EMPR & TORLS GMP Motor Protection Relays: An Easy Guide to Model Selection, Settings and Wiring

2SK   TECH NOTE

LS ELECTRIC · GMP SERIES

LS GMP Motor Protection Relays: An Easy Guide to Model Selection, Settings and Wiring

Understand the differences between GMP22, GMP40, GMP60 and GMP80—even if you are new to motor protection.

Pin, tunnel and screw connections / two- and three-element sensing / inverse and definite time / ground-fault protection / operation and troubleshooting

Welcome to 2SK. This guide compares LS GMP relay models and selection criteria, then covers wiring, RC/D-Time/O-Time settings and post-trip checks.

What differs between GMP22 and GMP40? Does three-element sensing include phase-reversal protection? Which dial should you adjust when a motor keeps stopping? Start by understanding the model designation.

LS GMP Model Comparison: Protection Functions and Selection — original reference image 1

LS ELECTRIC · GMP SERIES

GMP Motor Protection Relay Comparison

Compare current ratings, connection types and protection functions for GMP22, GMP40, GMP60 and GMP80.

● Function provided / – Function not provided. Compare the current range and protection functions of the exact model.

 LS GMP model comparison: current, protection functions and operating characteristics 
Rated currentConnectionModelOvercurrentPhase lossLocked rotorImbalancePhase reversalUndercurrentGround faultCharacteristic
0.3~1.5A
1~5A
4.4~22A
Direct connection (Pin)GMP22-2P (1c)●●●––––Inverse time
GMP22-2PD (1c)●●●––––Definite time
GMP22-2P (1a1b)●●●––––Inverse time
GMP22-2PA (1a1b)●●●––––Inverse time; automatic reset
GMP22-3P●●●●–––Inverse time
GMP22-3PR●●●●●––Inverse time
Terminal connection (Screw)GMP22-2S●●●––––Inverse time
GMP22-3S●●●●–––Inverse time
GMP22-3SR●●●●●––Inverse time
Feed-through (Tunnel)GMP22-2T●●●––––Inverse time
GMP22-3T●●●●–––Inverse time
GMP22-3TR●●●●●––Inverse time
4~20A
8~40A
Direct connection (Pin)GMP40-2PD●●●––––Definite time
GMP40-2P●●●––––Inverse time
GMP40-2PA●●●––––Inverse time; automatic reset
GMP40-3P●●●●–––Inverse time
GMP40-3PR●●●●●––Inverse time
Terminal connection (Screw)GMP40-2S●●●––––Inverse time
GMP40-3S●●●●–––Inverse time
GMP40-3SR●●●●●––Inverse time
Feed-through (Tunnel)GMP40-2T●●●––––Inverse time
GMP40-3T●●●●–––Inverse time
GMP40-3TR●●●●●––Inverse time
0.5~6A
3~30A
5~60A
Feed-through (Tunnel)GMP60T●●●––––Definite time
GMP60TE●●●––––Definite time
GMP60TA●●●––––Definite time; automatic reset
5~60AGMP60TD●●●––––Definite time
GMP60TDa●●●––●–Definite time
0.5~60AFeed-through (Tunnel)GMP60-3T●●●●–––Definite time
GMP60-3TR●●●●●––Definite time
GMP60-3TZ●●●●––●Definite time
GMP60-3TN●●●●––●Definite time
0.5~6A
5~60A
Feed-through (Tunnel)GMP60-3TZR●●●●●–●Definite time
GMP60-3TNR●●●●●–●Definite time
0.5~6A
5~60A
Terminal connection (Screw)GMP60-3S●●●●–––Definite time
GMP60-3SR●●●●●––Definite time
16~80AGMP80-2S●●●––––Inverse time
GMP80-2SA●●●––––Inverse time; automatic reset
GMP80-3S●●●●–––Inverse time
GMP80-3SR●●●●●––Inverse time

Before Selecting

Note 1: GMP60-3TZ/3TZR require a separate zero-sequence current transformer (ZCT).

Multiple current ranges indicate separate available variants. Confirm full model, current range, operating voltage and output-contact specification when ordering.

LS GMP product information and quotations ↗

01 / GMP GUIDE

GMP Monitors the Motor and Sends a Stop Signal

The MC switches motor power; the relay monitors abnormal conditions. When GMP detects a protection condition, its output changes state and the connected control circuit releases the contactor to stop the motor.

Installing a relay must be accompanied by a complete protective control circuit. Review short-circuit breakers/fuses and existing protection. Not every GMP includes the same functions, so check the full model.

02 / GMP GUIDE

P, T and S Describe the Connection Method

P TYPE

Pin: Direct Connection to the Contactor

LS GMP Model Comparison: Protection Functions and Selection — original reference image 2

The relay attaches directly to the contactor's load side for compact wiring. The contactor model and mounting dimensions must match. Check compatibility separately for older GMC and Metasol MC families.

T TYPE

Tunnel: Conductors Pass Through Sensing Openings

LS GMP Model Comparison: Protection Functions and Selection — original reference image 3

Check conductor size, aperture, direction, number of passes and mounting space. A conductor fitting through the opening does not establish a suitable current range.

S TYPE

Screw: Conductors Connect to Terminals

LS GMP Model Comparison: Protection Functions and Selection — original reference image 4

Check cable size, crimp terminals and tightening torque as well as current. Where a terminal block is added to a feed-through product, include the required accessories.

03 / GMP GUIDE

GMP22, 40, 60 and 80: Do Not Select by the Number Alone

The number identifies the family. Orders also require adjustment range, operating voltage, output contacts and connection type. Even GMP22 has multiple current-range versions.

Main familyConnection / indicationCharacteristic / check
GMP22 / GMP40P: pin; T: tunnel; S: screwDistinguish inverse-time and 2PD definite-time versions by model
GMP60-TFeed-through; two elementsDefinite time; check current range and reset mode
GMP60-TDFeed-through with current display; two elementsDefinite time; distinguish TD, TDa and other variants
GMP60-3T familyFeed-through; three elementsDefinite time; suffixes R, Z and N define protection differences
GMP60-3S / 3SRTerminal arrangementDefinite time; check separately purchased terminal block
GMP80-2S / 3S / 3SRTerminal type; two or three elementsInverse time; check protection by full model

This table summarizes the families. Terminal and feed-through types still require checks of ratings, dimensions and conductor capacity; frame size matters even without direct contactor mounting.

Looking for a Replacement?

Photograph the side label as well as the front. The full model, current range, operating voltage and contacts are needed for a reliable comparison.

04 / GMP GUIDE

Required Functions Matter More Than Element Count Alone

Elements refer to current-sensing CTs: two-element models sense two phases; three-element models sense all three. Evaluate element count together with the detailed model's protection functions.

FunctionSimple explanation
OvercurrentMotor current exceeds the set reference
Locked rotorRotor stops or cannot turn normally
Phase lossOne or more phases of the three-phase supply are interrupted
ImbalancePhase currents are unequal
Phase reversalSupply phase sequence changes, potentially reversing rotation

Two-element GMP models principally provide overcurrent, locked-rotor and phase-loss protection; three-element models also offer imbalance protection. Phase-loss detection conditions differ by model and fault condition.

Three Elements Do Not Automatically Include Phase-Reversal Protection

For example, GMP22-3P and GMP22-3PR are different. Check the function table for 3PR, 3TR, 3SR, TZR or TNR where phase reversal is required. A model suffix R and an output-contact [R] designation can mean different things.

05 / GMP GUIDE

Inverse Time and Definite Time Describe Trip Timing

Inverse Time: More Overcurrent, Faster Operation

For the relevant overcurrent function, trip time decreases as current rises. Greater overload produces a faster response.

Definite Time: A Set Delay Above the Threshold

If the overcurrent condition persists, operation follows the specified delay. Other elements such as phase loss or locked rotor may have separate timing.

Do not confuse these characteristics with starting delay. Allowing normal starting current and delaying an operating overcurrent trip are different functions. Adjustable and fixed settings vary by model.

06 / GMP GUIDE

For Ground-Fault Protection, Check GMP60 Z, N and R Suffixes

A ground fault is current flowing to earth, for example through damaged insulation. Ground-fault versions of GMP60-3T use either an external ZCT or internal residual-current detection.

ModelGround-fault detectionPhase reversal
GMP60-3TZExternal ZCTNot supported
GMP60-3TZRExternal ZCTSupported
GMP60-3TNResidual current; no separate ZCTNot supported
GMP60-3TNRResidual current; no separate ZCTSupported

A ZCT senses zero-sequence current. Match an external ZCT to the relay; for residual-current models, check the internal detection method's application conditions. Do not assume equal sensitivity or substitute an arbitrary ZCT.

07 / GMP GUIDE

Separate Main/Sensing, Supply and Output Wiring

① Main circuit and sensing: connect motor conductors using the specified P/T/S arrangement. Follow phase, direction and pass-count requirements. For external CTs, check approved combinations and setting basis; never open an energized CT secondary.

② Relay supply: check the marked supply terminals, such as A1/A2, and the label. A 380 V motor does not establish a 380 V relay supply.

③ Output and contactor control: use the designed contact path to interrupt the MC coil on trip. A 1c contact has COM, NO and NC, but verify actual terminal numbers and states during normal operation, trip and power loss.

Do Not Wire from “NC” Alone

Some relay contacts change state when control power is applied. Distinguish 1c/1a1b and normally energized/de-energized operation, then check the contacts in the actual operating state. Auxiliary outputs are not intended to interrupt motor main current.

08 / GMP GUIDE

RC, D-Time and O-Time: Know Each Dial's Job

This explanation applies to definite-time models with these controls, such as GMP60-T. It is not one universal sequence or setting for every GMP.

MarkingPurpose and checks
RC(A)Current reference: match motor nameplate, actual sensing location and CT arrangement.
D-TimeStarting delay: accommodate the high-current starting period using measured starting time.
O-TimeOvercurrent trip delay: check whether adjustable or fixed on the model.
TEST / RESETTest/reset: follow the manual's procedure and restrictions during operation.

1. Compare relay and motor information while stopped. Check range, operating voltage, starting method and contacts. Prevent another person from starting the motor during work.

2. Establish the current-setting basis. Use nameplate and measured current with the sensing location. In star-delta circuits, line and inside-delta currents differ.

3. Review starting and trip times. Consider acceleration time and load. Increasing D-Time does not disable all protection; check each element's operating conditions.

4. Test, then commission under controlled conditions. Verify output/contact coordination by the manufacturer procedure and record phase currents and starting time. TEST alone does not validate all sensors, wiring and functions.

Find the Cause Before Increasing Settings

Raising RC or delays simply to stop trips can delay necessary protection. Review motor rating, actual current, mechanical load, wiring and settings together.

09 / GMP GUIDE

When the Motor Stops, Record Before Resetting

Photograph a display fault code or record LED color/flashing. Checks differ depending on whether the trip occurs immediately after starting or after prolonged operation.

SituationFirst checks
Trip just after startingActual starting time, setting range, phase loss/sequence and mechanical restraint
Overcurrent while runningIncreased load, bearing/pump condition, phase currents, voltage and contacts
Ground-fault indicationInsulation, ZCT specification/wiring and sensing arrangement
Abnormal operation after replacementFull model, operating voltage, output-contact mode and mounting compatibility

The meaning and detection conditions of indications vary by model. Remove the cause and confirm safe restart before resetting. For automatic-reset versions, also consider unexpected restarting.

10 / GMP GUIDE

Start a Selection or Replacement Enquiry with Photos

Send the relay front and side label, motor nameplate and contactor model. Include quantity, required delivery date and phase-reversal/ground-fault requirements.

2SK

GMP Selection and Replacement Start with Your Application

Use the page below for LS EMPR information and configuration-specific quotations.

Product information and quotations ↗ Korea: 1833-7728

Email 2sk@2sk.co.kr
Fax 031-479-3585

This guide explains main GMP models and their use. Detailed specifications/settings vary by model and version. Qualified electrical personnel must isolate, verify no voltage and follow the current model manual and site design for wiring and inspection.

Sources: LS ELECTRIC GMP product information, catalogues and operating/setting guides
Manufacturer GMP products and downloads ↗

LS GMP Model Comparison: Protection Functions and Selection — original reference image 5

#LSGMP #EMPR #GroundFaultProtection #PhaseLoss #MotorProtection #LSELECTRIC #2SK

English edition by 2SK. Original catalogue/reference images are retained; some labels within images are in Korean. Read the original Korean article

2SK Tech Blog

E.mail. 2sk@2sk.co.kr  Tel.1833-7728  Fax.031-479-3585


Company Name: 2SK 

Business Registration No.: 657-76-00077


Store: #16-111, Anyang International Distribution Complex, 92 LS-ro, Dongan-gu, Anyang-si, Gyeonggi-do, Postal Code 14771, Republic of Korea

Office: Room 503, Building B, Geumjeong Station 3rd SK V1 Center, 91 LS-ro 116beon-gil, Dongan-gu, Anyang-si, Gyeonggi-do, Republic of Korea

Factory: 1F, 27 Heongan-daero 49beon-gil, Dongan-gu, Anyang-si, Gyeonggi-do, Republic of Korea


CEO: Shin Jae-woon


Mail-Order Business License: No. 2017-Anyang Dongan-0311

Retail Webpage: https://2sk.co.kr

Copyright: Copyright ⓒ 2SK SOLUTION. All rights reserved.


MON-FRI · AM 09:00 ~ PM 05:00
LUNCH · PM 12:00 - PM 01:00
SAT.SUN.HOLIDAY OFF