EMPR & TORDMPi, IMP or MMP: Which Motor Protection Relay Should You Choose?

2SK    TECH NOTE

LS ELECTRIC · Electronic Motor Protection Relays

DMPi, IMP or MMP: Which Motor Protection Relay Should You Choose?

Product comparison, wiring checks, initial settings and post-trip troubleshooting.

Series features / selection / installation and operation / settings and commissioning / troubleshooting / quotations

Welcome to 2SK. Motor protection relays can look similar while offering many model variants, communication options and ground-fault functions. How do you choose the right one?

Can a replacement be selected by current alone? Should a setting be increased when trips keep occurring? This guide connects selection with practical use, focusing on the LS EMPR DMPi, IMP and MMP series.

01 / MOTOR PROTECTION

A Contactor Does Not Replace Motor Protection

A magnetic contactor switches motor power. A motor protection relay monitors conditions such as current and signals the control circuit through its output contacts when a protection threshold is reached.

Detection and Stopping Must Form One Complete Circuit

Monitor motor conditions → relay trips → control circuit responds → contactor opens. This illustrates the functional sequence; actual wiring must follow the model-specific diagram.

A trip indication alone does not prove the motor has stopped. Confirm that relay outputs are correctly connected to the control circuit. Coordinate short-circuit protection with breakers/fuses and consider the complete protection system already installed.

02 / MOTOR PROTECTION

Comparing DMPi, IMP and MMP

Choose by the protection, measurement, control and communication functions required, rather than simply ranking the series from basic to premium. Features also vary by detailed model.

DMPi SERIES

Digital Protection with Current Display

LS DMPi vs IMP vs MMP: Motor Protection Relay Guide — original reference image 1

DMPi offers three-phase current indication, fault-cause display, operating-time management and integrated or separate display arrangements. Options include RS-485 Modbus or 4–20 mA output, so it is more than a protection-only device.

Selection: check ground-fault detection, connection arrangement, display mounting and communication/output options in the full model code.

IMP SERIES

Protection Characteristics and Fault History

LS DMPi vs IMP vs MMP: Motor Protection Relay Guide — original reference image 2

IMP provides thermal inverse-time, inverse-time and definite-time characteristics, fault causes with date records, operating-time management and Modbus/RS-485 communication. Consider it where tracing trip causes matters as well as protection.

Selection: check current range, CT arrangement, required protection characteristic and communication specification. Choose it for its functions, not simply because it appears above DMPi in a lineup.

MMP SERIES

Add Measurement and Control to Motor Protection

LS DMPi vs IMP vs MMP: Motor Protection Relay Guide — original reference image 3

MMP supports motor protection together with starting methods and remote monitoring/control. Variants include MMP-C current type, MMP-S selective ground-fault type, MMP-P power type and MMP-IR insulation-resistance type.

Selection: voltage/power measurement and insulation-resistance functions are not included in every model. Define the required functions first, then select the variant.

For local panel monitoring, compare display and protection features first. Add communication for centralized monitoring, or select a model with voltage/power measurement when those values are needed.

03 / MOTOR PROTECTION

Selection Requires More Than Motor kW

Five Details to Check

① Motor nameplate: voltage, rated current and power.
② Starting method: direct-on-line, star-delta, VFD, etc.
③ Relay supply: control voltage and AC/DC.
④ Sensing arrangement: direct input, feed-through, external CT or ZCT.
⑤ Management needs: display, communication, analog output and control.

Motors with the same kW can have different rated currents depending on voltage and specifications. Send a nameplate photo showing voltage and current as well as power.

For replacements, check the full existing model and terminal photos. Similar appearance does not establish compatibility of control supply, contacts, CT/ZCT inputs or display cables. VFD applications also require the manufacturer's conditions for location and operating frequency.

04 / MOTOR PROTECTION

Distinguish Three Circuits During Installation

First is the current-measurement circuit. For feed-through models, check conductor direction and number of passes; for external CT models, check CT specifications and ratio. In star-delta circuits, current differs depending on whether sensing is on the line or inside the delta, so the setting must reflect CT location.

Second is the relay's operating supply. It may differ from motor main-circuit voltage. Compare the product label with the wiring diagram rather than relying on terminal names alone.

Third is the trip-output/control circuit that stops the motor. Check output-contact operation together with the contactor coil circuit. Never route motor main current through the relay's auxiliary contacts.

When Using Ground-Fault Protection

Check whether the ZCT is integrated or external, and identify the specified external ZCT. A CT measures phase current; a ZCT detects zero-sequence current. They are not interchangeable.

05 / MOTOR PROTECTION

Initial Setup and Checks

The following is a common commissioning framework. Buttons and menus vary by model/version. In particular, do not assume older DMP FUNC/SEL/STO instructions apply unchanged to every DMPi.

1. Compare Nameplates and Wiring While Stopped

Check motor rating, relay supply, current range, CT/ZCT and trip circuit. Isolate and verify no voltage before wiring; prevent unexpected starting during configuration.

2. Match CT Configuration and Rated Current

On supported external-CT models, match the actual CT ratio to the relay setting. A 100/5 A CT has a ratio of 20, but check whether the menu asks for ratio or primary rated current. Also account for CT location when setting current.

3. Set Starting Time and Protection Characteristics

Use the motor's acceleration time and load characteristics to set supported starting delay, trip time and inverse/definite-time functions. Starting delay does not disable every protection function. Do not simply increase current or delay to suppress trips.

4. Configure Protection, Reset and Communication

Review phase loss, imbalance, phase reversal, undercurrent and ground-fault functions for the application. Assess whether automatic reset could cause an automatic restart. Match communication address, speed and format to the connected equipment.

5. Save, Test and Verify Actual Operation

Save and reread settings. Follow the manufacturer's test procedure to verify relay outputs and contactor response, then record phase currents and starting time during controlled commissioning. A TEST button alone does not validate all sensing and wiring.

06 / MOTOR PROTECTION

Repeated Trips? Record the Cause Before RESET

Resetting immediately can erase useful clues. Photograph the trip display and record the time and operating state, including whether the fault occurred just after starting or after prolonged running.

Stops Immediately After Starting

Compare starting time and settings; check phase sequence, phase loss and mechanical restraint. Examine actual starting current and load before assuming a setting problem.

Overcurrent During Operation

Check real overload, bearings/pump/fan condition, supply voltage, phase currents, CT ratio and settings.

Phase Loss, Imbalance or Ground Fault

Inspect supply, fuses, contactor contacts, wiring and load. For ground faults, check insulation and ZCT arrangement. Do not continue operating by disabling protection.

Interpret codes using the specific model manual. Reset only after removing the cause and confirming restart is appropriate. Repeated trips call for circuit and load checks, not an immediate assumption that the relay is faulty.

07 / MOTOR PROTECTION

Send Product and Application Details Together

For new selection, provide the motor nameplate, starting method, control voltage and required protection/communication. For replacement, add the full model, terminal photos and wiring diagram. For a separate display, include mounting location and cable requirements.

2SK

Choose Protection That Fits Your Motor

Contact us for LS EMPR information and a quotation based on your quantities and configuration.

Product information and quotations ↗ Korea: 1833-7728

Email 2sk@2sk.co.kr
Fax 031-479-3585

This guide covers selection and common operating procedures. Functions, terminals and setting ranges depend on the detailed model. Qualified electrical personnel must wire and commission using the current model manual and site design.

LS DMPi vs IMP vs MMP: Motor Protection Relay Guide — original reference image 4

References: LS ELECTRIC official product information and catalogues
DMPi reference · IMP reference · MMP reference

Compare LS ELECTRIC DMPi, IMP and MMP motor protection relays. 2SK explains selection, wiring checks, initial settings, commissioning and trip troubleshooting.

#DMPi #IMP #MMP #EMPR #MotorProtectionRelay #LSELECTRIC #2SK

English edition by 2SK. Original catalogue/reference images are retained; some labels within images are in Korean. Read the original Korean article

2SK Tech Blog

E.mail. 2sk@2sk.co.kr  Tel.1833-7728  Fax.031-479-3585


Company Name: 2SK 

Business Registration No.: 657-76-00077


Store: #16-111, Anyang International Distribution Complex, 92 LS-ro, Dongan-gu, Anyang-si, Gyeonggi-do, Postal Code 14771, Republic of Korea

Office: Room 503, Building B, Geumjeong Station 3rd SK V1 Center, 91 LS-ro 116beon-gil, Dongan-gu, Anyang-si, Gyeonggi-do, Republic of Korea

Factory: 1F, 27 Heongan-daero 49beon-gil, Dongan-gu, Anyang-si, Gyeonggi-do, Republic of Korea


CEO: Shin Jae-woon


Mail-Order Business License: No. 2017-Anyang Dongan-0311

Retail Webpage: https://2sk.co.kr

Copyright: Copyright ⓒ 2SK SOLUTION. All rights reserved.


MON-FRI · AM 09:00 ~ PM 05:00
LUNCH · PM 12:00 - PM 01:00
SAT.SUN.HOLIDAY OFF