A standard contactor can control a motor running in one direction. Equipment such as conveyors and transfer mechanisms that needs both forward and reverse operation requires a different arrangement. This is where LS ELECTRIC reversing contactors come in.

The system involves more than placing two contactors side by side. The power circuit must reverse the phase sequence, interlocks must prevent simultaneous closing, and the control circuit must manage direction changes after stopping. This guide explains the components and operation around these three requirements.

Reversing two phases changes the direction of rotation

For a conventional three-phase induction motor, swapping any two supply phases changes the direction of rotation. Forward and reverse contactors supply the motor with different phase sequences.

Change the phase sequence to change the direction

Operating examplePhase sequence supplied to the motor
ForwardR → S → T
ReverseT → S → R (swap R and T)

2SK conceptual illustration—not a terminal wiring diagram.

These sequences illustrate the principle. The machine's operating requirements determine which direction is called forward. This explanation should not be applied directly to single-phase motors or motors connected to a variable frequency drive (VFD).

LS Reversing Contactors: Selection, Interlocks and Accessories — original reference image 1

Reference image showing the reversing power circuit, coils and interlock contacts. Use the wiring diagram for the actual product when making connections.

Why both contactors must never close together

The forward and reverse circuits interchange two phases. Closing both contactors at once can create a short circuit between phases. Interlocks are provided to prevent this simultaneous operation.

TypeFunction
Mechanical interlockPhysically restricts the other contactor from closing while one contactor is closed.
Electrical interlockUses contacts to interrupt the opposite coil circuit according to the operating state of each contactor.

An electrical interlock normally places the opposite contactor's normally closed (NC) auxiliary contact in series with the coil circuit. When the forward contactor operates, the reverse coil circuit opens; when the reverse contactor operates, the forward coil circuit opens.

The LS UR-02 is listed with two NC contacts for electrical interlocking. Installing a component with contacts and wiring those contacts into the coil circuits are separate tasks. Mechanical assembly alone does not complete the electrical interlock.

LS Reversing Contactors: Selection, Interlocks and Accessories — original reference image 2

Examine the interlock contacts in the center together with both coil circuits. This reference image does not replace the complete control circuit for the installation.

Two contactors, an interlock and a wiring kit each have a different job

LS Reversing Contactors: Selection, Interlocks and Accessories — original reference image 3

Example of a reversing assembly. Distinguish the wiring kits at the top and bottom from the central interlock unit when selecting components.

ComponentSelection checks
Two contactorsLoad voltage and current, utilization category, coil voltage and auxiliary contact arrangement
Interlock unitCompatible contactor models, assembly requirements and electrical interlock contacts
UW wiring kitKit matched to the contactor size; identify line-side and load-side parts
Protection and control componentsCircuit breaker, overload protection, start/stop buttons and other required control components

The wiring kit forms the reversing power connections between the two contactors. It does not replace start/stop buttons, seal-in circuits, emergency-stop arrangements or overload protection circuits.

For example, the manufacturer's accessory guide lists UW-22 for MC-9b to MC-22b, and UW-63 for MC-50a and MC-65a. Interlocks and wiring kits have different compatibility requirements, so provide the contactor model when ordering accessories.

Complete assembly or separate components?

Besides a complete reversing contactor, you can consider assembling two compatible MC contactors with the appropriate interlock and wiring kit. This may help with cost or lead time when suitable contactors are already available or components can be sourced separately.

Include assembly, wiring and inspection costs in the comparison. Confirm that coil voltage, contact arrangement and protection requirements are the same. Compare equivalent specifications rather than assuming separate components will always be cheaper.

When reusing an existing contactor, check contact condition, interlock compatibility and coil specifications as well as normal operation. Matching current ratings alone do not make different contactor frames a compatible pair.

Selecting an LS reversing contactor

Representative models include MC-9bR, MC-12bR, MC-18bR, MC-22bR; MC-32aR and MC-40aR; MC-50aR and MC-65aR; and MC-75aR, MC-85aR and MC-100aR. Look for the R suffix when identifying reversing models.

Select for the motor's actual operating voltage and current, starting method and switching frequency. Normal starting and stopping have different switching demands from repeated severe duties such as jogging and plugging. Reversing applications do not all have the same duty requirements.

Check coil voltage separately. A motor supplied at 380 V may use a 220 VAC or 24 VDC coil if the control supply is separate. Confirm AC/DC type, voltage and frequency as well as contactor capacity.

Operation: forward → verify stop → reverse

Contactor operating states

Operating stateForward MC / Reverse MC
ForwardON / OFF
StoppedOFF / OFF
ReverseOFF / ON
Prohibited stateON / ON — prevent simultaneous closing

2SK conceptual illustration—not a terminal wiring diagram.

In normal reversing operation, a forward command closes the forward contactor. A stop command releases it, and the reverse command is permitted after the stopped condition has been confirmed. In a seal-in circuit, the motor keeps running after the start button is released, making the stop circuit essential.

An interlock prevents simultaneous closing; it does not detect whether the motor shaft has stopped. The motor may coast after the forward contactor opens. Design stop confirmation and direction-change delay around the load and braking conditions.

Plugging—applying the opposite phase sequence while the motor is still rotating—is different from restarting in reverse after a stop. Braking applications require a review of contactor utilization category and motor/load limits. Do not apply an arbitrary universal delay.

Checks after assembly or replacement

Qualified electrical personnel must isolate both power and control supplies and verify absence of voltage before working. Fit interlocks according to the manufacturer's instructions and connect the correct line-side and load-side wiring kit parts. Follow the model-specific wiring and terminal torque requirements.

During commissioning, confirm that each direction command operates only the intended contactor and that stop and protection circuits release it correctly. Verify simultaneous-command handling using a designed safe test procedure; do not simply energize both coils together as a test.

Check motor direction, phase currents and machine travel direction. If motion is not as expected, review the relationship between commands and connections. Never change wiring while energized.

With a VFD, direction is often controlled through the drive's control inputs. Adding reversing contactors on the drive output, or switching that output while running, requires a separate review against the drive manufacturer's instructions.

Compare quotations for complete and component-based assemblies

Example enquiry: “We need forward/reverse control for a three-phase 380 V motor. The motor rated current is ___ A and the coil supply is 220 VAC. Please compare a complete reversing assembly with two contactors, an interlock and a wiring kit.”

This information helps us compare the main units and accessories on the same basis. If reusing a contactor, also send its full model number and coil nameplate photo. 2SK can review LS Metasol reversing contactors, UR interlocks, UW wiring kits and the required auxiliary contacts together.

Compare complete assemblies and separate components.

2SK · 1833-7728 (Korea)
2sk@2sk.co.kr

Interlocks & Wiring Kits · Request a Quote ↗

View Reversing Contactors ↗

The text and illustrations explain the products. Actual component combinations, wiring and operating conditions must follow current manufacturer documentation and the installation design. Installation and commissioning must be performed by qualified electrical personnel.

LS Reversing Contactors: Selection, Interlocks and Accessories — original reference image 4

#LSReversingContactor #ReversingContactor #ForwardReverse #MC9bR #MC22bR #MC32aR #MC65aR #UR02 #UW22 #UW63 #Interlock #WiringKit #LSELECTRIC #2SK

English edition by 2SK. Original catalogue/reference images are retained; some labels within images are in Korean. Read the original Korean article

2SK Tech Blog

E.mail. 2sk@2sk.co.kr  Tel.1833-7728  Fax.031-479-3585


Company Name: 2SK 

Business Registration No.: 657-76-00077


Store: #16-111, Anyang International Distribution Complex, 92 LS-ro, Dongan-gu, Anyang-si, Gyeonggi-do, Postal Code 14771, Republic of Korea

Office: Room 503, Building B, Geumjeong Station 3rd SK V1 Center, 91 LS-ro 116beon-gil, Dongan-gu, Anyang-si, Gyeonggi-do, Republic of Korea

Factory: 1F, 27 Heongan-daero 49beon-gil, Dongan-gu, Anyang-si, Gyeonggi-do, Republic of Korea


CEO: Shin Jae-woon


Mail-Order Business License: No. 2017-Anyang Dongan-0311

Retail Webpage: https://2sk.co.kr

Copyright: Copyright ⓒ 2SK SOLUTION. All rights reserved.


MON-FRI · AM 09:00 ~ PM 05:00
LUNCH · PM 12:00 - PM 01:00
SAT.SUN.HOLIDAY OFF