Magnetic ContactorLS Contactor Coil Current: Why Pickup and Holding Current Must Be Checked Separately

2SK ENGINEERING ยท LS ELECTRIC METASOL MC

LS Contactor Coil Current: Why Pickup and Holding Current Must Be Checked Separately

Read MC coil consumption tables, calculate AC/DC current and select PLC outputs and control power supplies.

Welcome to 2SK.

Motor power and main-contact ratings are usually the first considerations when selecting a contactor. But when a PLC or auxiliary relay controls the coil, two more questions arise: can this output operate the MC directly, and how many VA must the control transformer supply?

The answer starts with pickup and holding characteristics. Selecting from holding consumption alone can overlook the demand when the contactor first closes. Here is how to read and use the LS ELECTRIC Metasol MC data.

The 32 A Rating of MC-32a Is Not Its Coil Current

Main contacts switch the load current; the coil is the electromagnet that moves those contacts. Main-circuit current and coil current are separate specifications. Motor supply voltage and coil control voltage can also differ.

An MC-32a ordered with an AC 220 V coil needs a different control supply from one with a DC 24 V coil. Start with the model number and the coil nameplate's AC/DC, voltage and frequency markings.

LS Contactor Coil Current: Pickup vs Holding Consumption โ€” original reference image 1

Model identification from the 2SK product page. Check coil voltage and frequency along with the model. Click to enlarge.

What Do 70 VA, 9 VA and 2.3 W Mean?

The catalogue example for an 18AF AC coil lists 70 VA pickup, 9 VA holding and 2.3 W power dissipation. These describe different characteristics.

ย Pickup VA:ย  Apparent power while the contactor initially closes
ย Holding VA:ย  Apparent power while it remains closed
W: Active power / heat dissipation
A: Unit of current flowing through the coil

For AC coil current, divide the VA for the operating state by voltage. Dividing 2.3 W by 220 V does not give total AC coil current because power factor also matters.

The difference between pickup and holding consumption depends on coil design. Electronic coils can reduce consumption after pickup, so consumption does not necessarily increase in proportion to contactor frame size.

LS Metasol MC Coil Consumption Tables

The following tables summarize three-pole control-coil characteristics in the July 2024 English Metasol MS catalogue. Values are at 20ยฐC. The first table is for AC 220 V, 60 Hz; the second for AC 220 V, 50/60 Hz. Do not apply them directly to other coil voltages or four-pole products.

LS Contactor Coil Current: Pickup vs Holding Consumption โ€” original reference image 2




LS Contactor Coil Current: Pickup vs Holding Consumption โ€” original reference image 3


AC Coils ยท 18AFโ€“150AF(A)

Product / framePickup VAHolding VADissipation W
MC-6aยท9aยท12aยท18a / 18AF7092.3
MC-9bยท12bยท18bยท22b / 22AF7092.3
MC-32aยท40a / 40AF9092.7
MC-50aยท65a / 65AF110132.8
MC-75aยท85aยท100a / 100AF240175.4
MC-130aยท150a / 150AF(A)110182.7

AC/DC and Electronic Coil Families ยท AC Supply Conditions

Product / framePickup VAHolding VADissipation W
MC-130aยท150a / 150AF(B)320104.5
MC-185aยท225a / 225AF38011.64.7
MC-265aยท330aยท400a / 400AF571145
MC-500aยท630aยท800a, MCi-900ยท1050 / 800AF1000297.8

For MC-130a and MC-150a, distinguish semi-electronic (A) and electronic (B) coils: their pickup and holding values differ. An AC/DC family name does not mean every coil accepts every AC and DC voltage; check the individual coil's permitted supply.

For models absent from the table, including MC-48a, use their own documentation. A similar frame size is not a reason to substitute an adjacent model's values.

Calculating Current for an AC 220 V Coil

ย Formula: current (A) = apparent power (VA) รท voltage (V)ย 

MC-9a: pickup 70 รท 220 โ‰ˆ 0.318 A / holding 9 รท 220 โ‰ˆ 0.041 A

MC-100a: pickup 240 รท 220 โ‰ˆ 1.091 A / holding 17 รท 220 โ‰ˆ 0.077 A

MC-400a: pickup 571 รท 220 โ‰ˆ 2.595 A / holding 14 รท 220 โ‰ˆ 0.064 A

For MC-100a, calculated holding current is about 77 mA, but pickup current is about 1.09 A. A steady consumption below 0.1 A does not establish that a small output can operate it.

These are reference calculations from catalogue VA divided by rated voltage, not the maximum instantaneous waveform peak. Output selection must also account for pickup characteristics, switching ratings and operating frequency.

For DC Coils, Use Wattsโ€”and the Correct Voltage

For DC, calculate I = P รท V using power and voltage for the relevant operating state. The reference table gives 6 W pickup/holding for 18AF and 22AF, 9 W for 40AF and 65AF, and 18 W for 100AF, at DC 110 V. For example, 6 W รท 110 V โ‰ˆ 0.055 A.

ย Check the separate note for MC-130a/MC-150a 150AF(A) DC coils.ย 

The 280 W pickup / 7.5 W holding figures are for DC 24 V.

Reference: pickup 280 รท 24 โ‰ˆ 11.67 A / holding 7.5 รท 24 โ‰ˆ 0.313 A

Do not read the separate 150AF(A) figures as DC 110 V data or apply them to every MC-130a/MC-150a coil. Check the supply's pulse capability against both the size and duration of the coil's pickup demand, as well as holding power.

What Should You Check on a PLC Output or Auxiliary Relay?

A โ€œ5 Aโ€ relay label alone does not establish suitability for an MC coil. Check the specified voltage and whether the rating is for a resistive load. A coil is inductive, so both making and breaking duties matter.

Check the relevant utilization-category rating, such as AC-15 for AC electromagnets or DC-13 for DC electromagnets. For PLCs, distinguish relay and transistor outputs, then check per-channel current, common-terminal total current and inductive-load conditions. A DC transistor output cannot directly drive an AC coil.

Where direct operation is unsuitable, use an appropriately rated interposing relay or interface. Check both its contact rating and coil consumption. Select manufacturer-approved surge suppression for the coil's AC/DC supply and voltage, including its effect on release time.

Control Power Depends on How Many Contactors Pick Up Together

Three MC-9a units picking up simultaneously require a simple summed 70 VA ร— 3 = 210 VA, compared with 9 VA ร— 3 = 27 VA when all are holding.

If they operate sequentially and two are already holding when the third picks up, the example becomes 70 + 9 + 9 = 88 VA. Check whether pickup periods overlap and whether other control loads start at the same time.

Neither 210 VA nor 88 VA is automatically the final transformer rating. Consider the transformer's pickup-load capability, voltage drop and wiring losses. DC supplies also need assessment of transient overload duration and current limiting, which can prevent successful pickup.

A1/A2 Wiring and Commissioning Checks

Connect coil power to the marked A1/A2 terminals according to the wiring diagram. Where terminals are duplicated at the top and bottom, A1 connects internally to A1 and A2 to A2. They are not two independent coils.

LS Contactor Coil Current: Pickup vs Holding Consumption โ€” original reference image 4

Terminal arrangement diagram: upper and lower A1 are connected, as are upper and lower A2. This does not mean A1 is shorted to A2. Click to enlarge.

Check polarity markings on DC and electronic coils. In a seal-in circuit, the auxiliary contact maintains the start command, while stop and protective contacts interrupt coil power as specified in the circuit design.

During commissioning, check start/stop, seal-in release, contactor release on protective-relay operation and restart behavior after power restoration. If a contactor chatters, inspect coil terminal voltage during pickup, nameplate compatibility, connections and mechanical condition before trying repeatedly.

Include Both Model Number and Coil Voltage in Your Enquiry

โ€œWe use MC-100a with AC 220 V, 60 Hz coils. Three will pick up simultaneously, controlled by PLC relay outputs. Please help us review the control supply and interposing relays.โ€

Send the model, coil supply, number of simultaneous pickups and control-device details. For an existing installation, include body and coil nameplate photos and the control schematic. We can help review main-circuit and coil requirements from MC-9a/MC-22b through MC-100a, MC-150a, MC-400a and MC-800a.

Tell us the model number and coil voltage.

Contact 2SK for LS Metasol contactor selection and control-circuit component enquiries.

Product information and quotations โ†—

2SK ยท Korea: 1833-7728 ยท Email: 2sk@2sk.co.kr

Numerical source: LS ELECTRIC Metasol MS English catalogue, July 2024, pp. 24โ€“25 (three-pole coil characteristics) and pp. 61/89 (control-contact ratings). Tables summarize specific reference conditions. Qualified electrical personnel must select, wire and test against the supplied product nameplate, current model/coil documentation and site design.

LS ELECTRIC Metasol MS Catalogue ยท Reference

LS Contactor Coil Current: Pickup vs Holding Consumption โ€” original reference image 5

#ContactorCoil #CoilCurrent #Metasol #ControlTransformer #PLC #LSELECTRIC #2SK

English edition by 2SK. Original catalogue/reference images are retained; some labels within images are in Korean. Read the original Korean article

2SK Tech Blog

E.mail. 2sk@2sk.co.kr  Tel.1833-7728  Fax.031-479-3585


Company Name: 2SK 

Business Registration No.: 657-76-00077


Store: #16-111, Anyang International Distribution Complex, 92 LS-ro, Dongan-gu, Anyang-si, Gyeonggi-do, Postal Code 14771, Republic of Korea

Office: Room 503, Building B, Geumjeong Station 3rd SK V1 Center, 91 LS-ro 116beon-gil, Dongan-gu, Anyang-si, Gyeonggi-do, Republic of Korea

Factory: 1F, 27 Heongan-daero 49beon-gil, Dongan-gu, Anyang-si, Gyeonggi-do, Republic of Korea


CEO: Shin Jae-woon


Mail-Order Business License: No. 2017-Anyang Dongan-0311

Retail Webpage: https://2sk.co.kr

Copyright: Copyright โ“’ 2SK SOLUTION. All rights reserved.


MON-FRI · AM 09:00 ~ PM 05:00
LUNCH · PM 12:00 - PM 01:00
SAT.SUN.HOLIDAY OFF