Welcome to 2SK. This guide compares LS GMP relay models and selection criteria, then covers wiring, RC/D-Time/O-Time settings and post-trip checks.
What differs between GMP22 and GMP40? Does three-element sensing include phase-reversal protection? Which dial should you adjust when a motor keeps stopping? Start by understanding the model designation.

LS ELECTRIC · GMP SERIES
GMP Motor Protection Relay Comparison
Compare current ratings, connection types and protection functions for GMP22, GMP40, GMP60 and GMP80.
● Function provided / – Function not provided. Compare the current range and protection functions of the exact model.
LS GMP model comparison: current, protection functions and operating characteristics | Rated current | Connection | Model | Overcurrent | Phase loss | Locked rotor | Imbalance | Phase reversal | Undercurrent | Ground fault | Characteristic |
|---|
0.3~1.5A 1~5A 4.4~22A | Direct connection (Pin) | GMP22-2P (1c) | ● | ● | ● | – | – | – | – | Inverse time |
|---|
| GMP22-2PD (1c) | ● | ● | ● | – | – | – | – | Definite time |
|---|
| GMP22-2P (1a1b) | ● | ● | ● | – | – | – | – | Inverse time |
|---|
| GMP22-2PA (1a1b) | ● | ● | ● | – | – | – | – | Inverse time; automatic reset |
|---|
| GMP22-3P | ● | ● | ● | ● | – | – | – | Inverse time |
|---|
| GMP22-3PR | ● | ● | ● | ● | ● | – | – | Inverse time |
|---|
| Terminal connection (Screw) | GMP22-2S | ● | ● | ● | – | – | – | – | Inverse time |
|---|
| GMP22-3S | ● | ● | ● | ● | – | – | – | Inverse time |
|---|
| GMP22-3SR | ● | ● | ● | ● | ● | – | – | Inverse time |
|---|
| Feed-through (Tunnel) | GMP22-2T | ● | ● | ● | – | – | – | – | Inverse time |
|---|
| GMP22-3T | ● | ● | ● | ● | – | – | – | Inverse time |
|---|
| GMP22-3TR | ● | ● | ● | ● | ● | – | – | Inverse time |
|---|
4~20A 8~40A | Direct connection (Pin) | GMP40-2PD | ● | ● | ● | – | – | – | – | Definite time |
|---|
| GMP40-2P | ● | ● | ● | – | – | – | – | Inverse time |
|---|
| GMP40-2PA | ● | ● | ● | – | – | – | – | Inverse time; automatic reset |
|---|
| GMP40-3P | ● | ● | ● | ● | – | – | – | Inverse time |
|---|
| GMP40-3PR | ● | ● | ● | ● | ● | – | – | Inverse time |
|---|
| Terminal connection (Screw) | GMP40-2S | ● | ● | ● | – | – | – | – | Inverse time |
|---|
| GMP40-3S | ● | ● | ● | ● | – | – | – | Inverse time |
|---|
| GMP40-3SR | ● | ● | ● | ● | ● | – | – | Inverse time |
|---|
| Feed-through (Tunnel) | GMP40-2T | ● | ● | ● | – | – | – | – | Inverse time |
|---|
| GMP40-3T | ● | ● | ● | ● | – | – | – | Inverse time |
|---|
| GMP40-3TR | ● | ● | ● | ● | ● | – | – | Inverse time |
|---|
0.5~6A 3~30A 5~60A | Feed-through (Tunnel) | GMP60T | ● | ● | ● | – | – | – | – | Definite time |
|---|
| GMP60TE | ● | ● | ● | – | – | – | – | Definite time |
|---|
| GMP60TA | ● | ● | ● | – | – | – | – | Definite time; automatic reset |
|---|
| 5~60A | GMP60TD | ● | ● | ● | – | – | – | – | Definite time |
|---|
| GMP60TDa | ● | ● | ● | – | – | ● | – | Definite time |
|---|
| 0.5~60A | Feed-through (Tunnel) | GMP60-3T | ● | ● | ● | ● | – | – | – | Definite time |
|---|
| GMP60-3TR | ● | ● | ● | ● | ● | – | – | Definite time |
|---|
| GMP60-3TZ | ● | ● | ● | ● | – | – | ● | Definite time |
|---|
| GMP60-3TN | ● | ● | ● | ● | – | – | ● | Definite time |
|---|
0.5~6A 5~60A | Feed-through (Tunnel) | GMP60-3TZR | ● | ● | ● | ● | ● | – | ● | Definite time |
|---|
| GMP60-3TNR | ● | ● | ● | ● | ● | – | ● | Definite time |
|---|
0.5~6A 5~60A | Terminal connection (Screw) | GMP60-3S | ● | ● | ● | ● | – | – | – | Definite time |
|---|
| GMP60-3SR | ● | ● | ● | ● | ● | – | – | Definite time |
|---|
| 16~80A | GMP80-2S | ● | ● | ● | – | – | – | – | Inverse time |
|---|
| GMP80-2SA | ● | ● | ● | – | – | – | – | Inverse time; automatic reset |
|---|
| GMP80-3S | ● | ● | ● | ● | – | – | – | Inverse time |
|---|
| GMP80-3SR | ● | ● | ● | ● | ● | – | – | Inverse time |
|---|
Before Selecting
Note 1: GMP60-3TZ/3TZR require a separate zero-sequence current transformer (ZCT).
Multiple current ranges indicate separate available variants. Confirm full model, current range, operating voltage and output-contact specification when ordering.
LS GMP product information and quotations ↗01 / GMP GUIDE
GMP Monitors the Motor and Sends a Stop Signal
The MC switches motor power; the relay monitors abnormal conditions. When GMP detects a protection condition, its output changes state and the connected control circuit releases the contactor to stop the motor.
Installing a relay must be accompanied by a complete protective control circuit. Review short-circuit breakers/fuses and existing protection. Not every GMP includes the same functions, so check the full model.
02 / GMP GUIDE
P, T and S Describe the Connection Method
P TYPE
Pin: Direct Connection to the Contactor

The relay attaches directly to the contactor's load side for compact wiring. The contactor model and mounting dimensions must match. Check compatibility separately for older GMC and Metasol MC families.
T TYPE
Tunnel: Conductors Pass Through Sensing Openings

Check conductor size, aperture, direction, number of passes and mounting space. A conductor fitting through the opening does not establish a suitable current range.
S TYPE
Screw: Conductors Connect to Terminals

Check cable size, crimp terminals and tightening torque as well as current. Where a terminal block is added to a feed-through product, include the required accessories.
03 / GMP GUIDE
GMP22, 40, 60 and 80: Do Not Select by the Number Alone
The number identifies the family. Orders also require adjustment range, operating voltage, output contacts and connection type. Even GMP22 has multiple current-range versions.
| Main family | Connection / indication | Characteristic / check |
|---|
| GMP22 / GMP40 | P: pin; T: tunnel; S: screw | Distinguish inverse-time and 2PD definite-time versions by model |
| GMP60-T | Feed-through; two elements | Definite time; check current range and reset mode |
| GMP60-TD | Feed-through with current display; two elements | Definite time; distinguish TD, TDa and other variants |
| GMP60-3T family | Feed-through; three elements | Definite time; suffixes R, Z and N define protection differences |
| GMP60-3S / 3SR | Terminal arrangement | Definite time; check separately purchased terminal block |
| GMP80-2S / 3S / 3SR | Terminal type; two or three elements | Inverse time; check protection by full model |
This table summarizes the families. Terminal and feed-through types still require checks of ratings, dimensions and conductor capacity; frame size matters even without direct contactor mounting.
Looking for a Replacement?
Photograph the side label as well as the front. The full model, current range, operating voltage and contacts are needed for a reliable comparison.
04 / GMP GUIDE
Required Functions Matter More Than Element Count Alone
Elements refer to current-sensing CTs: two-element models sense two phases; three-element models sense all three. Evaluate element count together with the detailed model's protection functions.
| Function | Simple explanation |
|---|
| Overcurrent | Motor current exceeds the set reference |
| Locked rotor | Rotor stops or cannot turn normally |
| Phase loss | One or more phases of the three-phase supply are interrupted |
| Imbalance | Phase currents are unequal |
| Phase reversal | Supply phase sequence changes, potentially reversing rotation |
Two-element GMP models principally provide overcurrent, locked-rotor and phase-loss protection; three-element models also offer imbalance protection. Phase-loss detection conditions differ by model and fault condition.
Three Elements Do Not Automatically Include Phase-Reversal Protection
For example, GMP22-3P and GMP22-3PR are different. Check the function table for 3PR, 3TR, 3SR, TZR or TNR where phase reversal is required. A model suffix R and an output-contact [R] designation can mean different things.
05 / GMP GUIDE
Inverse Time and Definite Time Describe Trip Timing
Inverse Time: More Overcurrent, Faster Operation
For the relevant overcurrent function, trip time decreases as current rises. Greater overload produces a faster response.
Definite Time: A Set Delay Above the Threshold
If the overcurrent condition persists, operation follows the specified delay. Other elements such as phase loss or locked rotor may have separate timing.
Do not confuse these characteristics with starting delay. Allowing normal starting current and delaying an operating overcurrent trip are different functions. Adjustable and fixed settings vary by model.
06 / GMP GUIDE
For Ground-Fault Protection, Check GMP60 Z, N and R Suffixes
A ground fault is current flowing to earth, for example through damaged insulation. Ground-fault versions of GMP60-3T use either an external ZCT or internal residual-current detection.
| Model | Ground-fault detection | Phase reversal |
|---|
| GMP60-3TZ | External ZCT | Not supported |
| GMP60-3TZR | External ZCT | Supported |
| GMP60-3TN | Residual current; no separate ZCT | Not supported |
| GMP60-3TNR | Residual current; no separate ZCT | Supported |
A ZCT senses zero-sequence current. Match an external ZCT to the relay; for residual-current models, check the internal detection method's application conditions. Do not assume equal sensitivity or substitute an arbitrary ZCT.
07 / GMP GUIDE
Separate Main/Sensing, Supply and Output Wiring
① Main circuit and sensing: connect motor conductors using the specified P/T/S arrangement. Follow phase, direction and pass-count requirements. For external CTs, check approved combinations and setting basis; never open an energized CT secondary.
② Relay supply: check the marked supply terminals, such as A1/A2, and the label. A 380 V motor does not establish a 380 V relay supply.
③ Output and contactor control: use the designed contact path to interrupt the MC coil on trip. A 1c contact has COM, NO and NC, but verify actual terminal numbers and states during normal operation, trip and power loss.
Do Not Wire from “NC” Alone
Some relay contacts change state when control power is applied. Distinguish 1c/1a1b and normally energized/de-energized operation, then check the contacts in the actual operating state. Auxiliary outputs are not intended to interrupt motor main current.
08 / GMP GUIDE
RC, D-Time and O-Time: Know Each Dial's Job
This explanation applies to definite-time models with these controls, such as GMP60-T. It is not one universal sequence or setting for every GMP.
| Marking | Purpose and checks |
|---|
| RC(A) | Current reference: match motor nameplate, actual sensing location and CT arrangement. |
| D-Time | Starting delay: accommodate the high-current starting period using measured starting time. |
| O-Time | Overcurrent trip delay: check whether adjustable or fixed on the model. |
| TEST / RESET | Test/reset: follow the manual's procedure and restrictions during operation. |
1. Compare relay and motor information while stopped. Check range, operating voltage, starting method and contacts. Prevent another person from starting the motor during work.
2. Establish the current-setting basis. Use nameplate and measured current with the sensing location. In star-delta circuits, line and inside-delta currents differ.
3. Review starting and trip times. Consider acceleration time and load. Increasing D-Time does not disable all protection; check each element's operating conditions.
4. Test, then commission under controlled conditions. Verify output/contact coordination by the manufacturer procedure and record phase currents and starting time. TEST alone does not validate all sensors, wiring and functions.
Find the Cause Before Increasing Settings
Raising RC or delays simply to stop trips can delay necessary protection. Review motor rating, actual current, mechanical load, wiring and settings together.
09 / GMP GUIDE
When the Motor Stops, Record Before Resetting
Photograph a display fault code or record LED color/flashing. Checks differ depending on whether the trip occurs immediately after starting or after prolonged operation.
| Situation | First checks |
|---|
| Trip just after starting | Actual starting time, setting range, phase loss/sequence and mechanical restraint |
| Overcurrent while running | Increased load, bearing/pump condition, phase currents, voltage and contacts |
| Ground-fault indication | Insulation, ZCT specification/wiring and sensing arrangement |
| Abnormal operation after replacement | Full model, operating voltage, output-contact mode and mounting compatibility |
The meaning and detection conditions of indications vary by model. Remove the cause and confirm safe restart before resetting. For automatic-reset versions, also consider unexpected restarting.
10 / GMP GUIDE
Start a Selection or Replacement Enquiry with Photos
Send the relay front and side label, motor nameplate and contactor model. Include quantity, required delivery date and phase-reversal/ground-fault requirements.
This guide explains main GMP models and their use. Detailed specifications/settings vary by model and version. Qualified electrical personnel must isolate, verify no voltage and follow the current model manual and site design for wiring and inspection.
Sources: LS ELECTRIC GMP product information, catalogues and operating/setting guides
Manufacturer GMP products and downloads ↗

2SK TECH NOTE
LS ELECTRIC · GMP SERIES
LS GMP Motor Protection Relays: An Easy Guide to Model Selection, Settings and Wiring
Understand the differences between GMP22, GMP40, GMP60 and GMP80—even if you are new to motor protection.
Pin, tunnel and screw connections / two- and three-element sensing / inverse and definite time / ground-fault protection / operation and troubleshooting
Welcome to 2SK. This guide compares LS GMP relay models and selection criteria, then covers wiring, RC/D-Time/O-Time settings and post-trip checks.
What differs between GMP22 and GMP40? Does three-element sensing include phase-reversal protection? Which dial should you adjust when a motor keeps stopping? Start by understanding the model designation.
LS ELECTRIC · GMP SERIES
GMP Motor Protection Relay Comparison
Compare current ratings, connection types and protection functions for GMP22, GMP40, GMP60 and GMP80.
● Function provided / – Function not provided. Compare the current range and protection functions of the exact model.
1~5A
4.4~22A
8~40A
3~30A
5~60A
5~60A
5~60A
Before Selecting
Note 1: GMP60-3TZ/3TZR require a separate zero-sequence current transformer (ZCT).
Multiple current ranges indicate separate available variants. Confirm full model, current range, operating voltage and output-contact specification when ordering.
LS GMP product information and quotations ↗01 / GMP GUIDE
GMP Monitors the Motor and Sends a Stop Signal
The MC switches motor power; the relay monitors abnormal conditions. When GMP detects a protection condition, its output changes state and the connected control circuit releases the contactor to stop the motor.
Installing a relay must be accompanied by a complete protective control circuit. Review short-circuit breakers/fuses and existing protection. Not every GMP includes the same functions, so check the full model.
02 / GMP GUIDE
P, T and S Describe the Connection Method
P TYPE
Pin: Direct Connection to the Contactor
The relay attaches directly to the contactor's load side for compact wiring. The contactor model and mounting dimensions must match. Check compatibility separately for older GMC and Metasol MC families.
T TYPE
Tunnel: Conductors Pass Through Sensing Openings
Check conductor size, aperture, direction, number of passes and mounting space. A conductor fitting through the opening does not establish a suitable current range.
S TYPE
Screw: Conductors Connect to Terminals
Check cable size, crimp terminals and tightening torque as well as current. Where a terminal block is added to a feed-through product, include the required accessories.
03 / GMP GUIDE
GMP22, 40, 60 and 80: Do Not Select by the Number Alone
The number identifies the family. Orders also require adjustment range, operating voltage, output contacts and connection type. Even GMP22 has multiple current-range versions.
This table summarizes the families. Terminal and feed-through types still require checks of ratings, dimensions and conductor capacity; frame size matters even without direct contactor mounting.
Looking for a Replacement?
Photograph the side label as well as the front. The full model, current range, operating voltage and contacts are needed for a reliable comparison.
04 / GMP GUIDE
Required Functions Matter More Than Element Count Alone
Elements refer to current-sensing CTs: two-element models sense two phases; three-element models sense all three. Evaluate element count together with the detailed model's protection functions.
Two-element GMP models principally provide overcurrent, locked-rotor and phase-loss protection; three-element models also offer imbalance protection. Phase-loss detection conditions differ by model and fault condition.
Three Elements Do Not Automatically Include Phase-Reversal Protection
For example, GMP22-3P and GMP22-3PR are different. Check the function table for 3PR, 3TR, 3SR, TZR or TNR where phase reversal is required. A model suffix R and an output-contact [R] designation can mean different things.
05 / GMP GUIDE
Inverse Time and Definite Time Describe Trip Timing
Inverse Time: More Overcurrent, Faster Operation
For the relevant overcurrent function, trip time decreases as current rises. Greater overload produces a faster response.
Definite Time: A Set Delay Above the Threshold
If the overcurrent condition persists, operation follows the specified delay. Other elements such as phase loss or locked rotor may have separate timing.
Do not confuse these characteristics with starting delay. Allowing normal starting current and delaying an operating overcurrent trip are different functions. Adjustable and fixed settings vary by model.
06 / GMP GUIDE
For Ground-Fault Protection, Check GMP60 Z, N and R Suffixes
A ground fault is current flowing to earth, for example through damaged insulation. Ground-fault versions of GMP60-3T use either an external ZCT or internal residual-current detection.
A ZCT senses zero-sequence current. Match an external ZCT to the relay; for residual-current models, check the internal detection method's application conditions. Do not assume equal sensitivity or substitute an arbitrary ZCT.
07 / GMP GUIDE
Separate Main/Sensing, Supply and Output Wiring
① Main circuit and sensing: connect motor conductors using the specified P/T/S arrangement. Follow phase, direction and pass-count requirements. For external CTs, check approved combinations and setting basis; never open an energized CT secondary.
② Relay supply: check the marked supply terminals, such as A1/A2, and the label. A 380 V motor does not establish a 380 V relay supply.
③ Output and contactor control: use the designed contact path to interrupt the MC coil on trip. A 1c contact has COM, NO and NC, but verify actual terminal numbers and states during normal operation, trip and power loss.
Do Not Wire from “NC” Alone
Some relay contacts change state when control power is applied. Distinguish 1c/1a1b and normally energized/de-energized operation, then check the contacts in the actual operating state. Auxiliary outputs are not intended to interrupt motor main current.
08 / GMP GUIDE
RC, D-Time and O-Time: Know Each Dial's Job
This explanation applies to definite-time models with these controls, such as GMP60-T. It is not one universal sequence or setting for every GMP.
1. Compare relay and motor information while stopped. Check range, operating voltage, starting method and contacts. Prevent another person from starting the motor during work.
2. Establish the current-setting basis. Use nameplate and measured current with the sensing location. In star-delta circuits, line and inside-delta currents differ.
3. Review starting and trip times. Consider acceleration time and load. Increasing D-Time does not disable all protection; check each element's operating conditions.
4. Test, then commission under controlled conditions. Verify output/contact coordination by the manufacturer procedure and record phase currents and starting time. TEST alone does not validate all sensors, wiring and functions.
Find the Cause Before Increasing Settings
Raising RC or delays simply to stop trips can delay necessary protection. Review motor rating, actual current, mechanical load, wiring and settings together.
09 / GMP GUIDE
When the Motor Stops, Record Before Resetting
Photograph a display fault code or record LED color/flashing. Checks differ depending on whether the trip occurs immediately after starting or after prolonged operation.
The meaning and detection conditions of indications vary by model. Remove the cause and confirm safe restart before resetting. For automatic-reset versions, also consider unexpected restarting.
10 / GMP GUIDE
Start a Selection or Replacement Enquiry with Photos
Send the relay front and side label, motor nameplate and contactor model. Include quantity, required delivery date and phase-reversal/ground-fault requirements.
2SK
GMP Selection and Replacement Start with Your Application
Use the page below for LS EMPR information and configuration-specific quotations.
Product information and quotations ↗ Korea: 1833-7728Email 2sk@2sk.co.kr
Fax 031-479-3585
This guide explains main GMP models and their use. Detailed specifications/settings vary by model and version. Qualified electrical personnel must isolate, verify no voltage and follow the current model manual and site design for wiring and inspection.
Sources: LS ELECTRIC GMP product information, catalogues and operating/setting guides
Manufacturer GMP products and downloads ↗
#LSGMP #EMPR #GroundFaultProtection #PhaseLoss #MotorProtection #LSELECTRIC #2SK
English edition by 2SK. Original catalogue/reference images are retained; some labels within images are in Korean. Read the original Korean article