2SK TECH BLOG · LS ELECTRIC MT SERIES
LS TOR Thermal Overload Relays: MT Selection, Current Settings, Wiring and Reset
From MT-12 to MT-800: a practical guide to motor protection relays used with magnetic contactors.
Welcome to 2SK.
Open a motor control panel and you may see a device with a small adjustment dial beneath the contactor. This is the LS MT thermal overload relay, also known as TOR or THR.
Selection requires more than similar appearance: check contactor compatibility, current adjustment range and protection type. Correct current settings and post-trip reset procedures are equally important.

MT belongs to the thermal TOR category. Its sensing method and functions differ from electronic EMPR relays.
01. How Does a TOR Stop the Motor?
Motor overload increases current, heating and bending the TOR's internal bimetal elements. When the response reaches the trip threshold, the mechanism changes the auxiliary-contact state.
In a typical motor circuit, the TOR's NC contact is wired in series with the contactor coil. A trip opens this contact, removes coil power and opens the contactor's main contacts to stop the motor.
Understand the Separate Roles.
TOR detects overload; the contactor switches motor power; the selected breaker/fuse provides short-circuit protection. TOR alone does not provide short-circuit protection or supply isolation.
Current magnitude, duration and existing heat all influence operation. Residual heat helps explain why a recently tripped TOR can trip sooner after restarting.
02. Check the 2H, 3H, 3K or 3D Suffix
MT-32 identifies the body, not the complete protection type. Check the /2H, /3H, /3K or /3D suffix.
| Type | Construction / characteristic | Selection point |
|---|
| 2H standard | Three poles, two elements; Class 10A | Basic thermal overload protection |
| 3H three-element | Three poles, three elements; Class 10A | Three thermal sensing elements |
| 3K phase-loss protection | Three poles, three elements with differential mechanism; Class 10A | Check 3K and its operating characteristic when phase-loss protection is required |
| 3D delayed operation | Three poles, three elements; Class 20 | For long starting times, review both starting conditions and motor thermal limits |
Class 20 does not mean the relay always trips exactly 20 seconds after overcurrent begins. Trip class defines performance under specified test conditions. Actual time depends on current multiple and cold/hot state.
Before changing to 3D because of starting trips, check starting current, acceleration time and load. Delayed protection must still operate within the motor's withstand limits.
If you need phase reversal, undercurrent, ground-fault detection, current display or communication, compare electronic EMPR models offering those functions.
03. Match MT to MC, Then Select the Current Range
Direct mounting requires a compatible MC/MT combination. The table summarizes main Metasol combinations. The listed family ranges do not mean one relay adjusts across the entire range.
| Compatible contactor | TOR body | Family current-adjustment range |
|---|
| MC-6a·9a·12a·18a | MT-12 | 0.1~18A |
MC-9b·12b·18b·22b MC-32a·40a | MT-32 | 0.1~40A |
| MC-50a·65a | MT-63 | 4~65A |
| MC-75a·85a·100a | MT-95 | 7~100A |
| MC-130a·150a | MT-150 | 34~150A |
| MC-185a·225a | MT-225 | 65~240A |
| MC-265a·330a·400a | MT-400 | 85~400A |
| MC-500a·630a·800a | MT-800 | 200~800A |
An MT-32 with a 9–13 A dial range suits a different current requirement from a 12–18 A version. Specify “MT-32/2H, 9–13 A, for MC-32a” rather than just “MT-32.”
Check older models such as MC-48a from their nameplates. For replacement, verify actual connections and compatibility instead of matching only to a current catalogue name.

Example compact MT relay. Read the body model and dial current range together.

Example larger MT relay. Connections and compatible contactors differ as well as current range.
04. Direct Mounting or Separate Installation?
Mounting the TOR directly beneath the MC creates a compact motor starter. The mechanical and electrical connection arrangement must be compatible.

Contactor and TOR assembly: the upper contactor switches power; the lower relay detects overload.
If panel layout or existing wiring requires separation, consider the appropriate UZ separate-mounting unit for MT-12, MT-32, MT-63, MT-95, MT-150 and other supported models. Check current-code and terminal variations.

A separate-mounting unit supports the TOR and provides main-circuit wiring connections.

TOR and mounting-base assembly. Match the relay body and installation unit.
Separate Mounting Does Not Mean Stopping the Motor Without a Contactor.
It separates the physical mounting location. A power-switching device and trip-interlocked control circuit are still required.
05. Set Current from the Motor Nameplate
Start with motor rated current for the actual voltage and connection—not the 32 A contactor or 50 A breaker label. If the nameplate lists currents for several voltages, use the active operating condition.
Example: An 11 A Motor
For a typical direct-on-line circuit with the TOR sensing motor line current, select a range containing 11 A and use that rating as the setting basis. An MT-32 with a 9–13 A range is one example. Confirm installation position, manufacturer instructions and motor operating conditions.
Do not raise the dial to the starting-current value. Select overload protection to accommodate the starting characteristic. If trips occur only during starting, first check acceleration time, voltage, load and trip class.
In Star-Delta Circuits, Relay Location Matters
A line-mounted TOR measures a different current from one inside the delta winding circuit. Inside-delta arrangements may use about 1/√3, or 0.58, of line current as the setting basis. Do not apply that factor to every star-delta circuit; identify the current actually sensed in the drawing.
Stay Within the Range—and Meet the Protection Requirement
A movable dial does not justify an arbitrary setting. Match motor protection within the product range, considering panel temperature, installation and measured running current. Record the setting for future comparison.
06. Separate Main-Circuit and Control-Circuit Wiring
The main circuit carries motor current. The control circuit operates the contactor. Keeping these separate makes TOR terminal functions easier to understand.
| Terminal / circuit | Typical function | Check |
|---|
1/L1·3/L2·5/L3 2/T1·4/T2·6/T3 | Three-phase main-circuit input/output | Model markings, cable size and tightening torque |
| 95–96 | Usually NC; opens on trip | Protective contact in series with the contactor coil circuit |
| 97–98 | Usually NO; closes on trip | Alarm/status signal; check the receiving circuit and contact rating |
| MC A1/A2 | Contactor coil terminals | Coil AC/DC and rated voltage |
A typical functional path is control supply → stop/protective conditions → TOR NC contact → MC coil. The actual circuit can also include START, seal-in contacts, emergency stop and other interlocks.

Original protection-interlock concept diagram. Start, stop, seal-in and emergency-stop details are omitted; it is not a construction wiring drawing.
The TOR NC contact does not interrupt motor main current directly. Match control voltage/current to its contact rating and wire by the diagram and markings. A 380 V motor does not necessarily use a 380 V contactor coil.
Although the diagram groups EMPR, EOCR and TOR, actual output arrangements and terminal numbers differ by product. When replacing a relay, verify the new contact operation rather than transferring wires by old numbers alone.
07. Front Controls: TEST, TRIP and RESET

Example MT front layout. Check the markings on the actual product because layouts vary.
| Control | Purpose | Practical check |
|---|
| Current adjustment dial | Set overload protection current | Use motor nameplate and TOR sensing location |
| STOP / TEST | Stop / test operation | Check contact response and the connected control circuit as instructed |
| TRIP indicator | Show tripped state | Distinguish protection operation from ordinary stopping |
| RESET / H·A | Select manual/automatic reset and reset the relay | Choose reset mode with machine restart behavior in mind |

Front-control reference image. Read the model instructions and site operating conditions before use.
What Does TEST Check?
TEST helps verify protective-contact and control-circuit coordination: does the contactor release and does the trip signal reach its destination? It does not by itself validate actual overload trip time or the complete protection performance.
Allow Cooling Before RESET
The bimetal must cool sufficiently before a thermal relay can reset. If reset is not immediately possible, investigate the overload and wait for cooling rather than repeatedly pressing the button. Restarting under the same fault condition can cause another trip.
Automatic Reset and Automatic Restart Are Different
In automatic reset mode, protective contacts can return after cooling. Whether the motor restarts depends on the external circuit. A maintained run command can cause restart on reset, so prevent unexpected movement where people may approach the machine.
08. Repeated Trips? Do Not Start by Raising the Dial
Repeated trips can indicate incorrect settings or a motor/load problem. Classifying when the trip occurs helps focus the checks.
| Symptom | First checks |
|---|
| Trips during starting | Starting time, voltage drop, mechanical restraint, trip class and setting |
| Trips after running for a while | Phase currents, increased load, cooling and panel temperature |
| Trips sooner after restarting | Residual motor/TOR heat, starting frequency and whether the cause was removed |
| Large phase-current difference | Supply phase loss/imbalance, contactor contacts and terminal connections |
| TOR trips but MC stays closed | NC-contact interlock, bypass wiring, control circuit and contactor condition |
Record motor nameplate current, TOR setting, three-phase running currents, starting time and time to trip. These details are far more useful than “it keeps tripping.”
09. Commissioning Sequence
① Confirm selection: MC/MT models, protection type, current range and mounting unit. Match cable size and tightening requirements to the product documentation.
② Check settings and control: set current from the motor nameplate and sensing location. Verify reset mode and NC protective interlock.
③ Test and start: follow the test procedure to check contactor release and alarms, then measure starting current and time during actual startup.
④ Record operation: note stable phase currents and settings for comparison after future load changes or trips.
10. Information for TOR Replacement and Quotations
For replacement, send a front photo of the TOR, contactor nameplate and motor nameplate. For separate mounting, include the base and wiring.
For new selection, provide motor voltage/current, starting method, contactor model and required protection type. Include long starting times or star-delta circuit details.
Stock and lead time depend on type, current range and order date. Tell us quantity and planned replacement date so we can check availability.

Use the link below for LS TOR MT product information and selection enquiries.
Related Products
LS Metasol contactors · EMPR electronic motor protection relays
This article and its images explain selection and operation. Qualified electrical personnel must isolate all relevant supplies, verify no voltage and follow the current model instructions and site design for installation, wiring and testing.
#LSELECTRIC #TOR #ThermalOverloadRelay #OverloadRelay #MotorProtection #MT12 #MT32 #MT63 #MT95 #MT150 #MT225 #MT400 #MT800 #TORSettings #TORWiring #Metasol #MagneticContactor #2SK
2SK TECH BLOG · LS ELECTRIC MT SERIES
LS TOR Thermal Overload Relays: MT Selection, Current Settings, Wiring and Reset
From MT-12 to MT-800: a practical guide to motor protection relays used with magnetic contactors.
Welcome to 2SK.
Open a motor control panel and you may see a device with a small adjustment dial beneath the contactor. This is the LS MT thermal overload relay, also known as TOR or THR.
Selection requires more than similar appearance: check contactor compatibility, current adjustment range and protection type. Correct current settings and post-trip reset procedures are equally important.
MT belongs to the thermal TOR category. Its sensing method and functions differ from electronic EMPR relays.
01. How Does a TOR Stop the Motor?
Motor overload increases current, heating and bending the TOR's internal bimetal elements. When the response reaches the trip threshold, the mechanism changes the auxiliary-contact state.
In a typical motor circuit, the TOR's NC contact is wired in series with the contactor coil. A trip opens this contact, removes coil power and opens the contactor's main contacts to stop the motor.
TOR detects overload; the contactor switches motor power; the selected breaker/fuse provides short-circuit protection. TOR alone does not provide short-circuit protection or supply isolation.
Current magnitude, duration and existing heat all influence operation. Residual heat helps explain why a recently tripped TOR can trip sooner after restarting.
02. Check the 2H, 3H, 3K or 3D Suffix
MT-32 identifies the body, not the complete protection type. Check the /2H, /3H, /3K or /3D suffix.
Class 20 does not mean the relay always trips exactly 20 seconds after overcurrent begins. Trip class defines performance under specified test conditions. Actual time depends on current multiple and cold/hot state.
Before changing to 3D because of starting trips, check starting current, acceleration time and load. Delayed protection must still operate within the motor's withstand limits.
If you need phase reversal, undercurrent, ground-fault detection, current display or communication, compare electronic EMPR models offering those functions.
03. Match MT to MC, Then Select the Current Range
Direct mounting requires a compatible MC/MT combination. The table summarizes main Metasol combinations. The listed family ranges do not mean one relay adjusts across the entire range.
MC-32a·40a
An MT-32 with a 9–13 A dial range suits a different current requirement from a 12–18 A version. Specify “MT-32/2H, 9–13 A, for MC-32a” rather than just “MT-32.”
Check older models such as MC-48a from their nameplates. For replacement, verify actual connections and compatibility instead of matching only to a current catalogue name.
Example compact MT relay. Read the body model and dial current range together.
Example larger MT relay. Connections and compatible contactors differ as well as current range.
04. Direct Mounting or Separate Installation?
Mounting the TOR directly beneath the MC creates a compact motor starter. The mechanical and electrical connection arrangement must be compatible.
Contactor and TOR assembly: the upper contactor switches power; the lower relay detects overload.
If panel layout or existing wiring requires separation, consider the appropriate UZ separate-mounting unit for MT-12, MT-32, MT-63, MT-95, MT-150 and other supported models. Check current-code and terminal variations.
A separate-mounting unit supports the TOR and provides main-circuit wiring connections.
TOR and mounting-base assembly. Match the relay body and installation unit.
It separates the physical mounting location. A power-switching device and trip-interlocked control circuit are still required.
05. Set Current from the Motor Nameplate
Start with motor rated current for the actual voltage and connection—not the 32 A contactor or 50 A breaker label. If the nameplate lists currents for several voltages, use the active operating condition.
Example: An 11 A Motor
For a typical direct-on-line circuit with the TOR sensing motor line current, select a range containing 11 A and use that rating as the setting basis. An MT-32 with a 9–13 A range is one example. Confirm installation position, manufacturer instructions and motor operating conditions.
Do not raise the dial to the starting-current value. Select overload protection to accommodate the starting characteristic. If trips occur only during starting, first check acceleration time, voltage, load and trip class.
In Star-Delta Circuits, Relay Location Matters
A line-mounted TOR measures a different current from one inside the delta winding circuit. Inside-delta arrangements may use about 1/√3, or 0.58, of line current as the setting basis. Do not apply that factor to every star-delta circuit; identify the current actually sensed in the drawing.
Stay Within the Range—and Meet the Protection Requirement
A movable dial does not justify an arbitrary setting. Match motor protection within the product range, considering panel temperature, installation and measured running current. Record the setting for future comparison.
06. Separate Main-Circuit and Control-Circuit Wiring
The main circuit carries motor current. The control circuit operates the contactor. Keeping these separate makes TOR terminal functions easier to understand.
2/T1·4/T2·6/T3
A typical functional path is control supply → stop/protective conditions → TOR NC contact → MC coil. The actual circuit can also include START, seal-in contacts, emergency stop and other interlocks.
Original protection-interlock concept diagram. Start, stop, seal-in and emergency-stop details are omitted; it is not a construction wiring drawing.
The TOR NC contact does not interrupt motor main current directly. Match control voltage/current to its contact rating and wire by the diagram and markings. A 380 V motor does not necessarily use a 380 V contactor coil.
Although the diagram groups EMPR, EOCR and TOR, actual output arrangements and terminal numbers differ by product. When replacing a relay, verify the new contact operation rather than transferring wires by old numbers alone.
07. Front Controls: TEST, TRIP and RESET
Example MT front layout. Check the markings on the actual product because layouts vary.
Front-control reference image. Read the model instructions and site operating conditions before use.
What Does TEST Check?
TEST helps verify protective-contact and control-circuit coordination: does the contactor release and does the trip signal reach its destination? It does not by itself validate actual overload trip time or the complete protection performance.
Allow Cooling Before RESET
The bimetal must cool sufficiently before a thermal relay can reset. If reset is not immediately possible, investigate the overload and wait for cooling rather than repeatedly pressing the button. Restarting under the same fault condition can cause another trip.
Automatic Reset and Automatic Restart Are Different
In automatic reset mode, protective contacts can return after cooling. Whether the motor restarts depends on the external circuit. A maintained run command can cause restart on reset, so prevent unexpected movement where people may approach the machine.
08. Repeated Trips? Do Not Start by Raising the Dial
Repeated trips can indicate incorrect settings or a motor/load problem. Classifying when the trip occurs helps focus the checks.
Record motor nameplate current, TOR setting, three-phase running currents, starting time and time to trip. These details are far more useful than “it keeps tripping.”
09. Commissioning Sequence
① Confirm selection: MC/MT models, protection type, current range and mounting unit. Match cable size and tightening requirements to the product documentation.
② Check settings and control: set current from the motor nameplate and sensing location. Verify reset mode and NC protective interlock.
③ Test and start: follow the test procedure to check contactor release and alarms, then measure starting current and time during actual startup.
④ Record operation: note stable phase currents and settings for comparison after future load changes or trips.
10. Information for TOR Replacement and Quotations
For replacement, send a front photo of the TOR, contactor nameplate and motor nameplate. For separate mounting, include the base and wiring.
For new selection, provide motor voltage/current, starting method, contactor model and required protection type. Include long starting times or star-delta circuit details.
Stock and lead time depend on type, current range and order date. Tell us quantity and planned replacement date so we can check availability.
Use the link below for LS TOR MT product information and selection enquiries.
LS TOR Product Information and Quotations
MT-12, MT-32, MT-63, MT-95, MT-150, MT-225, MT-400 and MT-800. We help check contactor combinations and current ranges.
View TOR products and request a quotation →
2SK
Phone: 1833-7728
Email: 2sk@2sk.co.kr
Fax: 031-479-3585
Related Products
LS Metasol contactors · EMPR electronic motor protection relays
This article and its images explain selection and operation. Qualified electrical personnel must isolate all relevant supplies, verify no voltage and follow the current model instructions and site design for installation, wiring and testing.
English edition by 2SK. Original catalogue/reference images are retained; some labels within images are in Korean. Read the original Korean article