Welcome to 2SK.
When replacing a contactor, you will encounter names such as MC, GMC-P2, MD and MCi. Similar appearance or equal current ratings are not enough: identify the load being switched and the required coil voltage.
This guide organizes LS ELECTRIC Metasol contactors and related products by application, then explains basic operation and replacement checks. These devices are also commonly called magnetic contactors.
A Contactor Switches a Load ON and OFF
A magnetic contactor energizes a coil to move its main contacts and switch power to a motor or heater. On a standard non-latching contactor, the contacts return to their normal state when coil power is removed.
The breaker provides functions such as short-circuit protection, the overload relay monitors motor overload, and the contactor switches according to run or protection commands. Installing an MC alone does not complete motor protection.
Standard Three-Pole Metasol MC: The Motor-Control Foundation

Representative three-pole Metasol MC image. Appearance varies by frame and specification.
For starting and stopping three-phase pumps, fans and compressors, begin with this family. Standard three-pole MC models range from MC-6a to the high-current MC-2650a.
Smaller models include MC-6a, MC-9a, MC-12a, MC-18a and MC-9b, MC-12b, MC-18b, MC-22b, followed by MC-32a, MC-40a, MC-48a, MC-50a, MC-65a, MC-75a, MC-85a and MC-100a.
Larger models include MC-130a, MC-150a, MC-185a, MC-225a, MC-265a, MC-330a, MC-400a, MC-500a, MC-630a, MC-800a, MC-1260a, MC-1400a, MC-1700a, MC-2100a and MC-2650a. Compare each model's voltage-specific AC-1 and AC-3 ratings; the entire range does not share one motor-duty rating basis.
For motors, use AC-3 rated current and motor power at the actual operating voltage. Do not substitute resistive-load AC-1 ratings or select from the model number alone. Jogging and frequent reversing require assessment of switching duty.
Product information and quotations ↗
Four-Pole and Reversing Types: Different Contacts and Operation

Representative four-pole contactor image.
Use a four-pole contactor where the circuit requires four main contacts. Examples include MC-9a/4, MC-12a/4, MC-18a/4, MC-32a/4 and MC-40a/4. Check contact arrangement and ratings; four poles do not always mean the same contact configuration.
A three-phase four-wire system does not automatically require a four-pole MC. Determine whether neutral switching is needed and permitted by the design, then check contact arrangement and operating requirements.
Product information and quotations ↗
Reversing Contactors for Forward and Reverse Rotation

Example reversing assembly. Include the required interlocks and connecting accessories.
A reversing assembly combines two contactors to control motor direction. Examples include MC-9bR, MC-12bR, MC-18bR, MC-22bR, MC-32aR, MC-40aR, MC-50aR and MC-65aR.
Use mechanical and electrical interlocking to prevent simultaneous forward/reverse pickup. Whether reversal is permitted while the motor is turning is a separate design issue: account for load characteristics and stopping/changeover time.
Product information and quotations ↗
Single-Phase GMC-P2 and Compact GMC-D: Check the Contacts

Representative GMC-P2 single-phase two-pole contactor.
The single-phase GMC-P2 range comprises GMC-10P2, GMC-20P2, GMC-25P2, GMC-30P2, GMC-35P2 and GMC-40P2. Consider it for single-phase air-conditioning, refrigeration and display-case loads.
For example, GMC-20P2 is listed at AC-3 20 A for 200–220 V and 17 A for 380–440 V. Ratings change with voltage. Select motor and heater loads by the appropriate duty, and check main-circuit connections and coil voltage.
Product information and quotations ↗
Read the Full GMC-20D / GMC-25D Model Number

Representative GMC-D image. Distinguish D2/D3 and contact configuration.
The compact range includes GMC-20D2, GMC-20D3, GMC-25D2 and GMC-25D3. The manufacturer's designation distinguishes D2 with 2NO or 2NO+1NC from D3 with 3NO.
Do not group every GMC-D as the same three-pole product. Specify D2 or D3 and the required contacts, not just “GMC-20D.” Review the intended low-switching-frequency HVAC or refrigeration duty.
Product information and quotations ↗
Distinguish MD for DC Loads from MCi for Renewable Energy
The MD DC-load family includes MD-30a, MD-60a and MD-100a. DC switching depends on voltage and load type; check the applicable DC-1, DC-3 or DC-5 rating.
A standard MC with a DC 24 V coil is not automatically suitable for switching a DC load at any desired voltage/current. Coil AC/DC describes the control supply; main-contact DC ratings are separate. Select MD using voltage, load type and the manufacturer's specified connection arrangement.
Product information and quotations ↗
MCi for Renewable Energy: Check AC 1000 V Ratings

Representative MCi image. Check AC-side application conditions and temperature-dependent ratings.
MCi-900, MCi-1050, MCi-1260, MCi-1700, MCi-2100 and MCi-2650 form the renewable-energy contactor range. Review them separately from standard MC for AC 1000 V applications.
Use in solar or ESS equipment does not make MCi a DC contactor. Identify whether the installation point is on the AC or DC side.
Panel temperature also matters. MCi-900 is listed at AC-1 1000 VAC as 900 A at 55°C, 850 A at 65°C and 700 A at 70°C. Its allowable current changes with temperature.
Product information and quotations ↗
MR Auxiliary Relays and MC Accessories

Representative MR auxiliary relay. Select using control-circuit contact ratings.
MR-4, MR-6 and MR-8 distribute signals and implement control conditions. Their role differs from main contacts that switch motor power.
A normally open (NO, a) contact closes when operated; a normally closed (NC, b) contact opens. Thus 2a2b means two NO and two NC contacts. Check voltage and control-load rating as well as contact count.
Accessories include UA-1, UA-2, UA-4 and AU-100 auxiliary contacts; US/AS surge units; UR/UW interlock-related parts; and ML latch units. Compatibility varies with frame and coil voltage, so include the contactor model when ordering accessories.
Latched contactors hold and release differently from standard units. Check the dedicated control circuit and manufacturer operating conditions, including the required state during power loss.
Product information and quotations ↗
View auxiliary contacts, surge units and interlocks ↗
MC-65aSP for Welder Electric-Shock Prevention Devices

Representative MC-65aSP welding contactor.
MC-65aSP is designed for electric-shock prevention devices used with AC arc welders. Its application differs from a general three-phase motor contactor.
The contactor alone does not replace the complete protective device. Match main contacts, auxiliary options and control voltage to the device circuit. For replacement of an older CH-10N/SP, send the existing nameplate and circuit information.
Product information and quotations ↗
Basic Operation: Separate Main and Coil Circuits
A contactor is not a meter with an adjustable current setting. Select the correct contactor and coil, then operate it through the external control circuit. Overload settings belong to the connected TOR/EOCR or other protective device.
On a typical three-pole MC, R/L1, S/L2 and T/L3 are supply terminals; U/T1, V/T2 and W/T3 are load terminals. A1/A2 are coil terminals. Follow the exact model's markings and diagram.
A 380 V motor circuit can use an AC 220 V or DC 24 V coil with a separate control supply. Check coil voltage, AC/DC and frequency, and observe polarity where marked on DC coils and accessories.
In a seal-in start/stop circuit, pressing START energizes the coil and closes the MC. Its NO auxiliary contact then maintains the coil circuit after START is released. A stop or protective contact interrupts the coil circuit and opens a standard non-latching MC.
This describes the operating principle. Emergency stop, restart prevention, interlocking and safety circuits must meet the machine's requirements. For PLC operation, compare output ratings with coil pickup/holding demand and use a suitable interface and surge suppression where needed.
After Replacement, Check the Load—not Just the Click
Qualified personnel must isolate both main and control supplies and verify no voltage before installation. Follow the model instructions for cable, terminals and tightening torque, then the machine's commissioning procedure.
Verify pickup on START and opening on STOP, then check motor direction, phase currents, status indication and protection. A click alone does not prove correct main-circuit wiring or motor protection.
If the MC does not pick up, check coil supply, fuses, stop/protective contacts and interlocks. For chatter, inspect pickup-time voltage drop and unstable commands. For hot terminals, check connections and contact deterioration as well as load current.
Do not arbitrarily switch a contactor on a running VFD's output. Its location and operating sequence must follow the drive manufacturer's instructions and control design.
Include Model and Coil Voltage in Your Enquiry
For example: “MC-32a, AC 220 V coil, 2NO+2NC auxiliary contacts, three-phase motor.” For new selection, also send motor voltage/current/kW, starting method and switching frequency.
For replacements, photograph coil markings, auxiliary contacts, accessories and mounting as well as the body nameplate. An older GMC, SMC or CH model number alone does not establish identical wiring or mounting for a Metasol replacement.
2SK can help with standard MC, single-phase GMC-P2, DC MD, renewable-energy MCi, MR auxiliary relays and accessories. Price and availability are confirmed for the specification at the time of enquiry.
Based on 2SK product pages and the LS ELECTRIC Metasol MS catalogue. Images represent product families; specifications and appearance vary by model, coil, contacts and options. Qualified electrical personnel must install and wire using the current product instructions and site design.

2SK ENGINEERING · LS ELECTRIC
LS Metasol Contactor Lineup: Selecting and Using MC, GMC-P2, MD and MCi
Motor, single-phase and DC applications; coil voltage, auxiliary contacts and replacement checks.
Welcome to 2SK.
When replacing a contactor, you will encounter names such as MC, GMC-P2, MD and MCi. Similar appearance or equal current ratings are not enough: identify the load being switched and the required coil voltage.
This guide organizes LS ELECTRIC Metasol contactors and related products by application, then explains basic operation and replacement checks. These devices are also commonly called magnetic contactors.
A Contactor Switches a Load ON and OFF
A magnetic contactor energizes a coil to move its main contacts and switch power to a motor or heater. On a standard non-latching contactor, the contacts return to their normal state when coil power is removed.
The breaker provides functions such as short-circuit protection, the overload relay monitors motor overload, and the contactor switches according to run or protection commands. Installing an MC alone does not complete motor protection.
Standard Three-Pole Metasol MC: The Motor-Control Foundation
Representative three-pole Metasol MC image. Appearance varies by frame and specification.
For starting and stopping three-phase pumps, fans and compressors, begin with this family. Standard three-pole MC models range from MC-6a to the high-current MC-2650a.
Smaller models include MC-6a, MC-9a, MC-12a, MC-18a and MC-9b, MC-12b, MC-18b, MC-22b, followed by MC-32a, MC-40a, MC-48a, MC-50a, MC-65a, MC-75a, MC-85a and MC-100a.
Larger models include MC-130a, MC-150a, MC-185a, MC-225a, MC-265a, MC-330a, MC-400a, MC-500a, MC-630a, MC-800a, MC-1260a, MC-1400a, MC-1700a, MC-2100a and MC-2650a. Compare each model's voltage-specific AC-1 and AC-3 ratings; the entire range does not share one motor-duty rating basis.
For motors, use AC-3 rated current and motor power at the actual operating voltage. Do not substitute resistive-load AC-1 ratings or select from the model number alone. Jogging and frequent reversing require assessment of switching duty.
Product information and quotations ↗
Four-Pole and Reversing Types: Different Contacts and Operation
Representative four-pole contactor image.
Use a four-pole contactor where the circuit requires four main contacts. Examples include MC-9a/4, MC-12a/4, MC-18a/4, MC-32a/4 and MC-40a/4. Check contact arrangement and ratings; four poles do not always mean the same contact configuration.
A three-phase four-wire system does not automatically require a four-pole MC. Determine whether neutral switching is needed and permitted by the design, then check contact arrangement and operating requirements.
Product information and quotations ↗
Reversing Contactors for Forward and Reverse Rotation
Example reversing assembly. Include the required interlocks and connecting accessories.
A reversing assembly combines two contactors to control motor direction. Examples include MC-9bR, MC-12bR, MC-18bR, MC-22bR, MC-32aR, MC-40aR, MC-50aR and MC-65aR.
Use mechanical and electrical interlocking to prevent simultaneous forward/reverse pickup. Whether reversal is permitted while the motor is turning is a separate design issue: account for load characteristics and stopping/changeover time.
Product information and quotations ↗
Single-Phase GMC-P2 and Compact GMC-D: Check the Contacts
Representative GMC-P2 single-phase two-pole contactor.
The single-phase GMC-P2 range comprises GMC-10P2, GMC-20P2, GMC-25P2, GMC-30P2, GMC-35P2 and GMC-40P2. Consider it for single-phase air-conditioning, refrigeration and display-case loads.
For example, GMC-20P2 is listed at AC-3 20 A for 200–220 V and 17 A for 380–440 V. Ratings change with voltage. Select motor and heater loads by the appropriate duty, and check main-circuit connections and coil voltage.
Product information and quotations ↗
Read the Full GMC-20D / GMC-25D Model Number
Representative GMC-D image. Distinguish D2/D3 and contact configuration.
The compact range includes GMC-20D2, GMC-20D3, GMC-25D2 and GMC-25D3. The manufacturer's designation distinguishes D2 with 2NO or 2NO+1NC from D3 with 3NO.
Do not group every GMC-D as the same three-pole product. Specify D2 or D3 and the required contacts, not just “GMC-20D.” Review the intended low-switching-frequency HVAC or refrigeration duty.
Product information and quotations ↗
Distinguish MD for DC Loads from MCi for Renewable Energy
The MD DC-load family includes MD-30a, MD-60a and MD-100a. DC switching depends on voltage and load type; check the applicable DC-1, DC-3 or DC-5 rating.
A standard MC with a DC 24 V coil is not automatically suitable for switching a DC load at any desired voltage/current. Coil AC/DC describes the control supply; main-contact DC ratings are separate. Select MD using voltage, load type and the manufacturer's specified connection arrangement.
Product information and quotations ↗
MCi for Renewable Energy: Check AC 1000 V Ratings
Representative MCi image. Check AC-side application conditions and temperature-dependent ratings.
MCi-900, MCi-1050, MCi-1260, MCi-1700, MCi-2100 and MCi-2650 form the renewable-energy contactor range. Review them separately from standard MC for AC 1000 V applications.
Use in solar or ESS equipment does not make MCi a DC contactor. Identify whether the installation point is on the AC or DC side.
Panel temperature also matters. MCi-900 is listed at AC-1 1000 VAC as 900 A at 55°C, 850 A at 65°C and 700 A at 70°C. Its allowable current changes with temperature.
Product information and quotations ↗
MR Auxiliary Relays and MC Accessories
Representative MR auxiliary relay. Select using control-circuit contact ratings.
MR-4, MR-6 and MR-8 distribute signals and implement control conditions. Their role differs from main contacts that switch motor power.
A normally open (NO, a) contact closes when operated; a normally closed (NC, b) contact opens. Thus 2a2b means two NO and two NC contacts. Check voltage and control-load rating as well as contact count.
Accessories include UA-1, UA-2, UA-4 and AU-100 auxiliary contacts; US/AS surge units; UR/UW interlock-related parts; and ML latch units. Compatibility varies with frame and coil voltage, so include the contactor model when ordering accessories.
Latched contactors hold and release differently from standard units. Check the dedicated control circuit and manufacturer operating conditions, including the required state during power loss.
Product information and quotations ↗
View auxiliary contacts, surge units and interlocks ↗
MC-65aSP for Welder Electric-Shock Prevention Devices
Representative MC-65aSP welding contactor.
MC-65aSP is designed for electric-shock prevention devices used with AC arc welders. Its application differs from a general three-phase motor contactor.
The contactor alone does not replace the complete protective device. Match main contacts, auxiliary options and control voltage to the device circuit. For replacement of an older CH-10N/SP, send the existing nameplate and circuit information.
Product information and quotations ↗
Basic Operation: Separate Main and Coil Circuits
A contactor is not a meter with an adjustable current setting. Select the correct contactor and coil, then operate it through the external control circuit. Overload settings belong to the connected TOR/EOCR or other protective device.
On a typical three-pole MC, R/L1, S/L2 and T/L3 are supply terminals; U/T1, V/T2 and W/T3 are load terminals. A1/A2 are coil terminals. Follow the exact model's markings and diagram.
A 380 V motor circuit can use an AC 220 V or DC 24 V coil with a separate control supply. Check coil voltage, AC/DC and frequency, and observe polarity where marked on DC coils and accessories.
In a seal-in start/stop circuit, pressing START energizes the coil and closes the MC. Its NO auxiliary contact then maintains the coil circuit after START is released. A stop or protective contact interrupts the coil circuit and opens a standard non-latching MC.
This describes the operating principle. Emergency stop, restart prevention, interlocking and safety circuits must meet the machine's requirements. For PLC operation, compare output ratings with coil pickup/holding demand and use a suitable interface and surge suppression where needed.
After Replacement, Check the Load—not Just the Click
Qualified personnel must isolate both main and control supplies and verify no voltage before installation. Follow the model instructions for cable, terminals and tightening torque, then the machine's commissioning procedure.
Verify pickup on START and opening on STOP, then check motor direction, phase currents, status indication and protection. A click alone does not prove correct main-circuit wiring or motor protection.
If the MC does not pick up, check coil supply, fuses, stop/protective contacts and interlocks. For chatter, inspect pickup-time voltage drop and unstable commands. For hot terminals, check connections and contact deterioration as well as load current.
Do not arbitrarily switch a contactor on a running VFD's output. Its location and operating sequence must follow the drive manufacturer's instructions and control design.
Include Model and Coil Voltage in Your Enquiry
For example: “MC-32a, AC 220 V coil, 2NO+2NC auxiliary contacts, three-phase motor.” For new selection, also send motor voltage/current/kW, starting method and switching frequency.
For replacements, photograph coil markings, auxiliary contacts, accessories and mounting as well as the body nameplate. An older GMC, SMC or CH model number alone does not establish identical wiring or mounting for a Metasol replacement.
2SK can help with standard MC, single-phase GMC-P2, DC MD, renewable-energy MCi, MR auxiliary relays and accessories. Price and availability are confirmed for the specification at the time of enquiry.
Tell Us the Product Model and Coil Voltage.
LS ELECTRIC contactor selection, replacement and accessory enquiries. 2SK · Korea: 1833-7728 · 2sk@2sk.co.kr
View the full lineup and request a quotation ↗Based on 2SK product pages and the LS ELECTRIC Metasol MS catalogue. Images represent product families; specifications and appearance vary by model, coil, contacts and options. Qualified electrical personnel must install and wire using the current product instructions and site design.
#LSContactor #Metasol #MagneticContactor #GMC #MD #MCi #LSELECTRIC #2SK