; change direction after verifying a stop.
drv = 1 and drv = 2 Are Different.
drv = 1: separate forward and reverse run inputs
drv = 2: one run/stop input and one direction input
Fx/Rx input roles differ between these modes. This article's wiring example uses drv=1.
08. Operating-Method Settings at a Glance
| Required method | drv | Frq |
|---|
| RUN key + numeric keypad frequency | 0 | 0 |
| RUN key + built-in front dial | 0 | 4 |
| External forward/reverse contacts + numeric frequency | 1 | 0 |
| External forward/reverse contacts + built-in dial | 1 | 4 |
| External forward/reverse contacts + external V1 voltage reference | 1 | 2 |
| RS-485 run and frequency commands | 3 | 6 |
V1 is an external voltage input, distinct from the V0 front dial. RS-485 also needs address, communication and connected-device settings; the two values in the table alone do not complete setup. Begin with keypad or built-in dial operation for the first check.
09. ACC and dEC Control Acceleration and Deceleration
ACC is acceleration time; dEC is deceleration time. Too-short acceleration can cause overcurrent, while abrupt deceleration of high-inertia loads can cause overvoltage. Smaller values are not automatically better.
With the manual's basic reference bA.08=0, time is based on 0 Hz to maximum frequency. At 60 Hz maximum, ACC=10 seconds and linear acceleration, reaching 30 Hz takes approximately 5 seconds mathematically. Load and other controls can affect actual time.
Acceleration: frequency screen → ▲ once → ACC → ENT → select digits with MODE/SHIFT and adjust with ▲/▼ → ENT → whole value flashes → ENT.
Deceleration: frequency screen → ▲ twice → dEC → ENT → edit and save the same way.
Times are in seconds. Choose values for the load and check while stopped.
10. If the Motor Will Not Run
| Symptom | First checks |
|---|
| No response to RUN | Check drv=0, nonzero target frequency, trips and output-disable signals |
| Dial does not change speed | Check Frq=4, preset-speed commands and frequency limits |
| External switch has no effect | Check drv, P1/P2 assignments, NPN/PNP, wiring and contact state |
| Cannot reverse | Check drC or external Rx, plus direction prohibition |
| Trip during operation | Record fault code and conditions; remove the cause before resetting |
On STO models, safety inputs can inhibit output. Do not bypass the safety circuit. Before reset, turn external run switches OFF and check restart settings and surroundings; a remaining run command can restart the motor depending on configuration.
The Essential Settings Again
① drv: where run/stop commands come from
② Frq: where frequency is set
③ drC or Fx/Rx: which direction to run
④ ACC/dEC: how quickly to start and stop
A short keypad test before moving to external control reduces the number of things to troubleshoot at once.
Simple Glossary
Keypad: front display and buttons.
Command/reference: an instruction sent to the machine.
Parameter: a setting defining operation.
Fx/Rx: forward/reverse run commands.
Dry contact: signals by opening/closing without supplying an external voltage.
Maintained contact: retains its selected ON/OFF state.
Trip: protective operation after an abnormal condition.
References and Scope
Based on LS ELECTRIC G100(C) Korean manual V4.04 (1 October 2026) and G100 Series Korean catalogue (June 2025). For basic operation/settings, see printed manual pp. 53, 58–67, 74–96, 98–100 and 278–280.
The original keypad image is from catalogue p.22. Product photos are official LS ELECTRIC material; explanatory tables were prepared by 2SK. Existing machine settings and detailed model variants can change operation.
Qualified electrical personnel must perform wiring. The manual specifies waiting at least 10 minutes after isolating power before opening the cover, then checking residual voltage with suitable test equipment. Guard rotating parts and confirm motor/machine limits before testing.
#LSG100 #G100VFD #G100Setup #G100Operation #G100FrequencySetting #ForwardReverse #G100C #LSELECTRIC #VFDGuide #MotorSpeedControl #2SK
2SK TECH BLOG · LS ELECTRIC G100
LS G100 Basic Operation: Start/Stop, Forward/Reverse and Frequency Settings
The settings you need for a first motor run: RUN key, speed dial and external run switch.
Welcome to 2SK.
After powering up a G100, the RUN key may seem ineffective or the dial may not change speed. Often nothing is broken: the drive is configured to receive its commands somewhere else.
This guide focuses on starting, stopping, frequency settings, direction and command-source selection. Begin with simple operation before exploring sensorless control, PID or detailed communication settings.
Official LS ELECTRIC image. Terminals and functions vary by rating and G100/G100C model.
01. Separate Two Commands to Make Setup Easy
A drive needs a run command telling it whether to turn, and a speed reference telling it how fast. G100 selects these with drv and Frq respectively.
Run and Speed Are Selected Separately
drv = 0 → run/stop from the front keys
Frq = 0 → enter frequency numerically on the keypad
Remember: buttons run the motor; the number sets speed.
Frequency is measured in Hz. For the same motor and connection, lower frequency generally means lower speed. But 30 Hz does not mean 30 rpm: actual speed depends on pole count and load.
02. Check Supply and Motor Before Settings
This guide assumes a suitable drive/motor and correctly installed main circuit, earth and safety circuit. G100 has different voltage classes, so compare the drive input nameplate with motor voltage and connection.
R/S/T are supply inputs; U/V/W are motor outputs. Connecting mains to output terminals can damage the drive. Protective earth and control CM serve different purposes.
The aim is to check existing values against the motor, not change every value blindly. Record installed-machine settings and avoid a factory reset without understanding the cause of a problem.
03. Press the Final ENT to Save
G100 setup follows a repeated pattern: find the code, edit the value, then confirm. A flashing entire value means a final confirmation is still needed.
Save the Setting: Press ENT Once More
Code → ENT → change with ▲/▼ → ENT → whole value flashes → ENT again. Move digits with MODE/SHIFT. Reopen the code afterward to verify the saved value.
04. First Run: Start and Stop from the Keypad
Start with the Keypad Diagram
Original “Keypad Operation and Functions” image from page 22 of the LS ELECTRIC G100 catalogue. Click to enlarge. Numbers ①–⑤ below match the original diagram.
① Numeric display: shows frequency, parameter names and values. 10.00 means 10 Hz on the frequency screen, but a time value inside ACC. Read the parameter as well as the number.
② SET flashes while setting a value.
③ RUN lights during operation and flashes during acceleration/deceleration.
④ FWD indicates forward operation.
⑤ REV indicates reverse operation.
RUN: starts the motor with keypad control (drv=0).
STOP/RESET: stops operation or resets a fault after its cause has been checked.
▲/▼: navigate and increase/decrease values.
MODE/SHIFT: changes groups or the edited digit.
ENT: opens, confirms and saves settings.
Right-hand dial: speed reference; select Frq=4 for the G100 built-in dial.
Read the following with the motor stopped. Record existing settings and operate under the responsible person's supervision. Clear explanations do not make electrical wiring or motor testing suitable for unsupervised beginners.
Start from the operation group's first frequency screen. A new drive commonly shows 0.00; an existing unit may differ. If dr.0 or bA.0 is shown, use MODE/SHIFT to reach the operation group. Confirm the actual drv/Frq code rather than relying only on press counts.
A. Set drv = 0 to Enable the RUN Key
B. Set Frq = 0 for Numeric Keypad Speed
C. Example: Change 0.00 to 10.00 Hz
This digit example starts at 0.00. First confirm the machine permits a 10 Hz test. If the current value differs, edit the necessary digits to reach the target.
First, save drv=0 and Frq=0 while stopped. Return to the frequency screen, enter an approved test frequency and save. The manual's 10 Hz example is not a universal test value for every machine.
Next, when the area is clear and direction can be checked, press RUN. Confirm acceleration toward the target, correct machine direction and absence of abnormal noise. CUr displays output current.
Press STOP/RESET to stop. With normal deceleration-stop settings, frequency ramps down. Existing stop-mode settings may produce different behavior. The STOP key does not replace an emergency-stop safety circuit.
The cited manual's default is drv=1, terminal control. For a keypad test, change to drv=0 and save.
05. Use the Front Dial Instead of a Number
Official LS ELECTRIC image. The dial provides a frequency reference, separate from the start command.
drv = 0 → front-key start/stop
Frq = 4 → built-in V0 dial frequency reference
Begin with a low dial position, check the displayed reference and press RUN. Adjust slowly within the permitted machine range. Turning the dial alone does not start the motor.
The dial's endpoint frequency depends on In.01, V0 scaling and frequency limits. Do not assume full rotation always means 60 Hz. G100's built-in dial uses Frq=4; do not copy another LS model's setting number.
06. Change Direction from the Keypad
With drv=0, select direction using drC in the operation group. F means forward; r means reverse and appears as a lowercase-style character.
FWD/REV indicates commanded direction; verify the physical machine direction separately. Do not reverse equipment such as pumps or fans that prohibit it. If reverse is blocked, check Ad.09, but do not remove a protective restriction without authorization from the machine design.
07. Forward/Reverse with External Switches
To use panel forward/stop/reverse switches, select terminal run control. A simple example assigns P1 to forward (Fx) and P2 to reverse (Rx).
External-switch setup:
① drv → ENT → 1 → ENT → flashing → ENT.
② MODE/SHIFT to In.0 → find In.65 → ENT → 1 → ENT → flashing → ENT.
③ In.66 → ENT → 2 → ENT → flashing → ENT.
④ Save Frq=0 for numeric speed or 4 for the front dial.
⑤ After wiring and safety checks, test the forward switch.
External-Switch Concept · NPN Mode
This example uses maintained dry contacts with SW1 set to NPN. PNP and PLC transistor outputs require different wiring checks. Never apply mains voltage to control input terminals.
The run command remains active while the contact is closed. A momentary “press once and keep running” circuit requires seal-in or three-wire control. Use an interlocked selector with a stop position or an equivalent design; change direction after verifying a stop.
drv = 1: separate forward and reverse run inputs
drv = 2: one run/stop input and one direction input
Fx/Rx input roles differ between these modes. This article's wiring example uses drv=1.
08. Operating-Method Settings at a Glance
V1 is an external voltage input, distinct from the V0 front dial. RS-485 also needs address, communication and connected-device settings; the two values in the table alone do not complete setup. Begin with keypad or built-in dial operation for the first check.
09. ACC and dEC Control Acceleration and Deceleration
ACC is acceleration time; dEC is deceleration time. Too-short acceleration can cause overcurrent, while abrupt deceleration of high-inertia loads can cause overvoltage. Smaller values are not automatically better.
With the manual's basic reference bA.08=0, time is based on 0 Hz to maximum frequency. At 60 Hz maximum, ACC=10 seconds and linear acceleration, reaching 30 Hz takes approximately 5 seconds mathematically. Load and other controls can affect actual time.
Acceleration: frequency screen → ▲ once → ACC → ENT → select digits with MODE/SHIFT and adjust with ▲/▼ → ENT → whole value flashes → ENT.
Deceleration: frequency screen → ▲ twice → dEC → ENT → edit and save the same way.
Times are in seconds. Choose values for the load and check while stopped.
10. If the Motor Will Not Run
On STO models, safety inputs can inhibit output. Do not bypass the safety circuit. Before reset, turn external run switches OFF and check restart settings and surroundings; a remaining run command can restart the motor depending on configuration.
① drv: where run/stop commands come from
② Frq: where frequency is set
③ drC or Fx/Rx: which direction to run
④ ACC/dEC: how quickly to start and stop
A short keypad test before moving to external control reduces the number of things to troubleshoot at once.
LS G100 Selection and Quotations
Send the motor nameplate, input voltage and preferred operating method. 2SK · Korea: 1833-7728 · 2sk@2sk.co.kr
Selection and quotation enquiry → Official LS ELECTRIC product information →Simple Glossary
Keypad: front display and buttons.
Command/reference: an instruction sent to the machine.
Parameter: a setting defining operation.
Fx/Rx: forward/reverse run commands.
Dry contact: signals by opening/closing without supplying an external voltage.
Maintained contact: retains its selected ON/OFF state.
Trip: protective operation after an abnormal condition.
Based on LS ELECTRIC G100(C) Korean manual V4.04 (1 October 2026) and G100 Series Korean catalogue (June 2025). For basic operation/settings, see printed manual pp. 53, 58–67, 74–96, 98–100 and 278–280.
The original keypad image is from catalogue p.22. Product photos are official LS ELECTRIC material; explanatory tables were prepared by 2SK. Existing machine settings and detailed model variants can change operation.
Qualified electrical personnel must perform wiring. The manual specifies waiting at least 10 minutes after isolating power before opening the cover, then checking residual voltage with suitable test equipment. Guard rotating parts and confirm motor/machine limits before testing.
#LSG100 #G100VFD #G100Setup #G100Operation #G100FrequencySetting #ForwardReverse #G100C #LSELECTRIC #VFDGuide #MotorSpeedControl #2SK
English edition by 2SK. Original catalogue/reference images are retained; some labels within images are in Korean. Read the original Korean article