LS EMPR TOR Series
LS EMPR: Features of the MMP Series
Welcome to 2SK.
This article takes a closer look at the MMP series of LS electronic motor protection relays.
MMP model designation
Product description: intelligent electronic motor protection relay
English designation: Digital Electric Motor Protector Relay
Product family: electronic motor protection relays
Product features
• Comprehensive digital motor protection using an MCU (microprocessor control unit)
Real-time data processing with high precision.
• Application in VFD circuits
The source specifications describe high harmonic-noise immunity and application on the secondary side of VFD-controlled circuits, subject to the manufacturer's application requirements.
The stated operating frequency range is 10–400 Hz. The source specifies a harmonic filter where harmonic content is 30% or higher.
The stated application conditions require this relay's ground-fault function to be disabled; the installation's required ground-fault protection must still be provided by an appropriate arrangement. Confirm the exact model and manufacturer's instructions before applying this configuration.
• Fault-event memory
Stores up to five motor fault events to help review fault history.
• Communications: RS-485 Modbus and 4–20 mA output supported simultaneously
Standard RS-485/Modbus supports networking with a range of systems. The 4–20 mA analog output can also interface with existing systems that use transducers.
• Multiple reset methods
Manual, automatic and electrical reset options are provided.
• Date and time information
Fault date and time are stored to identify exactly when a motor fault occurred.
• Password protection
A password can be required before settings may be changed.
• Total running hours and operating-hour setpoint
An indication is provided when the configured running time has elapsed, helping schedule bearing replacement and lubrication.
Metering and functions vary by model: voltage, current, zero-sequence current, negative-sequence current, active/reactive power, active/reactive energy, power factor, voltage/current harmonics, insulation resistance, motor temperature and motor ON/OFF control.
| Category | Function | MMP-C (current) | MMP-S (selective ground fault) | MMP-P (power) | MMP-IR (insulation resistance) |
| Current protection | Overcurrent | ● | ● | ● | ● |
| Locked rotor | ● | ● | ● | ● |
| Stall | ● | ● | ● | ● |
| Phase loss | ● | ● | ● | ● |
| Unbalance | ● | ● | ● | ● |
| Negative-sequence overcurrent | ● | ● | ● | ● |
| Undercurrent | ● | ● | ● | ● |
| Ground fault (zero-sequence current) | ● | ● | ● | ● |
| Ground fault (residual current) | ● | ● | ● | ● |
| Instantaneous | ● | ● | ● | ● |
| Selective ground fault | - | ● | - | - |
| Voltage protection | Overvoltage | - | - | ● | - |
| Undervoltage | - | - | ● | - |
| Voltage phase loss | - | - | ● | - |
| Voltage unbalance | - | - | ● | - |
| Negative-sequence overvoltage | - | - | ● | - |
| Ground-fault overvoltage | - | ● | - | - |
| Power protection | Overpower | - | - | ●(Alarm) | - |
| Underpower | - | - | ●(Alarm) | - |
| High power factor | - | - | ● | - |
| Low power factor | - | - | ● | - |
| Additional functions | Insulation resistance | - | - | - | ● |
| Motor temperature | - | - | - | ● |
Metering functions
| Measured quantity |
| Display range | Accuracy (%) | Notes |
| Voltage (V) |
| 0.00V ~ 9999V | ±1.0% | Single phase: phase voltage; three phase: line-to-line voltage |
| Current (A) |
| 0.00A ~ 9999A | ±1.0% | Current in each phase |
| Zero-sequence current (In) |
| 0.00A ~ 9999A | ±3.0% | - |
| Negative-sequence current (I2) |
| 0.00A ~ 9999A | ±3.0% | - |
| Active power (W) |
| 0.00A ~ 999.9MW | ±1.0% | Displayed for the forward direction |
| Reactive power (var) |
| 0.00A ~ 999.9MVAR | ±1.0% | Displayed for the forward direction |
| Active energy (Wh) |
| 0.00A ~ 999.9MWH | ±1.0% | - |
| Reactive energy (varh) |
| 0.00A ~ 999.9MVARH | ±1.0% | - |
| Power factor (PF) |
| -1.00~1.00 | ±0.03 | cosθ |
| Voltage harmonics (%) |
| 0~100% | ±5.0% | Odd harmonics within the 2nd–16th order range |
| Current harmonics (%) |
| 0~100% | ±5.0% | Odd harmonics within the 2nd–16th order range |
| Insulation resistance |
| 0.2㏁~50㏁ | ±10% | - |
| Motor temperature |
| -50℃~200℃ | ±10% | - |
Two notable features of the MMP series
• Selective ground-fault protection
In an ungrounded system, a ground fault causes zero-sequence current in healthy feeders to flow from the load toward the supply, while the faulted feeder's current flows toward the load. The relay determines current direction relative to zero-sequence voltage to selectively trip the faulted feeder.


As illustrated, the faulted feeder (Feeder 1) and healthy feeders have opposite current directions. This difference allows selective protection.
For a fault on another feeder, only the protected feeder's charging current flows, in the opposite direction to a local fault, so the element remains inactive. Ground-fault current in an ungrounded system consists of line charging current and any current through a limiting resistor. Since the current is relatively small, zero-sequence CT detection is used. A model with an integrated ZCT simplifies the installation.
• Replacement option for the discontinued IMC-III
The source identifies the MMP series as the replacement family for LS IMC-III MCC products. Check wiring, functions and installation requirements for the specific replacement.
| IMC-III series (discontinued) | MMP series (replacement family) |
|---|
| Discontinued product | Replacement product |
|---|
IMC-III NO AC220V 50/60Hz IMC-IIIa NO AC220V 50/60Hz | ▶ | MMP-CB-10A AC220V 50/60Hz MMP-CB-100A AC220V 50/60Hz
|
IMC-III NO AC110V 50/60Hz IMC-IIIa NO AC110V 50/60Hz | ▶
| MMP-CB-10A AC110V 50/60Hz MMP-CB-100A AC110V 50/60Hz
|
IMC-III A420 AC220V 50/60Hz IMC-IIIa A420 AC220V 50/60Hz
| ▶ | MMP-CM-10A AC220V 50/60Hz MMP-CM-100A AC220V 50/60Hz
|
IMC-III A420 AC110V 50/60Hz IMC-IIIa A420 AC0V 50/60Hz | ▶ | MMP-CM-10A AC110V 50/60Hz MMP-CM-100A AC110V 50/60Hz
|
IMC-III M485 AC220V 50/60Hz IMC-IIIa M485 AC220V 50/60Hz | ▶ | MMP-CM-10A AC220V 50/60Hz MMP-CM-100A AC220V 50/60Hz
|
IMC-III M485 AC110V 50/60Hz IMC-IIIa M485 AC110V 50/60Hz | ▶ | MMP-CM-10A AC220V 50/60Hz MMP-CM-100A AC220V 50/60Hz
|
English edition by 2SK. Original catalogue/reference images are retained; some labels within images are in Korean. Read the original Korean article
LS EMPR TOR Series
LS EMPR: Features of the MMP Series
Welcome to 2SK.
This article takes a closer look at the MMP series of LS electronic motor protection relays.
MMP model designation
Product description: intelligent electronic motor protection relay
English designation: Digital Electric Motor Protector Relay
Product family: electronic motor protection relays
Product features
• Comprehensive digital motor protection using an MCU (microprocessor control unit)
Real-time data processing with high precision.
• Application in VFD circuits
The source specifications describe high harmonic-noise immunity and application on the secondary side of VFD-controlled circuits, subject to the manufacturer's application requirements.
The stated operating frequency range is 10–400 Hz. The source specifies a harmonic filter where harmonic content is 30% or higher.
The stated application conditions require this relay's ground-fault function to be disabled; the installation's required ground-fault protection must still be provided by an appropriate arrangement. Confirm the exact model and manufacturer's instructions before applying this configuration.
• Fault-event memory
Stores up to five motor fault events to help review fault history.
• Communications: RS-485 Modbus and 4–20 mA output supported simultaneously
Standard RS-485/Modbus supports networking with a range of systems. The 4–20 mA analog output can also interface with existing systems that use transducers.
• Multiple reset methods
Manual, automatic and electrical reset options are provided.
• Date and time information
Fault date and time are stored to identify exactly when a motor fault occurred.
• Password protection
A password can be required before settings may be changed.
• Total running hours and operating-hour setpoint
An indication is provided when the configured running time has elapsed, helping schedule bearing replacement and lubrication.
Metering and functions vary by model: voltage, current, zero-sequence current, negative-sequence current, active/reactive power, active/reactive energy, power factor, voltage/current harmonics, insulation resistance, motor temperature and motor ON/OFF control.
Control functions
Metering functions
Two notable features of the MMP series
• Selective ground-fault protection
In an ungrounded system, a ground fault causes zero-sequence current in healthy feeders to flow from the load toward the supply, while the faulted feeder's current flows toward the load. The relay determines current direction relative to zero-sequence voltage to selectively trip the faulted feeder.
As illustrated, the faulted feeder (Feeder 1) and healthy feeders have opposite current directions. This difference allows selective protection.
For a fault on another feeder, only the protected feeder's charging current flows, in the opposite direction to a local fault, so the element remains inactive. Ground-fault current in an ungrounded system consists of line charging current and any current through a limiting resistor. Since the current is relatively small, zero-sequence CT detection is used. A model with an integrated ZCT simplifies the installation.
• Replacement option for the discontinued IMC-III
The source identifies the MMP series as the replacement family for LS IMC-III MCC products. Check wiring, functions and installation requirements for the specific replacement.
IMC-IIIa NO AC220V 50/60Hz
MMP-CB-100A AC220V 50/60Hz
IMC-IIIa NO AC110V 50/60Hz
MMP-CB-100A AC110V 50/60Hz
IMC-IIIa A420 AC220V 50/60Hz
MMP-CM-100A AC220V 50/60Hz
IMC-IIIa A420 AC0V 50/60Hz
MMP-CM-100A AC110V 50/60Hz
IMC-IIIa M485 AC220V 50/60Hz
MMP-CM-100A AC220V 50/60Hz
IMC-IIIa M485 AC110V 50/60Hz
MMP-CM-100A AC220V 50/60Hz
2SK EMPR Pages
2SK Retail MC Page > 2SK Retail EMPR Page >
Send your model number, motor nameplate and required quantity to 2SK.
Request a quotation →Email 2SK →#MMP #SmartMotorProtection #EMPR #GroundFaultProtection #LSELECTRIC #2SK
Model-column names were checked against the LS ELECTRIC MMP comparison: MMP-C, MMP-S, MMP-P and MMP-IR.
English edition by 2SK. Original catalogue/reference images are retained; some labels within images are in Korean. Read the original Korean article