2SK Motor Control & Protective Device Blog

Motor Control & Protective Device


Motor Control & Protective Device

InverterLS G100 Variable Frequency Drive: Product Overview and iG5A Replacement Guide

2SK TECH BLOG · LS ELECTRIC

LS G100 Variable Frequency Drive: Product Overview and iG5A Replacement Guide

Find a G100 replacement from your existing SV iG5A model number. Compare ratings, voltage, control terminals and installation space.

Welcome to 2SK.

Your drive nameplate says SV008iG5A-4 or SV037iG5A-2. When a supplier recommends G100 as a replacement, the obvious question is: will the machine run as it did before?

LS ELECTRIC provides a migration guide from iG5A to G100/G100C. This makes G100 a practical starting point when replacing an iG5A. Model selection, wiring and parameter migration must be considered together. Here we explain both the product benefits and the replacement process.

LS G100 VFD: iG5A Replacement and Model Selection Guide — original reference image 1

Original LS ELECTRIC catalogue image. Appearance and terminal layout vary with rating and model.

01. What Is the G100?

A variable frequency drive (VFD) controls motor speed by adjusting the frequency and voltage supplied to the motor. G100 is a general-purpose drive for fans, pumps, conveyors and industrial machinery. It supports V/F and sensorless vector control to suit different loads.

ItemSelection information
G100 range0.4–22 kW, heavy-duty rating
G100C range0.4–4 kW, June 2025 catalogue
Input voltageThree-phase 200–240 V / three-phase 380–480 V
Control methodsV/F, slip compensation and sensorless vector control
Command sourcesKeypad, external terminals or communication
Overload capability150% of heavy-duty rated current for 1 minute / 120% of normal-duty rated current for 1 minute
CommunicationBuilt-in RS-485; check applicable expansion options for G100

Heavy-duty and normal-duty ratings describe load and overload conditions, not price tiers. Before applying a normal-duty rating, check motor current, starting conditions and ambient temperature—even for a fan or pump.

02. What Does G100 Offer When Replacing iG5A?

A speed adjustment dial is built into the front panel. Select the internal potentiometer as the frequency source to adjust speed directly. This is useful for test runs and simple machines without a separate panel-mounted potentiometer.

LS G100 VFD: iG5A Replacement and Model Selection Guide — original reference image 2

The dial sets the speed reference. The run command and speed reference are selected separately.

Sensorless vector control is useful for loads requiring torque at low speed. It estimates the motor state without a separate speed sensor. Enter the actual motor data and complete the appropriate tuning to obtain the intended performance.

Maintenance is another benefit. The catalogue describes an easily replaceable cooling fan and a replacement warning based on accumulated operating time. In dusty control panels, ventilation and cleaning are just as important as replacing the drive.

Built-in RS-485 supports equipment integration. G100 also offers applicable RAPIEnet+, EtherNet/IP and Modbus TCP communication options. These Ethernet functions are optional, not standard on every model. G100C does not support these communication options in the cited catalogue.

LS G100 VFD: iG5A Replacement and Model Selection Guide — original reference image 3

Cooling fan replacement structure shown in the catalogue. Follow the procedure for your model. Source: LS ELECTRIC.

03. Start with the Voltage on the iG5A Nameplate

LS G100 VFD: iG5A Replacement and Model Selection Guide — original reference image 4

Two drives rated 0.75 kW are not interchangeable if their input voltages differ. The iG5A suffix -2 identifies the three-phase 200 V class, while -4 identifies the three-phase 400 V class. Confirm the actual input specification on the nameplate.

 How to Select a Replacement 
Full existing model number → input voltage → motor kW and rated current → control terminals and options → exact G100 model.

The table below covers three-phase 400 V iG5A replacements. For ratings up to 4 kW, select G100C when seeking the corresponding iG5A-size replacement. Do not omit the C after G100. Applications requiring an EMC filter or STO need the appropriate suffix; power rating alone is insufficient for ordering.

Existing ratingExisting iG5AG100C / G100 replacement
0.4kWSV004iG5A-4LSLV0004G100C-4EONN
0.75kWSV008iG5A-4LSLV0008G100C-4EONN
1.5kWSV015iG5A-4LSLV0015G100C-4EONN
2.2kWSV022iG5A-4LSLV0022G100C-4EONN
3.7kWSV037iG5A-4LSLV0040G100C-4EONN
5.5kWSV055iG5A-4LSLV0055G100-4EONN
7.5kWSV075iG5A-4LSLV0075G100-4EONN
11kWSV110iG5A-4LSLV0110G100-4EONN
15kWSV150iG5A-4LSLV0150G100-4EONN
18.5kWSV185iG5A-4LSLV0185G100-4EONN
22kWSV220iG5A-4LSLV0220G100-4EONN

For three-phase 200 V models, match the iG5A -2 series to the corresponding G100 -2EONN series. Examples: SV008iG5A-2 → LSLV0008G100C-2EONN and SV015iG5A-2 → LSLV0015G100C-2EONN.

 Looking for a 3.7 kW Replacement? 
The corresponding replacement for a 3.7 kW iG5A is a 4.0 kW G100C.
Example: SV037iG5A-4 → LSLV0040G100C-4EONN
Also check motor rated current and operating load.

Single-phase input iG5A models require separate selection. Do not apply the three-phase table directly to SV004iG5A-1, SV008iG5A-1 or SV015iG5A-1. The 2021 migration leaflet recommends M100 for the single-phase 200 V range. The 2025 G100 catalogue also lists derated current for single-phase input; any such G100 application must be selected against those conditions.

Ordering an iG5A replacement? Check the letter C.

Existing 2.2 kW: SV022iG5A-4 → LSLV0022G100C-4EONN

Existing 3.7 kW: SV037iG5A-4 → LSLV0040G100C-4EONN

Read the old nameplate → select G100C up to 4 kW → check I/O and parameter migration.

04. For an iG5A-Size Replacement up to 4 kW, Choose G100C

The C is important in iG5A replacements up to 4 kW. Select G100C when matching the existing iG5A size. For example, SV022iG5A-4 corresponds to LSLV0022G100C-4EONN. Physical compatibility does not automatically mean control-circuit compatibility: compare the I/O and options below.

ComparisonG100G100C
Power range0.4–22 kW, heavy duty0.4–4 kW, heavy duty
Built-in EMC filter, 400 V classAvailable on applicable modelsNo built-in filter
Expansion communication optionsApplicable options availableNot supported in the cited catalogue
Standard output arrangementRelay outputs 1 and 2Relay output 1 + open-collector output
Selection prioritiesRequired rating, communication, outputs and safety optionsInstallation space and required output functions

The 2021 migration leaflet lists G100C only up to 1.5 kW. This article uses the later June 2025 catalogue range of up to 4 kW. Check publication dates when comparing older replacement charts with newer catalogues.

LS G100 VFD: iG5A Replacement and Model Selection Guide — original reference image 5

Original G100 I/O terminal image. For G100C and STO models, check the terminal layout and specifications for the exact model. Source: LS ELECTRIC.

05. Four Things to Check Before Replacement

① How many input terminals are in use? The iG5A migration leaflet shows multifunction inputs P1–P8. In the 2025 catalogue, standard G100/G100C models have P1–P5, while G100 STO models have P1–P8. If your machine uses P6–P8, a standard replacement may not have enough inputs. Check this before ordering by voltage and kW alone.

② Match terminal functions, not wire numbers. iG5A terminals AM, MO/MG and 3A/3B/3C differ from the AO, relay and transistor outputs of the G100 family. Identify each wire as a run command, speed reference or fault output, then connect it to the equivalent function. Also check current-signal type and NPN/PNP configuration.

③ Separate G100C replacements up to 4 kW from larger G100 installations. Do not assume all larger G100 drives share iG5A dimensions. For example, the leaflet lists the 400 V 7.5 kW iG5A at 180 × 220 × 170 mm and G100 at 180 × 240 × 144 mm (W × H × D), excluding dial projection. Check the current outline drawing, mounting holes and cooling clearances.

④ Transfer the meaning of each setting. Record the existing run and speed sources, acceleration/deceleration times, motor ratings, preset speeds, relay assignments and communication settings. Re-enter the corresponding G100 functions. Do not assume parameter numbers or configuration files are interchangeable. Check braking resistors and remote keypads separately.

 Take photos before removing the old drive. 
Drive nameplate · motor nameplate · complete control terminal block · wiring diagram · key settings.
These records make replacement selection and commissioning much easier.

06. Basic Settings for the First Run

First decide where the run command and speed reference will come from. On G100, drv selects the run command source and Frq selects the frequency source. The combinations below assume wiring and motor settings are complete and the machine is stopped.

Required operating methoddrvFrq
Front RUN/STOP keys + numeric keypad speed setting00
Front RUN/STOP keys + built-in speed dial04
External maintained forward/reverse contacts + built-in dial14

To save a setting: find the code → ENT → select the value with ▲/▼ → ENT → when the entire value flashes, press ENT again. Confirm the displayed code rather than counting button presses. Start at a low test frequency approved for the machine, checking rotation and current.

LS G100 VFD: iG5A Replacement and Model Selection Guide — original reference image 6LS G100 VFD: iG5A Replacement and Model Selection Guide — original reference image 7LS G100 VFD: iG5A Replacement and Model Selection Guide — original reference image 8

The keypad diagram, indicators and button functions from page 22 of the G100 catalogue are shown separately below. Click an image to enlarge it in a new tab.

See the button-by-button guide: G100 Basic Operation →

07. What to Send Us for an iG5A Replacement Enquiry

Send the full existing drive model number and a motor nameplate photo. For example: “We use SV075iG5A-4 with a 7.5 kW motor, an external run switch and a speed potentiometer.” This establishes the voltage, rating and control method.

For communication control, include the PLC model and protocol. For a remote keypad, send its photo. If panel space is tight, include mounting and available-space photos. 2SK can then help select a G100/G100C and prepare a quotation.

Planning an iG5A Replacement? Explore G100.

Send your existing model number and application details so we can identify the required configuration. 2SK · Korea: 1833-7728 · 2sk@2sk.co.kr

View G100 products and lineup →Request replacement advice or a quotation →

Frequently Asked Questions
Can G100 replace iG5A? LS ELECTRIC lists corresponding G100/G100C models in its migration guide. Match input voltage, motor rated current, I/O, options and installation conditions.
What replaces a 3.7 kW iG5A? Select the corresponding 4 kW G100C: for example, SV037iG5A-4 → LSLV0040G100C-4EONN.
Do all G100 drives include an EMC filter and STO? No. These depend on the exact model. G100C, standard G100 and STO versions also have different terminal arrangements.

Simple Glossary
V/F: basic control that adjusts voltage with frequency.
Sensorless vector control: estimates the motor state without a separate speed sensor.
EMC filter: reduces electromagnetic noise.
STO: a safety function that prevents torque-producing output. It does not replace electrical isolation for maintenance.
Rated current: the current used for selection under specified operating conditions.

References: LS ELECTRIC G100 Series Korean catalogue (June 2025), G100/G100C migration leaflet (20 April 2021), and G100(C) Korean user manual V4.04 (1 October 2026). Product ranges and functions follow the 2025 catalogue; replacements up to 4 kW are based on G100C. Product and keypad images: LS ELECTRIC. Replacement, wiring and commissioning must be performed by qualified electrical personnel using the applicable manual and site design. Isolate power and verify residual voltage before work; check rotating parts and restart conditions before testing.

LS G100 VFD: iG5A Replacement and Model Selection Guide — original reference image 9

#G100 #G100VFD #LSG100 #iG5A #iG5AReplacement #G100C #LSInverter #LSELECTRIC #MotorDrive #VFDReplacement #2SK

English edition by 2SK. Original catalogue/reference images are retained; some labels within images are in Korean. Read the original Korean article

2SK Tech Blog

E.mail. 2sk@2sk.co.kr  Tel.1833-7728  Fax.031-479-3585


Company Name: 2SK 

Business Registration No.: 657-76-00077


Store: #16-111, Anyang International Distribution Complex, 92 LS-ro, Dongan-gu, Anyang-si, Gyeonggi-do, Postal Code 14771, Republic of Korea

Office: Room 503, Building B, Geumjeong Station 3rd SK V1 Center, 91 LS-ro 116beon-gil, Dongan-gu, Anyang-si, Gyeonggi-do, Republic of Korea

Factory: 1F, 27 Heongan-daero 49beon-gil, Dongan-gu, Anyang-si, Gyeonggi-do, Republic of Korea


CEO: Shin Jae-woon


Mail-Order Business License: No. 2017-Anyang Dongan-0311

Retail Webpage: https://2sk.co.kr

Copyright: Copyright ⓒ 2SK SOLUTION. All rights reserved.


MON-FRI · AM 09:00 ~ PM 05:00
LUNCH · PM 12:00 - PM 01:00
SAT.SUN.HOLIDAY OFF