Selecting or replacing a motor protection relay requires more than reading GMP22 or GMP60 on the front. Current range, connection type, protection functions and output contacts can differ within a frame family.
This guide covers selection and practical operation of LS ELECTRIC GMP electronic motor protection relays. It is useful when researching EMPR products or searching more generally for EOCR motor protection.
ย MC Switches Power; GMP Monitors Abnormal Conditions.ย
GMP typically operates the control circuit through its output contact to release the MC. It does not directly interrupt motor main current; separate short-circuit protection by breaker/fuse is also required.
01 ยท Start with the Motor Nameplate and Full Relay Model
Check motor operating voltage and rated current. Confirm the current falls within the relay's adjustment range rather than selecting by kW alone. For replacement, also check the existing current specification, control supply and contact markings.
| Family | Typical current-adjustment ranges | Selection check |
|---|
| GMP22 | 0.3~1.5A 1~5A 4.4~22A | Separate current-range variants |
| GMP40 | 4~20A 8~40A | Distinguish 20 A and 40 A versions |
| GMP60T family | 0.5~6A 3~30A 5~60A | Not a universal range for every GMP60 model |
| GMP60-3T family | 0.5โ60 A or specified range variants | Check full model and nameplate |
| GMP80 | 16~80A | Check terminal arrangement and protection functions |
Multiple listed ranges represent different versions, not one unit covering every range. For GMP60, distinguish basic T, current-display, three-element and ground-fault models.

Original catalogue model-code guide. Confirm the applicable product and supply specification when requesting a quotation.
ย โGMP40-2P 40 Aโ and โ30 A Current Settingโ Are Different Information.ย
An 8โ40 A version can be considered for a 30 A setting, provided motor rating and sensing location support it. Do not use the product's maximum current automatically as the setting.
02 ยท Match P, T or S to the Installation
| Code | Connection type | Check |
|---|
| P | Direct connection ยท Pin | MC model and mounting compatibility |
| T | Feed-through ยท Tunnel | Cable size, direction and number of passes |
| S | Terminal connection ยท Screw | Cable/terminal specification and tightening torque |
 GMP-P direct-connect example |  GMP-T feed-through example |
 GMP60T feed-through example |  GMP-S terminal example |
 GMP80 terminal example |
|
Direct-connect relays mount to the contactor, so distinguish older GMC versions from Metasol MC versions. The manufacturer's ordering guidance uses the Sol designation for Metasol-compatible direct-connect products.
Not every GMP60 is feed-through only. GMP60-3S/3SR are terminal arrangements requiring separately purchased terminal blocks. Include these parts and installation space in selection.
03 ยท Identify Required Protection by the Full Model Code
| Protection | Condition monitored | Selection / inspection point |
|---|
| Overcurrent | Excessive motor current persisting | Load, starting conditions and operating curve |
| Locked rotor | Rotor unable to turn | Mechanical load and starting condition |
| Phase loss | One phase not supplied normally | Detection method and model-specific conditions |
| Imbalance | Unequal phase currents | Availability on the three-element model |
| Phase reversal | Incorrect phase sequence | Select a model with phase-reversal protection |
| Undercurrent | Load current falling below the threshold | Supported models such as GMP60TDa |
| Ground fault | Fault current flowing to earth | ZCT or residual-current detection |
Two-element models can provide phase-loss protection, subject to their detection conditions. Three elements do not automatically include phase-reversal protection: GMP40-3P and GMP40-3PR differ in this respect.
Basic GMP22/GMP40 models are inverse-time, while 2PD is definite-time. GMP60 is generally definite-time and GMP80 inverse-time. Definite-time products are also used for motor protection, not only heaters or lighting.
| Ground-fault model | Detection arrangement | Phase-reversal protection |
|---|
| GMP60-3TZ | Dedicated external ZCT | Not supported |
| GMP60-3TZR | Dedicated external ZCT | Supported |
| GMP60-3TN | Residual-current method; no separate ZCT | Not supported |
| GMP60-3TNR | Residual-current method; no separate ZCT | Supported |
N models do not need a separate ZCT. Describe them as residual-current detection rather than simply โbuilt-in ZCT.โ Check model-specific conditions for single-phase use, VFD output applications and sensitivity.
04 ยท CT and ZCT Have Different Jobs
 Zero-sequence current transformer (ZCT) example |  Current transformer (CT) example |
A ZCT detects ground faults. GMP60-3TZ/3TZR require the specified compatible ZCT and connection arrangement. Similar appearance does not establish compatibility with another relay's ZCT.
A CT converts load current to a level the relay can measure. For external-CT applications, define ratio, secondary rating, sensing elements and conductor routing together. Do not simply add an arbitrary CT above 60 A.
ย External CTs Change the Setting Basis.ย
With a 100/5 A CT, 80 A primary ideally corresponds to 4 A secondary. This is a calculation example; determine RC from the applicable model and circuit. Never open an energized CT secondary.
05 ยท Inverse-Time Operation: RC and TIME

Example inverse-time GMP front panel. RC sets current; TIME sets the inverse-time operating reference.
RC sets the protection current reference. Start from motor rated current, then account for external CTs and sensing location.
On inverse-time GMP22/GMP40, TIME references operation at six times the current setting (600%). A 10-second TIME setting does not mean every overcurrent trips in exactly 10 seconds.
If starting current remains near six times the setting for 10 seconds, a 10-second TIME setting interacts directly with startup. Review measured starting current/time, motor limits and the operating curve instead of adding an arbitrary delay margin.
GMP22/GMP40 LED Reference

Match color and flashing pattern to the exact model's indication table. Record a photo or video before RESET.
06 ยท Definite-Time Operation: D-TIME and O-TIME

Example GMP60T front panel. Not every definite-time model has the same dials.
| Adjustment | Meaning | Check when setting |
|---|
| RC | Protection current reference | Motor current, sensing location and CT arrangement |
| D-TIME | Starting delay | Actual starting time and applicability to each protection function |
| O-TIME | Overcurrent operating delay | Model-specific adjustable or fixed timing |
| TEST/RESET | Test and reset | Conditions under which testing stops the machine |
D-TIME accommodates normal starting current. It does not suspend all protection during the set period. Check the model's phase-loss, locked-rotor, phase-reversal and ground-fault behavior.
O-TIME determines the delay for a persisting overcurrent condition. Some models have fixed timing, so do not copy settings from a different product.
GMP60T LED Reference

Example GMP60T indication. Compare the actual front markings with the model manual.
GMP60 Ground-Fault LED and Control Reference

Example ground-fault version. Phase-reversal/ground-fault functions and dials depend on the full model.
07 ยท Check Terminal Functions, Not Numbers Alone
A1/A2 supply the relay's operating power. A 380 V motor does not mean the relay accepts 380 V. Read the relay's control-voltage nameplate first.

GMP22/GMP40/GMP80 terminal reference. Contact and connection arrangements vary within a frame.

GMP60T/TD/3T terminal reference.
| Terminal / marking | Function to verify |
|---|
| A1ยทA2 | Operating-supply input |
| 95ยท96ยท97ยท98 | Protection output contacts; check model-specific arrangement |
| Z1ยทZ2 | External-ZCT terminals on applicable models |
| 1c / 1a1b | Output-contact arrangement |
| 1c(N) / 1c(R) | Output operating-mode option |
1c and 1a1b have different contact arrangements. States during normal operation, trip and power loss also depend on the specification. Do not assume 95โ96 is closed in the required operating state without checking the internal diagram.
GMP60-3TZ/3TZR use Z1/Z2 for the dedicated ZCT. GMP60-3TN/3TNR and 3T/3TR do not use these terminals for a ZCT, so do not copy wiring from a similar-looking model.
08 ยท Output-Contact Wiring and Star-Delta Circuits
The original catalogue diagrams below are wiring references. Follow the relay-supply path separately from the contact path that stops the MC coil. Apply only the diagram matching the exact model and site circuit.
1c Output Models

Compare power and trip states for 1c(N) and 1c(R).
1a1b Output Models

1a1b and external-CT reference. Review CT ratio and current-setting basis together.
GMP60-3T and Ground-Fault Variants

External-ZCT requirements and output contacts vary by model.
Star-Delta Starting Circuit

Star-delta reference. Check sensing location and current-setting basis.
A relay on the line senses a different current from one inside the delta. Do not apply the same motor nameplate current at every location. Locate the sensing point in the drawing before setting current.
09 ยท Commissioning and Trip Checks
1. Record the existing condition. Photograph nameplates, full model, dial positions and wiring. If tripped, record LED flashing before RESET.
2. Check settings and sensing location. Review RC range, TIME or D-TIME/O-TIME, and CT/ZCT conditions. Do not indiscriminately raise current or delay to avoid trips.
3. Test the output and actual stopping action. Under controlled conditions, follow the model's TEST procedure and verify MC release. TEST alone does not validate every sensing connection or protection function.
4. Record starting and running data. Check phase currents, starting time and stable load conditions. Coordinate testing with the machine operator.
| Trip situation | First checks |
|---|
| Stops just after starting | Starting time, phase loss/reversal, mechanical restraint and setting range |
| Overcurrent during operation | Phase currents, increased load, voltage imbalance and MC contacts |
| Ground-fault indication | Motor/cable insulation and ZCT specification/wiring |
| Problem immediately after replacement | Full model, supply voltage, output contacts and sensing wiring |
ย Automatic Reset Is Not the Same as Automatic Restart.ย
GMP22-2PA, GMP40-2PA, GMP60TA and GMP80-2SA automatic reset describes relay recovery. The external circuit may then restart the motor, so design post-reset behavior as well.
10 ยท Information for a Quotation
For replacement, send front/side relay labels, motor nameplate, contactor model and surrounding wiring photos. For a new installation, specify motor rated current, control supply, connection type, phase-reversal/ground-fault requirements and quantity.
If the model is unclear, send photos and application details. 2SK can help identify the required information and product configuration.
ย Related Productsย
LS TOR thermal overload relays ยท LS Metasol MC contactors
This article and catalogue images are reference material. Qualified electrical personnel must wire, configure and test using the current model manual and site design. Isolate power and verify no voltage before wiring.

#LSELECTRIC #EMPR #MotorProtectionRelay #ElectronicOverloadRelay #GMP22 #GMP40 #GMP60 #GMP80 #GMPSettings #GMPWiring #PhaseLossProtection #PhaseReversal #GroundFaultProtection #ZCT #2SK
2SK TECH NOTE ยท LS ELECTRIC EMPR
LS GMP Motor Protection Relays: Selection, Settings and Wiring
GMP22, GMP40, GMP60 and GMP80: RC, TIME, D-TIME, O-TIME, LED indications and wiring diagrams.
Welcome to 2SK.
Selecting or replacing a motor protection relay requires more than reading GMP22 or GMP60 on the front. Current range, connection type, protection functions and output contacts can differ within a frame family.
This guide covers selection and practical operation of LS ELECTRIC GMP electronic motor protection relays. It is useful when researching EMPR products or searching more generally for EOCR motor protection.
GMP typically operates the control circuit through its output contact to release the MC. It does not directly interrupt motor main current; separate short-circuit protection by breaker/fuse is also required.
01 ยท Start with the Motor Nameplate and Full Relay Model
Check motor operating voltage and rated current. Confirm the current falls within the relay's adjustment range rather than selecting by kW alone. For replacement, also check the existing current specification, control supply and contact markings.
1~5A
4.4~22A
8~40A
3~30A
5~60A
Multiple listed ranges represent different versions, not one unit covering every range. For GMP60, distinguish basic T, current-display, three-element and ground-fault models.
Original catalogue model-code guide. Confirm the applicable product and supply specification when requesting a quotation.
An 8โ40 A version can be considered for a 30 A setting, provided motor rating and sensing location support it. Do not use the product's maximum current automatically as the setting.
02 ยท Match P, T or S to the Installation
GMP-P direct-connect example
GMP-T feed-through example
GMP60T feed-through example
GMP-S terminal example
GMP80 terminal example
Direct-connect relays mount to the contactor, so distinguish older GMC versions from Metasol MC versions. The manufacturer's ordering guidance uses the Sol designation for Metasol-compatible direct-connect products.
Not every GMP60 is feed-through only. GMP60-3S/3SR are terminal arrangements requiring separately purchased terminal blocks. Include these parts and installation space in selection.
03 ยท Identify Required Protection by the Full Model Code
Two-element models can provide phase-loss protection, subject to their detection conditions. Three elements do not automatically include phase-reversal protection: GMP40-3P and GMP40-3PR differ in this respect.
Basic GMP22/GMP40 models are inverse-time, while 2PD is definite-time. GMP60 is generally definite-time and GMP80 inverse-time. Definite-time products are also used for motor protection, not only heaters or lighting.
N models do not need a separate ZCT. Describe them as residual-current detection rather than simply โbuilt-in ZCT.โ Check model-specific conditions for single-phase use, VFD output applications and sensitivity.
04 ยท CT and ZCT Have Different Jobs
Zero-sequence current transformer (ZCT) example
Current transformer (CT) example
A ZCT detects ground faults. GMP60-3TZ/3TZR require the specified compatible ZCT and connection arrangement. Similar appearance does not establish compatibility with another relay's ZCT.
A CT converts load current to a level the relay can measure. For external-CT applications, define ratio, secondary rating, sensing elements and conductor routing together. Do not simply add an arbitrary CT above 60 A.
With a 100/5 A CT, 80 A primary ideally corresponds to 4 A secondary. This is a calculation example; determine RC from the applicable model and circuit. Never open an energized CT secondary.
05 ยท Inverse-Time Operation: RC and TIME
Example inverse-time GMP front panel. RC sets current; TIME sets the inverse-time operating reference.
RC sets the protection current reference. Start from motor rated current, then account for external CTs and sensing location.
On inverse-time GMP22/GMP40, TIME references operation at six times the current setting (600%). A 10-second TIME setting does not mean every overcurrent trips in exactly 10 seconds.
If starting current remains near six times the setting for 10 seconds, a 10-second TIME setting interacts directly with startup. Review measured starting current/time, motor limits and the operating curve instead of adding an arbitrary delay margin.
GMP22/GMP40 LED Reference
Match color and flashing pattern to the exact model's indication table. Record a photo or video before RESET.
06 ยท Definite-Time Operation: D-TIME and O-TIME
Example GMP60T front panel. Not every definite-time model has the same dials.
D-TIME accommodates normal starting current. It does not suspend all protection during the set period. Check the model's phase-loss, locked-rotor, phase-reversal and ground-fault behavior.
O-TIME determines the delay for a persisting overcurrent condition. Some models have fixed timing, so do not copy settings from a different product.
GMP60T LED Reference
Example GMP60T indication. Compare the actual front markings with the model manual.
GMP60 Ground-Fault LED and Control Reference
Example ground-fault version. Phase-reversal/ground-fault functions and dials depend on the full model.
07 ยท Check Terminal Functions, Not Numbers Alone
A1/A2 supply the relay's operating power. A 380 V motor does not mean the relay accepts 380 V. Read the relay's control-voltage nameplate first.
GMP22/GMP40/GMP80 terminal reference. Contact and connection arrangements vary within a frame.
GMP60T/TD/3T terminal reference.
1c and 1a1b have different contact arrangements. States during normal operation, trip and power loss also depend on the specification. Do not assume 95โ96 is closed in the required operating state without checking the internal diagram.
GMP60-3TZ/3TZR use Z1/Z2 for the dedicated ZCT. GMP60-3TN/3TNR and 3T/3TR do not use these terminals for a ZCT, so do not copy wiring from a similar-looking model.
08 ยท Output-Contact Wiring and Star-Delta Circuits
The original catalogue diagrams below are wiring references. Follow the relay-supply path separately from the contact path that stops the MC coil. Apply only the diagram matching the exact model and site circuit.
1c Output Models
Compare power and trip states for 1c(N) and 1c(R).
1a1b Output Models
1a1b and external-CT reference. Review CT ratio and current-setting basis together.
GMP60-3T and Ground-Fault Variants
External-ZCT requirements and output contacts vary by model.
Star-Delta Starting Circuit
Star-delta reference. Check sensing location and current-setting basis.
A relay on the line senses a different current from one inside the delta. Do not apply the same motor nameplate current at every location. Locate the sensing point in the drawing before setting current.
09 ยท Commissioning and Trip Checks
1. Record the existing condition. Photograph nameplates, full model, dial positions and wiring. If tripped, record LED flashing before RESET.
2. Check settings and sensing location. Review RC range, TIME or D-TIME/O-TIME, and CT/ZCT conditions. Do not indiscriminately raise current or delay to avoid trips.
3. Test the output and actual stopping action. Under controlled conditions, follow the model's TEST procedure and verify MC release. TEST alone does not validate every sensing connection or protection function.
4. Record starting and running data. Check phase currents, starting time and stable load conditions. Coordinate testing with the machine operator.
GMP22-2PA, GMP40-2PA, GMP60TA and GMP80-2SA automatic reset describes relay recovery. The external circuit may then restart the motor, so design post-reset behavior as well.
10 ยท Information for a Quotation
For replacement, send front/side relay labels, motor nameplate, contactor model and surrounding wiring photos. For a new installation, specify motor rated current, control supply, connection type, phase-reversal/ground-fault requirements and quantity.
If the model is unclear, send photos and application details. 2SK can help identify the required information and product configuration.
LS GMP Product Information and Quotations
Send the product nameplate and application details.
Product information and quotations โ2SK
Korea: 1833-7728 ยท Fax 031-479-3585
2sk@2sk.co.kr
ย Related Productsย
LS TOR thermal overload relays ยท LS Metasol MC contactors
This article and catalogue images are reference material. Qualified electrical personnel must wire, configure and test using the current model manual and site design. Isolate power and verify no voltage before wiring.