Magnetic ContactorLS Metasol MC Latch Units: Selection and Wiring

2SK TECH NOTE · LS ELECTRIC

LS Metasol MC Latch Units: Selection and Wiring

A pulse closes the contactor; a mechanical latch holds it. Understand the difference from an electrical seal-in circuit and how release works.

Welcome to 2SK.

Sometimes a contactor must remain ON without continuously energizing its coil. A mechanical latch unit is an accessory designed for this purpose.

A latched contactor needs separate closing and release signals, and its contacts can remain closed after control power is lost. Here we cover ML-40, ML-65 and ML-150 for LS Metasol MC, along with factory-assembled latched models.

How Does a Latch Differ from a Seal-In Circuit?

A standard MC stays closed while its coil is energized. Even with an auxiliary-contact seal-in circuit, removing coil power opens the contactor.

A latch mechanically holds the contactor closed after the closing signal ends. A separate release signal unlocks the mechanism and opens the contactor.

ItemStandard MC + electrical seal-inMC + mechanical latch
Holding methodCoil remains electrically energizedClosed state is held mechanically
Loss of control powerCoil de-energizes; contactor opensLatched state can remain
Stopping methodInterrupt coil circuitApply a latch-release signal
 Maintaining Contacts Is Not Uninterruptible Power. 
A latch does not supply electricity. If load power fails, the motor loses power. When supply returns, still-closed contacts can re-energize the load, so power-restoration behavior must be designed deliberately.

Where Is a Latch Useful?

Consider a latch where long ON periods make continuous coil energization undesirable, or where control-supply fluctuations should not drop the contactor out. Suitability depends on the required machine state during power loss and faults.

Application requirementSelection consideration
Long periods ONCompare latch operation with existing coil holding consumption
Keep contacts closed during brief control-power lossReview load power and release-power availability
PLC ON/OFF controlUse closing/release pulses and status feedback
Must open on power loss or emergency stopReview stop and protective circuits before choosing a latch

A latch does not add explosion-proof certification or a safety function. Reduced continuous coil energization may reduce coil heat or hum, but does not establish longer overall contactor life or eliminate all noise. Contact wear and mechanical life remain separate considerations.

Match ML-40, ML-65 or ML-150 to the MC Model

Select the latch for the contactor frame. The table follows models listed in the Korean Metasol catalogue. For older models such as MC-48a, send a photo and nameplate so compatibility can be checked separately.

Latch unitCompatible contactorSupply arrangement
ML-40MC-6a·9a·12a·18a
MC-9b·12b·18b·22b
MC-32a·40a
Purchased separately and fitted by the user
ML-65MC-50a·65aPurchased separately and fitted by the user
ML-150MC-75a·85a·100a·130a·150aPurchased separately and fitted by the user
LS MC Latch Units: ML-40, ML-65 and ML-150 — original reference image 1

Example of a user-fitted latch. Check the actual supplied product's appearance and nameplate.

From MC-185a upward, order the designated assembled latched contactor. Do not assume a small ML accessory can be fitted to a larger standard contactor.

Latched contactorMatched latchOrdering arrangement
MC-185aL·MC-225aLAL-225Order as an assembly
MC-265aL·MC-330aL·MC-400aLAL-400Order as an assembly
LS MC Latch Units: ML-40, ML-65 and ML-150 — original reference image 2

Example of a larger latched assembly. Specify the contactor model and control supply when ordering.

Check Control Voltage Separately from Motor Voltage

A 380 V motor does not automatically require a 380 V latch. Check the contactor closing coil and latch-release coil voltages separately. A PLC's 24 V output is not automatically compatible with either existing coil.

The catalogue lists the following operating-voltage choices for ML-40, ML-65 and ML-150. These are separate order variants, not one unit accepting every listed voltage.

Nominal voltageLatch operating voltage
24VAC 24V 50/60Hz / DC 24V
48VAC 48V 50/60Hz / DC 48V
100VAC 100~127V 50/60Hz / DC 100~125V
200VAC 200~240V 50/60Hz / DC 200~220V
400VAC 380~440V 50/60Hz

AL-225 and AL-400 distinguish AC 100–127 V / DC 100–110 V and AC 200–240 V / DC 200–220 V ranges. The 100 V-series DC range differs from the smaller ML units. Confirm stock and order availability with your quotation.

Wiring Principle: A1/A2 Close; E1/E2 Release

For MC-6a/L–MC-150a/L, closing and release paths are separate. A1/A2 identify the contactor coil; E1/E2 relate to the latch-release circuit. Wire according to the actual product's internal diagram and terminal markings.

LS MC Latch Units: ML-40, ML-65 and ML-150 — original reference image 3

2SK conceptual diagram. Internal interlocking contacts, protection and interlocks are omitted; this is not a construction wiring drawing.

The sequence is: closing pulse → contacts close and latch → closing signal ends → release pulse → contacts open. Prevent simultaneous ON/OFF signals and use auxiliary-contact feedback where required.

 Do Not Leave the Release Output Energized. 
The LS catalogue warns that applying an opening signal for 1 second or longer to MC-6a/L–MC-150a/L can burn out the latch coil. Do not copy a maintained stop-button circuit. Design the pulse within the model's minimum energization time and maximum permitted input duration.

PLC control is possible. Use pulses of the required duration rather than maintained outputs, and select interfaces and surge suppression for the output type and coil voltage/current. Do not apply small-unit timing directly to larger assemblies.

Commissioning Sequence

1. Check nameplates and mechanical fitting. Confirm MC model, latch model and both coil voltages. Fit the unit according to its instructions; do not energize an incompletely engaged mechanism.

2. Remove the closing signal after pickup. Under controlled test conditions, apply the specified closing pulse and verify that the contacts remain closed after it ends.

3. Check release. Apply a release pulse within the permitted duration and verify opening. Do not hold the button or output on if the mechanism fails to release.

4. Test protection and power restoration. A standard overload circuit that only interrupts the MC coil may not stop a latched contactor. Design and test a reliable stop path for overload/emergency stop, plus the required behavior after power returns.

SymptomFirst checks
Does not remain latchedModel compatibility, fitting, coil voltage and closing-pulse duration
Does not open on release commandRelease supply/output, E1/E2 wiring and mechanism
Coil heating or smellMaintained output, rated voltage and possible coil damage
Load becomes energized when power returnsRemaining latch state and power-restoration/restart logic

Send the MC Nameplate and Control Supply for a Quotation

“ML-65 for MC-65a, with AC 220 V release power” is more useful than “one latch unit.” For a new installation, specify whether the MC body is included, PLC or pushbutton control, and quantity.

For an existing system, send MC and latch nameplate photos plus the control schematic. 2SK will help confirm compatibility and the supply configuration.

Enquire About Latch Units and Metasol MC Assemblies

Send your MC nameplate and control-supply details.

Product information and quotations ↗

2SK · Korea: 1833-7728
2sk@2sk.co.kr

This article and its conceptual diagram explain the product. Installation, wiring and testing must be performed by qualified electrical personnel after isolation and verification of no voltage, following the current model manual and site design.

LS MC Latch Units: ML-40, ML-65 and ML-150 — original reference image 4

#LatchUnit #ML40 #ML65 #ML150 #Metasol #Contactor #LSELECTRIC #2SK

English edition by 2SK. Original catalogue/reference images are retained; some labels within images are in Korean. Read the original Korean article

2SK Tech Blog

E.mail. 2sk@2sk.co.kr  Tel.1833-7728  Fax.031-479-3585


Company Name: 2SK 

Business Registration No.: 657-76-00077


Store: #16-111, Anyang International Distribution Complex, 92 LS-ro, Dongan-gu, Anyang-si, Gyeonggi-do, Postal Code 14771, Republic of Korea

Office: Room 503, Building B, Geumjeong Station 3rd SK V1 Center, 91 LS-ro 116beon-gil, Dongan-gu, Anyang-si, Gyeonggi-do, Republic of Korea

Factory: 1F, 27 Heongan-daero 49beon-gil, Dongan-gu, Anyang-si, Gyeonggi-do, Republic of Korea


CEO: Shin Jae-woon


Mail-Order Business License: No. 2017-Anyang Dongan-0311

Retail Webpage: https://2sk.co.kr

Copyright: Copyright ⓒ 2SK SOLUTION. All rights reserved.


MON-FRI · AM 09:00 ~ PM 05:00
LUNCH · PM 12:00 - PM 01:00
SAT.SUN.HOLIDAY OFF