EMPR & TORLS GMP Motor Protection Relays: Selection, Settings and Wiring

2SK TECH NOTE ยท LS ELECTRIC EMPR

LS GMP Motor Protection Relays: Selection, Settings and Wiring

GMP22, GMP40, GMP60 and GMP80: RC, TIME, D-TIME, O-TIME, LED indications and wiring diagrams.

Welcome to 2SK.

Selecting or replacing a motor protection relay requires more than reading GMP22 or GMP60 on the front. Current range, connection type, protection functions and output contacts can differ within a frame family.

This guide covers selection and practical operation of LS ELECTRIC GMP electronic motor protection relays. It is useful when researching EMPR products or searching more generally for EOCR motor protection.

ย MC Switches Power; GMP Monitors Abnormal Conditions.ย 
GMP typically operates the control circuit through its output contact to release the MC. It does not directly interrupt motor main current; separate short-circuit protection by breaker/fuse is also required.

01 ยท Start with the Motor Nameplate and Full Relay Model

Check motor operating voltage and rated current. Confirm the current falls within the relay's adjustment range rather than selecting by kW alone. For replacement, also check the existing current specification, control supply and contact markings.

FamilyTypical current-adjustment rangesSelection check
GMP220.3~1.5A
1~5A
4.4~22A
Separate current-range variants
GMP404~20A
8~40A
Distinguish 20 A and 40 A versions
GMP60T family0.5~6A
3~30A
5~60A
Not a universal range for every GMP60 model
GMP60-3T family0.5โ€“60 A or specified range variantsCheck full model and nameplate
GMP8016~80ACheck terminal arrangement and protection functions

Multiple listed ranges represent different versions, not one unit covering every range. For GMP60, distinguish basic T, current-display, three-element and ground-fault models.

LS GMP Motor Protection Relays: Settings and Wiring Guide โ€” original reference image 1

Original catalogue model-code guide. Confirm the applicable product and supply specification when requesting a quotation.

ย โ€œGMP40-2P 40 Aโ€ and โ€œ30 A Current Settingโ€ Are Different Information.ย 
An 8โ€“40 A version can be considered for a 30 A setting, provided motor rating and sensing location support it. Do not use the product's maximum current automatically as the setting.

02 ยท Match P, T or S to the Installation

CodeConnection typeCheck
PDirect connection ยท PinMC model and mounting compatibility
TFeed-through ยท TunnelCable size, direction and number of passes
STerminal connection ยท ScrewCable/terminal specification and tightening torque
LS GMP Motor Protection Relays: Settings and Wiring Guide โ€” original reference image 2

GMP-P direct-connect example

LS GMP Motor Protection Relays: Settings and Wiring Guide โ€” original reference image 3

GMP-T feed-through example

LS GMP Motor Protection Relays: Settings and Wiring Guide โ€” original reference image 4

GMP60T feed-through example

LS GMP Motor Protection Relays: Settings and Wiring Guide โ€” original reference image 5

GMP-S terminal example

LS GMP Motor Protection Relays: Settings and Wiring Guide โ€” original reference image 6

GMP80 terminal example


Direct-connect relays mount to the contactor, so distinguish older GMC versions from Metasol MC versions. The manufacturer's ordering guidance uses the Sol designation for Metasol-compatible direct-connect products.

Not every GMP60 is feed-through only. GMP60-3S/3SR are terminal arrangements requiring separately purchased terminal blocks. Include these parts and installation space in selection.

03 ยท Identify Required Protection by the Full Model Code

ProtectionCondition monitoredSelection / inspection point
OvercurrentExcessive motor current persistingLoad, starting conditions and operating curve
Locked rotorRotor unable to turnMechanical load and starting condition
Phase lossOne phase not supplied normallyDetection method and model-specific conditions
ImbalanceUnequal phase currentsAvailability on the three-element model
Phase reversalIncorrect phase sequenceSelect a model with phase-reversal protection
UndercurrentLoad current falling below the thresholdSupported models such as GMP60TDa
Ground faultFault current flowing to earthZCT or residual-current detection

Two-element models can provide phase-loss protection, subject to their detection conditions. Three elements do not automatically include phase-reversal protection: GMP40-3P and GMP40-3PR differ in this respect.

Basic GMP22/GMP40 models are inverse-time, while 2PD is definite-time. GMP60 is generally definite-time and GMP80 inverse-time. Definite-time products are also used for motor protection, not only heaters or lighting.

Ground-fault modelDetection arrangementPhase-reversal protection
GMP60-3TZDedicated external ZCTNot supported
GMP60-3TZRDedicated external ZCTSupported
GMP60-3TNResidual-current method; no separate ZCTNot supported
GMP60-3TNRResidual-current method; no separate ZCTSupported

N models do not need a separate ZCT. Describe them as residual-current detection rather than simply โ€œbuilt-in ZCT.โ€ Check model-specific conditions for single-phase use, VFD output applications and sensitivity.

04 ยท CT and ZCT Have Different Jobs

LS GMP Motor Protection Relays: Settings and Wiring Guide โ€” original reference image 7

Zero-sequence current transformer (ZCT) example

LS GMP Motor Protection Relays: Settings and Wiring Guide โ€” original reference image 8

Current transformer (CT) example

A ZCT detects ground faults. GMP60-3TZ/3TZR require the specified compatible ZCT and connection arrangement. Similar appearance does not establish compatibility with another relay's ZCT.

A CT converts load current to a level the relay can measure. For external-CT applications, define ratio, secondary rating, sensing elements and conductor routing together. Do not simply add an arbitrary CT above 60 A.

ย External CTs Change the Setting Basis.ย 
With a 100/5 A CT, 80 A primary ideally corresponds to 4 A secondary. This is a calculation example; determine RC from the applicable model and circuit. Never open an energized CT secondary.

05 ยท Inverse-Time Operation: RC and TIME

LS GMP Motor Protection Relays: Settings and Wiring Guide โ€” original reference image 9

Example inverse-time GMP front panel. RC sets current; TIME sets the inverse-time operating reference.

RC sets the protection current reference. Start from motor rated current, then account for external CTs and sensing location.

On inverse-time GMP22/GMP40, TIME references operation at six times the current setting (600%). A 10-second TIME setting does not mean every overcurrent trips in exactly 10 seconds.

If starting current remains near six times the setting for 10 seconds, a 10-second TIME setting interacts directly with startup. Review measured starting current/time, motor limits and the operating curve instead of adding an arbitrary delay margin.

GMP22/GMP40 LED Reference

LS GMP Motor Protection Relays: Settings and Wiring Guide โ€” original reference image 10

Match color and flashing pattern to the exact model's indication table. Record a photo or video before RESET.

06 ยท Definite-Time Operation: D-TIME and O-TIME

LS GMP Motor Protection Relays: Settings and Wiring Guide โ€” original reference image 11

Example GMP60T front panel. Not every definite-time model has the same dials.

AdjustmentMeaningCheck when setting
RCProtection current referenceMotor current, sensing location and CT arrangement
D-TIMEStarting delayActual starting time and applicability to each protection function
O-TIMEOvercurrent operating delayModel-specific adjustable or fixed timing
TEST/RESETTest and resetConditions under which testing stops the machine

D-TIME accommodates normal starting current. It does not suspend all protection during the set period. Check the model's phase-loss, locked-rotor, phase-reversal and ground-fault behavior.

O-TIME determines the delay for a persisting overcurrent condition. Some models have fixed timing, so do not copy settings from a different product.

GMP60T LED Reference

LS GMP Motor Protection Relays: Settings and Wiring Guide โ€” original reference image 12

Example GMP60T indication. Compare the actual front markings with the model manual.

GMP60 Ground-Fault LED and Control Reference

LS GMP Motor Protection Relays: Settings and Wiring Guide โ€” original reference image 13

Example ground-fault version. Phase-reversal/ground-fault functions and dials depend on the full model.

07 ยท Check Terminal Functions, Not Numbers Alone

A1/A2 supply the relay's operating power. A 380 V motor does not mean the relay accepts 380 V. Read the relay's control-voltage nameplate first.

LS GMP Motor Protection Relays: Settings and Wiring Guide โ€” original reference image 14

GMP22/GMP40/GMP80 terminal reference. Contact and connection arrangements vary within a frame.

LS GMP Motor Protection Relays: Settings and Wiring Guide โ€” original reference image 15

GMP60T/TD/3T terminal reference.

Terminal / markingFunction to verify
A1ยทA2Operating-supply input
95ยท96ยท97ยท98Protection output contacts; check model-specific arrangement
Z1ยทZ2External-ZCT terminals on applicable models
1c / 1a1bOutput-contact arrangement
1c(N) / 1c(R)Output operating-mode option

1c and 1a1b have different contact arrangements. States during normal operation, trip and power loss also depend on the specification. Do not assume 95โ€“96 is closed in the required operating state without checking the internal diagram.

GMP60-3TZ/3TZR use Z1/Z2 for the dedicated ZCT. GMP60-3TN/3TNR and 3T/3TR do not use these terminals for a ZCT, so do not copy wiring from a similar-looking model.

08 ยท Output-Contact Wiring and Star-Delta Circuits

The original catalogue diagrams below are wiring references. Follow the relay-supply path separately from the contact path that stops the MC coil. Apply only the diagram matching the exact model and site circuit.

1c Output Models

LS GMP Motor Protection Relays: Settings and Wiring Guide โ€” original reference image 16

Compare power and trip states for 1c(N) and 1c(R).

1a1b Output Models

LS GMP Motor Protection Relays: Settings and Wiring Guide โ€” original reference image 17

1a1b and external-CT reference. Review CT ratio and current-setting basis together.

GMP60-3T and Ground-Fault Variants

LS GMP Motor Protection Relays: Settings and Wiring Guide โ€” original reference image 18

External-ZCT requirements and output contacts vary by model.

Star-Delta Starting Circuit

LS GMP Motor Protection Relays: Settings and Wiring Guide โ€” original reference image 19

Star-delta reference. Check sensing location and current-setting basis.

A relay on the line senses a different current from one inside the delta. Do not apply the same motor nameplate current at every location. Locate the sensing point in the drawing before setting current.

09 ยท Commissioning and Trip Checks

1. Record the existing condition. Photograph nameplates, full model, dial positions and wiring. If tripped, record LED flashing before RESET.

2. Check settings and sensing location. Review RC range, TIME or D-TIME/O-TIME, and CT/ZCT conditions. Do not indiscriminately raise current or delay to avoid trips.

3. Test the output and actual stopping action. Under controlled conditions, follow the model's TEST procedure and verify MC release. TEST alone does not validate every sensing connection or protection function.

4. Record starting and running data. Check phase currents, starting time and stable load conditions. Coordinate testing with the machine operator.

Trip situationFirst checks
Stops just after startingStarting time, phase loss/reversal, mechanical restraint and setting range
Overcurrent during operationPhase currents, increased load, voltage imbalance and MC contacts
Ground-fault indicationMotor/cable insulation and ZCT specification/wiring
Problem immediately after replacementFull model, supply voltage, output contacts and sensing wiring
ย Automatic Reset Is Not the Same as Automatic Restart.ย 
GMP22-2PA, GMP40-2PA, GMP60TA and GMP80-2SA automatic reset describes relay recovery. The external circuit may then restart the motor, so design post-reset behavior as well.

10 ยท Information for a Quotation

For replacement, send front/side relay labels, motor nameplate, contactor model and surrounding wiring photos. For a new installation, specify motor rated current, control supply, connection type, phase-reversal/ground-fault requirements and quantity.

If the model is unclear, send photos and application details. 2SK can help identify the required information and product configuration.

LS GMP Product Information and Quotations

Send the product nameplate and application details.

Product information and quotations โ†—

2SK
Korea: 1833-7728 ยท Fax 031-479-3585
2sk@2sk.co.kr

ย Related Productsย 
LS TOR thermal overload relays ยท LS Metasol MC contactors

This article and catalogue images are reference material. Qualified electrical personnel must wire, configure and test using the current model manual and site design. Isolate power and verify no voltage before wiring.

LS GMP Motor Protection Relays: Settings and Wiring Guide โ€” original reference image 20

#LSELECTRIC #EMPR #MotorProtectionRelay #ElectronicOverloadRelay #GMP22 #GMP40 #GMP60 #GMP80 #GMPSettings #GMPWiring #PhaseLossProtection #PhaseReversal #GroundFaultProtection #ZCT #2SK

English edition by 2SK. Original catalogue/reference images are retained; some labels within images are in Korean. Read the original Korean article

2SK Tech Blog

E.mail. 2sk@2sk.co.kr  Tel.1833-7728  Fax.031-479-3585


Company Name: 2SK 

Business Registration No.: 657-76-00077


Store: #16-111, Anyang International Distribution Complex, 92 LS-ro, Dongan-gu, Anyang-si, Gyeonggi-do, Postal Code 14771, Republic of Korea

Office: Room 503, Building B, Geumjeong Station 3rd SK V1 Center, 91 LS-ro 116beon-gil, Dongan-gu, Anyang-si, Gyeonggi-do, Republic of Korea

Factory: 1F, 27 Heongan-daero 49beon-gil, Dongan-gu, Anyang-si, Gyeonggi-do, Republic of Korea


CEO: Shin Jae-woon


Mail-Order Business License: No. 2017-Anyang Dongan-0311

Retail Webpage: https://2sk.co.kr

Copyright: Copyright โ“’ 2SK SOLUTION. All rights reserved.


MON-FRI · AM 09:00 ~ PM 05:00
LUNCH · PM 12:00 - PM 01:00
SAT.SUN.HOLIDAY OFF